![background image](http://html1.mh-extra.com/html/omron/cs1w-clk12-v1/cs1w-clk12-v1_operation-manual_742356164.webp)
147
Response Codes
Section 6-6
04: Not executable
01
An undefined command has been
used.
Check the command code and be sure that
the Unit supports it.
02
Cannot process command because the
specified unit model or version is
wrong.
Check the unit model and version.
05: Routing error
01
Remote node address is not set in the
routing table.
Set the remote node address in the routing
table.
02
Routing table isn’t registered.
Set the local nodes, remote nodes, and
relay nodes in the routing table.
03
Routing table error
Set the routing table correctly.
04
The maximum number of relay nodes
(2) was exceeded in the command.
Redesign the network or reconsider the
routing table to reduce the number of relay
nodes in the command.
10: Command format
error
01
The command is longer than the max.
permissible length.
Check the command format of the com-
mand and set it correctly.
02
The command is shorter than min. per-
missible length.
Check the command format of the com-
mand and set it correctly.
03
The designated number of data items
differs from the actual number.
Check the number of items and the data,
and make sure that they agree.
04
An incorrect command format has
been used.
Check the command format of the com-
mand and set it correctly.
05
An incorrect header has been used.
(The local node’s relay table or relay
node’s local network table is wrong.)
Set the routing table correctly.
11: Parameter error
01
A correct memory area code has not
been used or Extended Data Memory
is not available.
Check the command’s memory area code
and set the appropriate code.
02
The access size specified in the com-
mand is wrong, or the first address is
an odd number.
Set the correct access size for the com-
mand.
03
The first address is in an inaccessible
area.
Set a first address that is in an accessible
area.
04
The end of specified word range
exceeds the acceptable range.
Check the acceptable limits of the data area
and set the word range within the limits.
The total number of words exceeds the
acceptable range.
Check the data link tables to be sure the
limit to link words has not been exceeded.
06
A non-existent program no. has been
specified.
Check the program number and be sure
that it is set correctly.
09
The sizes of data items in the com-
mand block are wrong.
Check the command data and be sure that
the sixes of the data items are correct.
A node that is not set as a common link
parameter is in the refresh parameters.
Check the data link tables to be sure all
nodes in the refresh parameters are in the
common link parameters.
0A
The IOM break function cannot be exe-
cuted because it is already being exe-
cuted.
Either abort the current IOM break function
processing, or wait until it is completed and
execute the command.
There are node addresses that have
been set twice.
Check the data link tables for node
addresses that have been set twice.
0B
The response block is longer than the
max. permissible length.
Check the command format and set the
number of items correctly.
0C
An incorrect parameter code has been
specified.
Check the command data and reenter it cor-
rectly.
There is a file error.
Check the data link table file for corruption.
Main code
Sub-
code
Probable cause
Remedy
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...