177
Precautions for Duplex Systems
Section 8-4
• Basically, the maximum number of CS-series CPU Bus Units that can be
mounted to a single CS1D PLC (including Expansion Racks) is 16. This is
because unit numbers are restricted to the range 0 to 15. For this reason,
standby Controller Link Units that have the same unit number as an active
Controller Link Unit are not included in this figure. (For example, if there
are 3 pairs of Duplex Units, the maximum number of mountable Units is
19.)
• CX-Programmer Ver. 3.0 or later is required to make settings for Duplex
Units.
• Although standby Controller Link Units do not participate in the network
as nodes, they are physically connected to the network and so they are
included in the figure for the maximum number of connectable Units. For
this reason, up to a total of 62 active and standby Controller Link Units
can be connected. Therefore, if all the nodes are used in the CS1D Sys-
tem, with all the Controller Link Units used in duplex operation, the maxi-
mum number of nodes is 31 (62
−
Number of standby Controller Link
Units).
• It is also possible to use only some of the Units in the Controller Link Net-
work in duplex operation. In this case, up to a total of 62 active and
standby Controller Link Units and Controller Link Units that are not used
in duplex operation can be connected. The Units that are not used in
duplex operation can include both existing Units (CS1W-CLK12, CS1W-
CLK52, CVM1-CLK12, or CVM1-CLK52) and duplex-compatible Units.
• As long as they are mounted on the same PLC, two Controller Link Units
used in duplex operation can be mounted on different Racks or in non-
adjacent slots.
1 pair of Units
3 Units
1 active Unit + 1 standby Unit + 3 Units =
5 Units in total
None
4 Units
0 active Units + 0 standby Units + 4 Units =
4 Units in total
Used in duplex
operation
Not used in
duplex
operation
Maximum number of mountable Units
Active Controller Link Units
Standby Controller Link Units
In 1 network, a total of up to 62 active and standby
Controller Link Units can be connected (31 nodes).
Only some Controller Link Units
are used in duplex operation.
(CS1D CPU Unit used.)
Controller Link Units are not used in
duplex operation.
(CPU Unit does not have to be CS1D.)
Controller Link Units
that are either active
or not used in duplex
operation
Standby Controller
Link Units
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...