![background image](http://html1.mh-extra.com/html/omron/cs1w-clk12-v1/cs1w-clk12-v1_operation-manual_742356296.webp)
279
CS-series Optical Bus Controller Link Units
Appendix C
The node address can be set to any value between 01 and 32.
Set the node address using a small flat-blade screwdriver, being careful not to damage the rotary switches.
Note 1.
Always turn OFF the PLC’s power before setting the node address.
2.
Do not set the same node address twice within the same Network. An error will occur if the same
address is set for two different nodes. The ERC indicator on the front of the Unit will light (Communi-
cations Error Flag) and either communications will stop, or the INS indicator will not light and you will
be unable to participate in the Network.
3.
The send sequence for the data link areas is determined according to the sequence of node address-
es for automatically set data links.
4.
Assign node addresses consecutively beginning from 01 whenever possible to minimize Network
construction time.
Item
Specifications
Setting method
2-digit decimal
Setting range
01 to 32 (default is 01)
Node
All nodes in the Network
1's digit
10's digit
0
1
Note: The factory default settings are shown above.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...