98
Setting Data Links
Section 5-2
2.
The following limitations apply when Optical Bus (CLK11) and Optical Ring
(H-PCF cable) (CLK12 or CLK12-V1) Controller Link Units are used in
combination.
• The data that can be received by the Optical Bus Controller Link Units
is limited to node addresses 1 to 32, and the data link status that is re-
flected is also limited to these node addresses.
• When data links are set automatically, and an Optical Ring Controller
Link Unit is used as the startup node, register the participating nodes
within the range of node addresses 1 to 32. If a node address of 33 or
higher is included, a data link table setting error will be generated at
the Optical Ring Controller Link Unit.
• When setting data links manually, the receiving nodes that are set in
the Optical Bus Controller Link Unit data link table must be within the
range of node addresses 1 to 32. If a node address of 33 or higher is
included, a data link table setting error will be generated at the Optical
Bus Controller Link Unit.
5-2-5
Automatic Setting Example
This section shows an example of DM parameter area settings and the data
link areas that are created as a result.
DM Parameter Area Settings
Set the parameters in the startup node as follows:
Data link mode: Automatic
First data link status word: IR 310
Participating nodes: #1, #2, and #3
Area 1 data link start word: LR 00
Number of words: 10
Area 2 data link start word: DM 1000
Number of words: 200
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...