245
Locating and Correcting Cable Disconnections
Section 10-4
Sample Program for CS-series PLCs
• As long as the Network Disconnection Flag (CIO 152315 for unit number
0) is ON, the “node address of the disconnected node” in bits 8 to 13 is
stored in D00000 and the “node address of the disconnected node” in bits
0 to 5 is stored in D00001.
• The contents of D00000 are shifted 8 bits to the right to convert the node
address to a proper hexadecimal value.
• The hexadecimal node addresses stored in D00000 and D00001 are con-
verted to BCD.
Note When using the sample program as written above, be sure that the bits and
words in the sample program are not already being used by the program or
other Special Units.
Sample Program for CV-series PLCs
• As long as the Network Disconnection Flag (CIO 152315 for unit number
0) is ON, the “node address of the disconnected node” in bits 8 to 13 is
Always ON Flag
Always ON Flag
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...