169
Duplex Unit System Configuration
Section 8-2
2.
Duplex systems cannot be created using the CS1W-CLK12 or CS1W-
CLK52. Use the CS1W-CLK12-V1 or CS1W-CLK52-V1.
3.
The CS1W-CLK12-V1 and CS1W-CLK52-V1 are completely compatible
upgrades of the CS1W-CLK12 and CS1W-CLK52. They can be used with
CS-series (CS1-H, CS1) PLCs in the same way.
8-2-2
Duplex Specifications
Specifications relating to duplex functionality are given below. For other speci-
fications, refer to 1-2 Specifications and Configurations.
Note
1.
Although standby Controller Link Units do not participate in the network as
nodes, they are physically connected to the network and so they are in-
cluded in the figure for the maximum number of connectable Units. For this
reason, up to a total of 62 active and standby Controller Link Units can be
connected. Therefore, if all the nodes are used in the CS1D System, with
all the Controller Link Units used in duplex operation, the maximum num-
ber of nodes is 31 (62
−
Number of standby Controller Link Units).
It is also possible to use only some of the Units in the Controller Link Net-
work in duplex operation. In this case, up to a total of 62 active and standby
Controller Link Units and Controller Link Units that are not used in duplex
operation can be connected. The Units that are not used in duplex opera-
tion can include both existing Units (CS1W-CLK12, CS1W-CLK52, CVM1-
CLK12, or CVM1-CLK52) and duplex-compatible Units.
Item
Specification
Duplex-compatible model
numbers
CS1W-CLK12-V1 (H-PCF cable)
CS1W-CLK52-V1 (GI cable)
Maximum number of nodes
Up to 31 nodes if all nodes are duplex.
In 1 network, a total of up to 62 active and
standby Controller Link Units can be connected.
(See note 1.)
Number of duplex-compatible
Units that can be mounted to 1
CS1D PLC
6
Up to 3 active and 3 standby Units can be
mounted. (See note 2.)
Mounting position of duplex-
compatible Units
Duplex Units can be mounted in any slots on the
same CS1D PLC. When using a connecting
cable (CS1D-CN051) between Duplex Units,
however, the cable length is 50 cm and so mount
in adjacent slots.
Active Controller Link Units
Standby Controller Link Units
In 1 network, a total of up to 62 active and standby
Controller Link Units can be connected (31 nodes).
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...