55
Optical Wiring
Section 3-3
See 1-2-6 Devices Required for Connection for details on available H-PCF
Optical Fiber Cables.
Note
1.
Always use the specified Optical Fiber Cables.
2.
The maximum distance between nodes depends on how the cable is pro-
cessed. For details, refer to the applicable Optical Fiber Cable (H-PCF)
manual.
Optical Ring System
(Token-ring Mode) with
Duplex Operation
All of the nodes in the network (including standby Units) are connected in a
ring with H-PCF Optical Fiber Cable.
The nodes can be connected in any order, but be sure to begin with the upper
connector (SL1) of the highest node in the network and connect to the lower
connector (SL2) in the next lower node, as shown in the following diagram.
Although there is no fixed order in which the nodes must be connected, in
order to minimize the effect on communications time in the event of a discon-
nection, it is recommended that they be connected in order of node address
(node 1
→
node 2...
→
node 62 whenever possible).
Pairs of Controller Link Units used in duplex operation can also be connected
in any order but they must be connected with special cable. (There must be no
other nodes between them.)
Note
1.
Connect active and standby Controller Link Units using either the CS1D-
CN051 Duplex Unit Connecting Cable or an Optical Fiber Cable with a con-
nector (S3200-CN
@@@
-
@@
-
@@
). See 1-2-6 Devices Required for Con-
nection for details on available H-PCF Optical Fiber Cables.
2.
Always use the specified Optical Fiber Cables.
←
Higher
Lower
→
Higher
Lower
1 node
1 node
1 node
Active mode
Active mode
Active mode
Standby mode
Standby mode
Standby mode
(See
note 1.)
(See
note 1.)
(See
note 1.)
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...