84
Setting Data Links
Section 5-2
Note
1.
The total number of words in data link send and receive areas must not ex-
ceed 12,000 per node.
2.
The following values must be satisfied for each node for the data link Area
1 and Area 2 so that the final word in the data link does not go beyond the
last word in the PLC memory area.
(Data link start word – 1) + (Total number of send/receive
words in Area 1 or Area 2)
≤
6143 (CIO Area)
199 (LR Area)
32767 (DM Area, EM Area)
Area 1
Data link
start word
CIO Area: CIO 000 to CIO 6143
LR Area: LR 00 to LR 199 (*)
DM Area: DM 0000 to DM 32767
EM Area: Banks 00 to 12, EM 0000 to EM 32767
The same area cannot be set for both Area 1 and Area 2. Set
different areas.
*:
When a word between LR 000 and LR 199 is specified, the
data link area will be allocated between CIO 1000 and
CIO 1199.
Number of
words
Remote nodes: 0 to the number of source words
Set the number of words to be received.
Local node:
0 to 1,000
Set the number of words to be transmitted.
The total number of words in Area 1 and Area 2 in each node
must not exceed 1,000.
The numbers of words in both Area 1 and Area 2 in each node
must not be set to 0.
Offset
Remote nodes: 0 to one less than number of source words
Set the offset for the data to be received.
Local node: Cannot be set.
This setting is not required if an offset is not used.
Area 2
Data link
start word
CIO Area:
CIO 000 to CIO 6143
LR Area:
LR 00 to LR 199 (*)
DM Area:
DM 0000 to DM 32767
EM Area :
Banks 00 to 12, EM 0000 to EM 32767
(EM must be installed)
The same area cannot be set for both Area 1 and Area 2. Set
different areas.
*:
When a word between LR 000 and LR 199 is specified, the
data link area will be allocated between CIO 1000 and
CIO 1199.
Number of
words
Remote nodes: 0 to the number of source words
Set the number of words to be received.
Local node:
0 to 1,000
Set the number of words to be transmitted.
The total number of words in Area 1 and Area 2 in each node
must not exceed 1,000.
The numbers of words in both Area 1 and Area 2 in each node
must not be set to 0.
Offset
Remote nodes: 0 to one less than number of source words
Set the offset for the data to be received.
Local node:
Cannot be set.
This setting is not required if an offset is not used.
Setting item
Setting range
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...