232
Error Log
Section 10-3
3.
Error codes 021E through 0223 are recorded for Optical Ring Controller
Link Units/Boards only.
4.
Error Status:
The status of each bit indicates that an error has occurred as given in the
diagram below.
5.
Ring Status:
The network disconnection information is indicated as shown in the dia-
gram below.
10-3-3 Reading and Clearing Error Logs
Error logs can be read or cleared using the Controller Link Support Software,
the CX-Programmer, PLC Programming Devices, or the message service.
The following examples are for the Controller Link Support Software and the
message service. When using a PLC Programming Device, refer to the Pro-
gramming Device’s operation manual for details.
Controller Link Support Software
Read or clear the error log using the following procedure.
1,2,3...
1.
Display the Main Menu.
2.
Select “E: Error log.”
3.
Designated the node. The error log for the designated node will be dis-
played.
1: Token timeout error
1: Polling timeout error
1: Communications controller hardware error
1: Polling node was changed
1: Nodes in Network changed (added or removed)
1: Communications controller send error
1: Node address duplication error
Node address of disconnected node
(00 Hex: No disconnected nodes detected.)
Disconnected Interface Flag
0: SL1 (uplink) or normal status
1: SL2 (downlink)
Disconnected node
information #2
(See note.)
Local Node Disconnection Flag
0: Normal
1: Disconnection detected
Node address of disconnected node
(00 Hex: No disconnected nodes detected.)
Disconnected Interface Flag
0: SL1 (uplink) or normal status
1: SL2 (downlink)
Disconnected node
information #1
(See note.)
Network Disconnection Flag
0: Normal
1: Disconnection detected
Note The disconnected node information is valid only when bit 15 (the Network
Disconnection Flag) is ON. If bit 15 is OFF, the earlier disconnected node
information is retained.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...