Table of Contents

 

I. Safety Considerations..

……………………………………..

 

1

 

II. Description

………………...…...………………...……………

 

1

III. System Overview

…………………………………………….

 

2

 

IV. Operation

……………………………………………...……….

 

3

V. Menu Screens

……………..…..………………………………

 

4

 

VI. Layout & I/O Configuration

….………….……………..

 

8

 

VII. Electrical Connections

……………………………………

 

9

 

VIII. Electrical Schematic

………………………………………

 

10

 

IX. Limited Warranty & Contact Info

……………………

 

11

 

I. SAFETY CONSIDERATIONS

GENERAL WARNING

 

Ensure all appropriate personnel read owner

s manual prior to installation and/or operation of controller. Failure to

 

Comply with instructions and safety precautions could lead to personal injury or product damage.  Please call

 

and ask to speak with one of our customer service representatives if there are any questions.

 

CAUTION

 

Disconnect controller from power source before servicing or removing cover.

 

II. DESCRIPTION

The PDA/ATF

-

MAX is a dual purpose controller for both monitoring the pressure differential with alarm indicator and automatically controlling 

the flush valve of a Thompson strainer.

 

OWNER

S MANUAL

 

Summary of Contents for THOMPSON PDA

Page 1: ...installation and or operation of controller Failure to Comply with instructions and safety precautions could lead to personal injury or product damage Please call and ask to speak with one of our customer service representatives if there are any questions CAUTION Disconnect controller from power source before servicing or removing cover II DESCRIPTION The PDA ATF MAX is a dual purpose controller f...

Page 2: ...troller screen and keypad interface as shown The clear cover provides protection for the controller and can be opened with the two latches on the side of the controller housing to access the keypad A PDA ATF MAX controller B Power supply C Transducer Wiring assembly D Mounting bracket E Flush valve assembly A Controller Screen B Keypad ...

Page 3: ...lows for a remote reset of the Consecutive Flush Alarm Scrolling through Menu Screens The PDA ATF MAX allows the operator to scroll through a selection of menu screens by pressing the A or B buttons Press A to scroll backward to the previous menu or press B to scroll forward to the next menu The LCD backlight will automatically turn on for 5 minutes when a button is pressed thus allowing the opera...

Page 4: ...tatus OFF MAX High PSID Status OFF MAX The Inlet Pressure transducer is monitored to sense sufficient Inlet Pressure and allow Timed Flushes and Differential Pressure Flushing When the inlet pressure is sensed as lower than the Setpoint the Flush Interval timer will be paused and a timed Flush will not occur Differential Pressure Flushing will also be inhibited DP sensing will continue and the Sta...

Page 5: ...but will instead indicate Flush Cycle The Flush Valve is opened and the Alarm Light Sounder output is flash ing This output flashes the Light and Sounder throughout the entire Flush cycle The Flush Duration is nominally set for 8 seconds The Flush Duration time is adjustable see Setup screen 3 for information After this Flush duration time the Flush Cycle is complete The Open Flush Valve Output wi...

Page 6: ... is 7 PSID This set point is located on Screen 2 Flush Duration Screen The time allotted for the Flush Valve to be open This time should be set according to the type of filter and the nature of the material being fil tered This value is adjustable from 5 to 300 seconds Factory Preset value is 8 seconds This setpoint is located on Screen 3 Please Note Flush Valve is not completely open until 3 seco...

Page 7: ... elapsed since the system last Flushed example 00011 30 is 11 hours and 30 minutes and how the last Flush was triggered There are four trigger possibilities 1 Local Operator Flush triggered manually by an operator 2 Timer the backflush was triggered by time as set on the Backflush Interval screen 3 PD Transducer the Flush was triggered by a high pressure differen tial as set on the PSID setpoint 4...

Page 8: ...et input will signal the PDA ATF MAX to remotely reset the Consecutive Flush Alarm The Analog Digital Input locations allow Miller Leaman Inc to design customer specific programs These programs are then able to receive and process both digital and analog signals from devices such as Pressure Transducers Flow meters Level Switches etc Inputs IC ID are the Inlet and Outlet Pressure Transducer connec...

