220
Status Area and Troubleshooting
Section 10-2
Network Participation Status: CIO 1500 + 25 x
(Unit No.) + 2 to + 5
Local Data Link Participation Status: CIO 1500 + 25 x
(Unit No.) + 6
Note Data link status is valid only when the local node is participating in the data
link. Confirm that the Local Data Link Active Bit is ON before referencing the
data link status.
Data Link Status: CIO 1500 + 25 x
(Unit No.) + 7 to + 22
8 Bit Format Specified
The numbers in the squares correspond to node addresses.
The bit status indicates each node's participation status as follows:
0: Not part of the network
1: Part of the network
Note When the local node is not part of the network, the local
node's participation status bit will be 0. The participa-
tion status of other nodes will not be reliable in this
case.
−
: Not used
1: Local node data link participating
0: Local node data link not participating or data link
inactive
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error
0: Normal
1: Error
Error: Offset exceeds
number of send words.
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.
Remaining receive area
0: Not remaining
1: Remaining
Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.
Note When a data link with node addresses
higher than 32 is required, specify the
beginning storage word rather than us-
ing the default.
(In this case, a 31 word area is used
when the 8-bit format is specified.)
Node 2
Node 4
Node 6
Node 8
Node 12
Node 14
Node 16
Node 18
Node 22
Node 24
Node 26
Node 28
Node 1
Node 3
Node 5
Node 7
Node 11
Node 13
Node 15
Node 17
Node 21
Node 23
Node 25
Node 27
+7
+8
+21
+22
+20
+19
+18
Node 10
Node 20
Node 9
Node 19
Node 30
Node 29
Node 32
Node 31
+16
+17
+15
+14
+13
+12
+11
+10
+9
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...