34
Data Links Procedures
Section 2-1
b) The data links will not start if there is an error in the data link tables
in the startup node.
9.
Stop the data links.
Note Data link Start/Stop Bit (N= unit number):
CS Series:
Word 0 of D 100
×
N
CVM1/CV Series: Word 0 of DM 2000 + 100
×
N
2-1-2
Automatically Setting Data Links
Data link tables can be automatically created by setting the data link mode to
automatic data link table creation. Use the following procedure.
1,2,3...
1.
Install and wire the Units.
2.
Prepare for communications.
Note When using Controller Link Units in duplex operation, set the same unit num-
ber and node address for both Units.
3.
Turn ON the power to the PLC.
4.
Connect the Programming Device.
5.
Make duplex settings for Communications Units. Create I/O tables.
Contents
Method
Nodes
Page
Stop the data links.
Switch the Data link Start/Stop
Bit (listed below) from OFF to ON
using either the Programming
Device, the user program, the
Controller Link Support Software
or CX-Programmer.
Any node that is
active in the data
link
Contents
Method
Nodes
Page
• Mount the Units to the
PLCs.
---
All nodes
• Wire the Network.
---
All nodes
Contents
Method
Nodes
Page
• Set the unit number.
(See note.)
Use the front rotary
switches.
All nodes
• Set the node address.
(See note.)
Use the front rotary
switches.
All nodes
Contents
Method
Nodes
Page
Turn ON the power to
the PLC.
---
All nodes
---
Contents
Method
Nodes
Page
Connect the Program-
ming Console or Con-
troller Link Support
Software.
Use the special connec-
tion cable.
All nodes
Contents
Method
Nodes
Page
Make duplex settings for
Communications Units
(in PLC Setup).
Use the Programming
Device.
Duplex nodes
Create the I/O tables.
(See note.)
Use the SYSMAC Sup-
port Software or Pro-
gramming Console.
All nodes
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...