225
Error Log
Section 10-3
10-3 Error Log
The error log records errors that occur in the Controller Link Unit and the time
they occur. The error log can be read or cleared using the Controller Link Sup-
port Software, the CX-Programmer, a PLC Programming Device such as the
SYSMAC Support Software, or the message service (FINS commands for the
Controller Link Unit.)
10-3-1 Error Log Table
Errors are recorded in an error log table in the Unit’s RAM, with one record for
each error and a maximum of 39 records.
Errors of significance are also recorded in the Unit’s EEPROM so that when
the power to the Unit is turned OFF or reset, a record of the error will remain.
(The error log table in EEPROM automatically reads the Unit’s RAM when the
power is turned ON again.)
If the number of records exceeds 39, the oldest record will be deleted and the
most recent error recorded.
Network parameter error
(CIO 1500 + 25
×
n, bit 0)
is 1: ON
The CPU Unit’s EEPROM
data link tables or the net-
work parameters are dam-
aged.
Refer to 9-1-3 Network
Parameters and reset the
data correctly. If the error
occurs again, replace the
CPU Unit.
Either set the EEPROM
Clear Bit in the DM parame-
ter area to ON, or use the Ini-
tialize network parameters
operation on the Mainte-
nance Menu of the Controller
Link Support Software to ini-
tialize the network parame-
ters and then cycle the power
supply.
There is an error in the net-
work parameter settings, or
node address of the local
node is larger then the maxi-
mum address set within the
network parameters.
Refer to 9-1-3 Network
Parameters and reset the
network parameters or the
node address.
Bit status
Probable cause
Probable remedy
Item
Specification
No. of records
39 max.
Data code
Binary (Times are in BCD)
Length of each record
10 bytes
Configuration of records
Error code: 2 bytes (Refer to page 226.)
Detail code: 2 bytes (Refer to page 226.)
Time: 6 bytes (Refer to the following
page.)
Record order
From the oldest record to the most
recent.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...