150
Response Codes
Section 6-6
26: Command error
01
The specified area is not protected.
This response code will be returned if
an attempt is made to clear protection
on an area that is not protected.
The program area is not protected, so it isn’t
necessary to clear protection.
02
An incorrect password has been speci-
fied.
Specify a password that is registered.
04
The specified area is protected.
Execute the command again after executing
the PROGRAM AREA PROTECT CLEAR
command for the PLC.
The destination has received more
than 5 commands.
Either interrupt servicing or wait for servic-
ing to complete before re-executing the
command.
05
The service is being executed.
Execute the command again after the ser-
vice has been completed or aborted.
06
The service is not being executed.
Execute the service if necessary.
07
The node does not have the right to
execute the service.
Service cannot be executed from local node
because the local node is not part of the
data links. Execute the service from a node
that is part of the data links.
A buffer error has prevented returning a
normal response.
Reset the board. If the error persists,
replace the board.
08
Service cannot be executed because
necessary settings haven’t been made.
Make the necessary settings.
09
Service cannot be executed because
necessary settings haven’t been made
in the command data.
Check the command format of and make
the necessary settings.
0A
The specified action or transition num-
ber has already been registered.
Execute the command again using an
action or transition number that hasn’t been
registered.
0B
Cannot clear error because the cause
of the error still exists.
Eliminate the cause of the error and exe-
cute the ERROR CLEAR command.
30: Access right error
01
The access right is held by another
node.
(Either a Programming Device at the
other node is executing an SFC online
edit, or the other node is executing an
ACCESS RIGHT ACQUIRE or
ACCESS RIGHT FORCED ACQUIRE
command.)
Execute the command again after the
access right has been released.
(The command can be executed after the
ACCESS RIGHT FORCED ACQUIRE or
ACCESS RIGHT RELEASE command is
completed. Releasing the access right
might affect processes in progress at the
node that held the access right.)
40: Abort
01
Command was aborted with ABORT
command.
---
Main code
Sub-
code
Probable cause
Remedy
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...