248
Troubleshooting for Duplex Communications Units
Section 10-5
Troubleshooting for Errors at Startup
Active Unit
Standby Unit
Status area
(Auxiliary Area)
Probable cause
Probable remedy
RUN
ERC
RUN
ERC
Lit
Not lit
Flashing
Not lit
---
Both the active and
standby Units are
operating normally.
---
Not lit
Not lit
Not lit
Not lit
---
Power is not being
supplied correctly to the
PLC.
Check the power supply
voltage and supply at the
recommended voltage.
---
The Power Supply Unit
is not a CS1D Power
Supply Unit.
Use CS1D Power Supply
Units for CS1D Systems.
---
The Controller Link Unit
has become loose.
Secure the Controller
Link Unit firmly.
CPU Bus Unit Error Flag
(A40207)
There were errors in
both active and standby
Units.
If the same problem
occurs when the Units
are mounted on another
PLC, replace them.
I/O bus error B:
I/O Bus Error Flag
(A40114)
I/O Bus Error Rack
Number (0B Hex is
stored in bits 8 to 15 of
A404)
The wrong Expansion
Backplane is connected.
Replace the Expansion
Backplane with a CS1D
Expansion Backplane
(supports online Unit
replacement).
Lit
Not lit
Lit
Not lit
(CPU on standby)
4 or more pairs of
Communications Units
are set for duplex
operation.
The maximum number of
pairs of Communications
Units mounted on 1
CS1D PLC that can be
set for duplex operation
is 3.
Not lit
Not lit
(ERH is
lit)
Flashing
Not lit
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
The active Controller
Link Unit’s unit number is
set incorrectly.
Set the active Controller
Link Unit’s unit number
to the same number as
the standby Unit and
reset the power.
The active Controller
Link Unit does not
support duplex
operation.
Mount a duplex-
compatible Controller
Link Unit (CS1W-
CLK12-V1 or CS1W-
CLK52-V1).
Lit
Not lit
Not lit
Not lit
(ERH is
lit)
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
The standby Controller
Link Unit’s unit number is
set incorrectly.
Set the standby
Controller Link Unit’s unit
number to the same
number as the active
Unit and reset the power.
Lit
Not lit
(ERH is
lit)
Not lit
Not lit
(ERH is
lit)
CPU Bus Unit
Duplication Error Flag
(A40113)
The duplex settings in
the PLC Setup have not
been made.
Make the duplex settings
for the relevant Unit
under Communication
Unit Duplex Setting in
the PLC Setup using
CX-Programmer.
Lit
Not lit
(ERH is
lit)
Not lit
Not lit
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40203)
CPU Bus Unit Setting
Error Flag (A40207)
The active Controller
Link Unit does not
support duplex
operation.
Mount a duplex-
compatible Controller
Link Unit (CS1W-
CLK12-V1 or CS1W-
CLK52-V1).
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...