Page 9: ...e assigned to the input IC or ID blue to the Common terminal and the brown to the 24VDC Power terminal Customer Initiated Flush Signal Optional The optional Customer Initiate Flush Signal input is connected to Input I1 Please Note this signal must be a discrete 24VDC signal that references the Common terminals Customer Remote Alarm Reset Signal Optional The optional Customer Remote Alarm Reset Sig...

Page 10: ...Page 10 VIII ELECTRICAL SCHEMATIC ...

Page 11: ...uator The valve body has a 316SS ball inside a UV modified glass filled Nylon housing The actuator has high torque motor gears and solid state components for increased durability and maintenance free performance contained inside a NEMA6P enclosure AUTOMATIC TIMER FLUSH VALVE ATF2 Primary Components D J C A E G K L I B H M N F A POWER SUPPLY B CONTROL TOGGLE SWITCH 3 POSITION LIGHTED C CONTROL BOX ...

Page 12: ...d result in equipment damage The valve is configured as normally closed however in the event of an extended power failure while the valve is fully or partially open the actuator will be unable to power back to fully closed position This could result in water continuing to drain from the strainer until power is restored It is important to inspect this equipment routinely to ensure that the ATF2 has...

Page 13: ...frequency of flush in ten 10 minute increments Digit Toggle 4 changes frequency of flush in one 1 minute increments When time has been selected push the RESET button to save the setting and begin the new cycle Example the Factory Setting will display as 24 00 Pushing 1 down twice pushing 2 up one time pushing 3 down two times and pushing 4 up five times will change the Frequency of flush cycle to ...

Page 14: ...alue Use SET LOCK button to toggle between T1 SET VALUE INDICATOR AMBER Displayed when showing editing T1 setting T2 SET VALUE INDICATOR AMBER Displayed when showing editing T2 setting BUTTON BUTTON ACTION RESET Set time selections and Clear Flush SET LOCK Toggle between T1 and T2 Setting Lock screen Push Lock and Digit 1 together BUTTON T1 FREQUENCY PROGRAMMING T2 DURATION PROGRAMMING DIGIT 1 Adj...

Page 15: ... BALL BODY MAXIMUM PRESSURE ATF2 075 3 4 316SS Nylon 150 PSI 70 deg F ATF2 100 1 316SS Nylon 150 PSI 70 deg F ATF2 150 1 1 2 316SS Nylon 150 PSI 70 deg F ATF2 200 2 316SS Nylon 150 PSI 70 deg F ATF2 300 3 316SS Polypropylene 100 PSI 70 deg F ATF2 MODEL INFORMATION Illuminated Rocker Switch AUTO Valve operates on Timer MANUAL Valve opens Momentary POWER SUPPLY SPECIFICATION AC DC SWITCHING ADAPTOR ...

Page 16: ... be used as a guide when installing the PDA on to an existing Thompson Strainer 1 Place the PDA enclosure with the black bracket over the high and low gauge ports on the side of the strainer housing 2 While applying pressure to the enclosure and bracket tighten the 2 10 24 stainless steel set screws to secure the bracket on the gauge ports 3 Connect the blue 1 4 tube into the upper gauge port 4 Co...

Page 17: ...us tomer s responsibility to provide a safe power outlet in terms of being water proof and physically able to accept the plug in power supply we provide Miller Leaman Inc also recommends that the installation be only performed by a qualified elec trician and that all Local State and National Electrical Codes be followed The pressure differential switch gauge is factory set to 7 8 PSI Since the Tho...

Page 18: ... PDA2 WIRING SCHEMATIC Office Hours 8 AM 5 PM Eastern Time Web www millerleaman com Email support millerleaman com 800 Orange Avenue Daytona Beach FL 32114 Phone 386 248 0500 Fax 386 248 3033 ML40191 2022 REV 6 22 22 ...