191
Data Link I/O Response Time
Section 9-3
CS-series PLCs, CVM1
and CV-series PLCs in
Synchronous Mode
When a CS-series, CVM1, or CV-series PLC is operating in synchronous
mode, data exchange with the Controller Link Unit is executed as interrupt
processing during peripheral processing for the PLC cycle. Data exchange
timing is as follows:
If interrupt processing for data exchange is executed, the PLC cycle time will
be lengthened by the time required for the interrupt processing (see 9-3-2
Data Processing Time below).
9-3-2
Data Processing Time
The time required for interrupt processing for data exchange (data processing
time) can be roughly estimated as shown in the following table.
The number of words processed in a single data exchange is shown in the fol-
lowing table for each series of PLC. If the number of data link words exceeds
the value shown in the table, data exchange will be executed as several sepa-
rate processes.
Note
1.
Use the above equations only if only one Controller Link Unit is mounted
on the PLC. If other CPU Bus Units are mounted on the PLC, obtain the
refresh times for each CPU Bus Unit and add to the above equations.
2.
The execution of some items takes precedence over data link area refresh-
ing. For example, data link area refreshing will not take place during exe-
cution of the SEND(192), RECV(193), or FAL(006) instruction.
PLC cycle time
Execution
PLC processing
Basic processing
Interrupt processing
for data exchange
Execution
I/O refreshing
Basic processing
CPU Bus
Unit service
Programming
Device/Host Link
service
Data link scale
Equation for estimating data processing time
Data link is established for both areas 1 and 2
0.001
×
Total number of data link words
+
1.7 (ms)
Data link is established for only area 1 or area 2
0.001
×
Total number of data link words
+
1.4 (ms)
PLCs
Words per data exchange
CS-series PLCs
Approx. 7,800 words
CVM1 and CV-series PLCs
Approx. 3,700 words
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...