186
Communications Mechanism
Section 9-1
9-1-3
Network Parameters
Network parameters are also used to control network operations. Network
parameters are read from the polling node and distributed to all other nodes
when the Controller Link Network is started. In this way, all nodes on the net-
work always have the same network parameter settings. If nodes are con-
nected to the network halfway during network operation, the network
parameter settings will also be distributed to these nodes when they are con-
nected. The following three network parameters can be specified.
Maximum Node Address
This parameter specifies the maximum node address of nodes to be checked
by the polling node. The default is 62 (or 32 for Optical Bus Networks). Reduc-
ing the setting of this parameter reduces the number of nodes checked by the
polling node and can thus avoids unnecessary check operations. However, if
the network contains nodes with node addresses greater than the setting of
the parameter, these nodes will not be connected to the network.
No. of Polled Nodes Per
Communications Cycle
This parameter specifies the number of nodes to be checked (polled) by the
polling node during each polling cycle. The default is 4. Setting this parameter
to a high value increases the communications cycle time, but reduces the time
required to recognize that nodes have been removed from or added to the
network. Reducing the setting of this parameter shortens the communications
cycle time but delays a network response when a node is disconnected from
or connected to the network.
No. of Event-frames per
Communications Cycle
This parameter specifies the maximum number of event frames (communica-
tions other than data links, such as message service transmissions) that can
be transferred during a communications cycle. Specify a value in units of 128
bytes. The default is 35 (128
×
35 = 4,480 bytes).
Increasing the setting of this parameter increases the communications cycle
time but allows for more event communications such as the message service.
Too small a parameter value restricts event communications, resulting in an
error. See 9-2 Communications Cycle Time (on page page 187) for the effects
of network parameters on communication cycle times.
9-1-4
Specifying Network Parameters
The network parameters can be specified from CX-Net in CX-Programmer or
the Controller Link Support Software. This section describes only the allow-
able setting range for each network parameter. Refer to the Controller Link
Support Software Operation Manual (W308) for setting procedures.
The following table shows the setting range and default for network parame-
ters.
The network parameters become valid immediately after being set.
Note
1.
The default value is 32 for Optical Bus Networks.
2.
The network parameters set at the polling node will be enabled. Therefore,
if there are multiple polling nodes, ensure that they all have the same set-
tings. If there are different settings, network operation will depend on the
polling node. Once the network has been constructed, however, the same
network parameters will be set for all nodes.
3.
Always stop the data link before changing network parameters.
Network parameter
Setting range
Default value
Maximum node address
2 to 62
62 (See note 1.)
Number of polled nodes
1 to 31
4
Maximum number of event-frames
6 to 238
35
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...