229
Error Log
Section 10-3
0109
Hex
Transmission failed; destination
busy
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Increase number of
retries or reconfig-
ure system to distrib-
ute load.
No
CV, CS
010A
Hex
Transmission failed; communica-
tions controller error
Conduct an echo-
back test and if the
effects of noise are
considerable, recon-
sider the operating
environment. Restart
the Controller Link
Unit. If the error
occurs again,
replace the Unit.
Yes
CV, CS
010B
Hex
Transmission failed; PLC error
Refer to the PLC
operating manual. If
the error occurs
again, replace the
PLC.
No
CV, CS
010C
Hex
Transmission failed; unit number
incorrect
Check unit number
settings to be sure
they are within range
and unique.
No
CV, CS
010D
Hex
Transmission failed; destination
address incorrect
Refer to 7-4 Setting
Routing Tables, and
set a destination
address in the rout-
ing table.
No
CV, CS
010E
Hex
Transmission failed; routing
tables not registered
Refer to 7-4 Setting
Routing Tables, and
set a routing table for
the source node,
destination node,
and relay node.
No
CV, CS
010F
Hex
Transmission failed; routing table
error
Refer to 7-4 Setting
Routing Tables, and
correctly set the rout-
ing table.
No
CV, CS
0110
Hex
Transmission failed; too many
relay points
Check routing tables
and system configu-
ration. Do not try to
access Networks
separated by more
than one other Net-
work.
No
CV, CS
0111
Hex
Transmission failed; command
packet too long
Be sure to use the
FINS command for-
mat.
No
CV, CS
0112
Hex
Transmission failed; header
error.
Be sure to use the
correct FINS com-
mand format.
No
CV, CS
0113
Hex
Transmission failed; I/O setting
error
Check I/O table
accuracy.
No
CV, CS
0114
Hex
Transmission failed; CPU bus
error
Check Unit and cable
connections and
clear error.
No
CV, CS
0115
Hex
Transmission failed; redundant
I/O allocations
Check unit numbers
for redundancy
within the same PLC.
No
CV, CS
Error
code
Contents
Detail code
Correction
Written to
EEPROM
Applicable
PLC
1st byte
2nd byte
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...