211
Troubleshooting Using Indicators
Section 10-1
Troubleshooting with LNK and M/A Indicators
Data Link Cannot be Started
The following table describes the LNK and M/A indicators at the startup node
and their use in troubleshooting when a data link cannot be started.
Starting a data link depends on the Controller Link Unit operating normally
and participating in the Network. Refer to Troubleshooting with RUN, ERC,
ERH and INS Indicators earlier in this section and check Unit operation before
using the following table.
Lit
---
---
---
---
Not lit ---
---
Cables are not
connected cor-
rectly.
Check the cable
connections are
reconnect cor-
rectly.
The node address
is larger than the
maximum node
address set in the
network parame-
ters.
Either change the
maximum node
address setting
with the Controller
Link Support Soft-
ware (Ver. 2.00 or
higher) or set a
node address
below the maxi-
mum.
No other nodes
exist.
Make sure that 2 or
more nodes exist
within the Network.
No node has been
set as the polling
node.
Refer to 9-1-2 Set-
ting the Polling and
Polled Nodes and
set the Controller
Link Unit as the
polling node.
(If both types of
optical Units are
used in a network,
use the Optical
Ring Units as
polled nodes.)
The transmission
path format setting
is different in the
polling node.
Change the set-
ting to match the
one in the polling
node and turn the
power ON again.
---
---
---
---
Flashing
Lit
Ring status:
Bit 15 ON
Error information:
Bit 15 ON
021E Hex
A break was
detected in the net-
work cable. (Net-
work operation
continues.)
Determine the
location of the
break with the
Controller Link
Support Software
(Ver. 2.00 or
higher) or the ring
status word. Cor-
rect the break.
Refer to 10-4
Locating and Cor-
recting Cable Dis-
connections for
details.
---
---
---
---
Flashing
Not lit Ring status:
Bit 15 ON
Error information:
Bit 15 ON
021E Hex
A break was
detected in the net-
work cable. (The
Unit was out of the
network after the
error.)
Indicators
Status area
Error
code
Probable cause
Probable remedy
RUN
P/S
ERC
ERH
RING
INS
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...