131
Commands and Responses for Controller Link Units
Section 6-5
Response Block
Parameters
Model number, version (response): The Controller Link Unit’s model num-
ber and version are returned as shown below, each 20 characters in ASCII
code. If fewer than 20 bytes of data are used, 20 (Hex) (i.e., spaces) will be
returned for the remaining bytes. In the version numbers shown below, the
spaces are represented by boxes (
@
).
Model number
Optical Ring Controller Link Unit for CVM1/CV-series PLCs:
(H-PCF cable) CVM1-CLK12
@@@@@@@@@@
(GI cable)
CVM1-CLK52
@@@@@@@@@@
Optical Ring Controller Link Unit for CS-series PLCs:
(H-PCF cable) CS1W-CLK12
@@@@@@@@@@
(GI cable)
CS1W-CLK52
@@@@@@@@@@
Version
V*
@
V*
@
V*
@@@
The leftmost “V*” (*: version) represents the Communications Controller data
link level version number. The middle one represents the Communications
Controller network level version number. The rightmost one represents the
Controller Link Unit version number.
Connection Method (Response)
The connection method parameter for the Controller Link Unit (wired or optical
bus/ring) is configured as follows:
Node address (response): The Controller Link Unit’s node address is
returned between 01 and 3E Hex (1 to 62).
Unit Address (response): The Unit address set for the Controller Link Unit
(10 Hex + Unit number), is returned in hexadecimal. Even when there is a Unit
number setting error, the Unit address is returned.
Network Address: The Controller Link Unit’s network address, as set in the
routing table, is returned in hexadecimal. When the routing table has not been
set, the address becomes 00 Hex.
6-5-5
CONTROLLER STATUS READ
Reads the Controller Link Unit’s controller status.
Command Block
Response
code
Command
code
Model
20 bytes
20 bytes
Version
Node
address
05
01
Wired/
Optical
Unit
address
Network
address
Connection type:
0: Wired
1: Optical bus/ring
−
: Not used
Bit
Maximum number of nodes
00: 32 nodes
01: 62 nodes
Transmission path format
0: Token-bus mode
1: Token-ring mode
Command
code
01
06
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...