Procedure for Using Duplex Units
Section 8-3
Note If I/O tables cannot be created, check the following items.
1) In the PLC Setup’s duplex settings, make the Communications
Unit duplex setting for the corresponding unit number. Also, after
transferring the PLC Setup settings, reset the CS1D’s power
supply to enable the settings.
2) Set the same unit number for the two Duplex Units.
3) Set the same node address for the two Duplex Units.
4) Use duplex-compatible Units (e.g., the CS1W-CLK12-V1 or
CS1W-CLK52-V1). The CS1W-CLK12 and CS1W-CLK52 can-
not be used in duplex operation.
5) Complete online replacement if the procedure has not been
completed.
6) If there is an error in the CPU Unit, remove the cause of the error.
7.
Perform wiring for the backup (24-V) power supply cable.
Note Use a backup power supply with duplex communications systems.
By providing a backup power supply, the node bypass circuits in the
Controller Link Unit will operate, and the influence on the network of
active/standby switchover and online replacement can be reduced to
a minimum.
8.
Turn OFF the power supply, and perform wiring for the fiber-optic cable.
When using an H-PCF cable, connect the two Duplex Controller Link Units
using either a CS1D-CN051 Connecting Cable or a standard H-PCF cable.
Duplex Unit Connecting Cable (H-PCF Cable)
Name: Duplex Unit Connecting Cable (H-PCF Cable)
Length: 50 cm
Model number: CS1D-CN051
Note If a GI cable is used to connect the Units, use a standard GI cable. Take note,
however, of the following points.
1.
Use a GI cable of length at least 50 cm.
CS1D-CN051 Duplex
Unit Connecting Cable
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...