219
Status Area and Troubleshooting
Section 10-2
10-2-2 CVM1 and CV-series Controller Link Units
The status of the Unit and Network is indicated in the following manner in the
PLC.
Status Area
Error Information: CIO 1500 + 25 x
(Unit No.)
Polling Node Address, Startup Node Address: CIO 1500 + 25 x (Unit No.) + 1
Network parameter error (CIO 1500 +
25
×
n, bit 0) is 1: ON
The network parameter
data in the CPU Bus
Unit Area is damaged.
Refer to 9-1-3 Network
Parameters and reset
the data correctly. If the
error occurs again,
replace the CPU Unit.
Either set the EEPROM
Clear Bit in the DM
parameter area to ON,
or use the Initialize net-
work parameters opera-
tion on the
Maintenance Menu of
the Controller Link Sup-
port Software to initial-
ize the network
parameters and then
cycle the power supply.
There is an error in the
network parameter set-
tings, or node address
of the local node is
larger then the maxi-
mum address set within
the network parame-
ters.
Refer to 9-1-3 Network
Parameters and reset
the network parame-
ters or the node
address.
Bit status
Probable cause
Probable remedy
1: Network parameter error (in PLC's EEPROM)
1: Data link table error (in PLC's EEPROM)
1: Routing table error (in PLC's EEPROM)
1: PLC system setting error
1: EEPROM error
1: Duplicate node address setting error
1: Inconsistent network parameters
1: Communications controller send error
1: Error log exists
Polling node address
Startup node address
Each node address is displayed in 2-digit BCD.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...