Troubleshooting Using Indicators
Section 10-1
---
---
Lit
Not lit ---
Not lit Error information:
Bits 12 and 15 ON
021B Hex
Hardware error in
communications
controller.
Replace the Con-
troller Link Unit.
Error information:
Bits 11 and 15 ON
0210 Hex
Error in the com-
munications con-
troller’s transmitter.
Replace the Con-
troller Link Unit.
Lit
---
Lit
---
---
Not lit Error information:
Bits 09 and 15 ON
0211 Hex
The same node
address is being
used by two differ-
ent Units.
Change so that
each node address
in the Network is
unique.
The transmission
path format setting
does not match the
setting in the poll-
ing node.
Change the set-
ting to match the
one in the polling
node and turn the
power ON again.
Lit
---
---
Lit
---
---
Error information:
Bit 15 ON
0001 Hex
An error has
occurred in the
PLC.
Refer to the PLC’s
operation manual
and correct the
error. If the error
occurs again,
replace the PLC.
Error information:
Bits 00 and 15 ON
0203 Hex
There is an error in
the network
parameters stored
in the Controller
Link Unit’s
EEPROM.
Set the network
parameters again.
If the error occurs
again, replace the
Controller Link
Unit.
021A Hex
The network
parameter settings
are incorrect or the
local node address
is larger than the
maximum node
address set in the
network parame-
ters.
Set the network
parameters again.
Error information:
Bits 01 and 15 ON
0203 Hex
There is an error in
the data link tables
stored in the Con-
troller Link Unit’s
EEPROM.
Set the data link
tables again. If the
error occurs again,
replace the Con-
troller Link Unit.
021A Hex
The data link table
settings are incor-
rect.
Set the data link
tables again.
Delete the data link
tables if they aren’t
being used.
Error information:
Bits 02 and 15 ON
0203 Hex
There is an error in
the routing table in
the PLC’s routing
table area.
Set the routing
tables again. If the
error occurs again,
replace the PLC.
021A Hex
Routing table set-
ting error
Set the routing
tables again.
Delete the routing
tables if they aren’t
being used.
Indicators
Status area
Error
code
Probable cause
Probable remedy
RUN
P/S
ERC
ERH
RING
INS
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...