32
Data Links Procedures
Section 2-1
2-1
Data Links Procedures
2-1-1
Manually Setting Data Links
When the data link mode is set for manual data link table creation, the data
link tables can be input using the Controller Link Support Software or CX-Pro-
grammer. Use the following procedure.
1,2,3...
1.
Install and wire the Units.
2.
Prepare for communications.
Note When using Controller Link Units in duplex operation, set the same unit num-
ber and node address for both Units.
3.
Turn ON the power to the PLC.
4.
Connect the Programming Device.
5.
Make duplex settings for Communications Units. Create I/O tables.
Note When I/O tables for configurations with Communications Units used in duplex
operation are created, the Unit with the lower slot number will be designated
as the active Unit and the Unit with the higher slot number will be designated
as the standby Unit. To reverse this designation, edit the I/O tables offline and
transfer them to the PLC.
Contents
Method
Nodes
Page
• Mount the Units to the
PLCs.
---
All nodes
• Wire the Network.
---
All nodes
Contents
Method
Nodes
Page
• Set the unit number.
(See note.)
Use the front rotary
switches.
All nodes
• Set the node address.
(See note.)
Use the front rotary
switches.
All nodes
Contents
Method
Nodes
Page
Turn ON the power to
the PLC.
---
All nodes
---
Contents
Method
Nodes
Page
Connect the Program-
ming Device.
Note
A Programming
Console can be
used if there is
no duplex opera-
tion.
Use the special connec-
tion cable.
All nodes
Contents
Method
Nodes
Page
Make duplex settings for
Communications Units
(in PLC Setup).
Use the Programming
Device.
Duplex nodes
Input the I/O tables.
(See note.)
Use the SYSMAC Sup-
port Software or Pro-
gramming Console.
All nodes
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...