228
Error Log
Section 10-3
0101
Hex
Transmission failed; local node
not in Network
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Refer to page 202
Troubleshooting
Using Indicators and
place the local node
into Network.
No
CV, CS
0103
Hex
Transmission failed; retry count
exceeded
Using the Controller
Link Support Soft-
ware or FINS com-
mands, run
echoback test and
check operating envi-
ronment if errors
occur.
No
CV, CS
0104
Hex
Transmission failed; maximum
number of frames exceeded.
Reduce the number
of events per com-
munications cycle or
increase the maxi-
mum number of net-
work parameter
frames.
No
CV, CS
0105
Hex
Transmission failed; node
address incorrect
Refer to 4-1 CS-
series Optical Ring
Controller Link Units
or and check node
address settings to
be sure they are
within range and
unique.
No
CV, CS
0106
Hex
Transmission failed; redundant
node address
Correct node
addresses so that
they are unique
within the same Net-
work.
No
CV, CS
0107
Hex
Transmission failed; destination
node not in Network
Refer to 10-1 Trou-
bleshooting Using
Indicators and place
destination node into
Network.
No
CV, CS
0108
Hex
Transmission failed; specified
Unit does not exist
Refer to 4-2 CVM1
and CV-series Opti-
cal Ring Controller
Link Units and check
unit address and unit
number of destina-
tion.
No
CV, CS
Error
code
Contents
Detail code
Correction
Written to
EEPROM
Applicable
PLC
1st byte
2nd byte
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...