Checking Data Link Status
Section 5-4
5-4-1
LED Indicators
Check the LNK, M/A, and RING indicators on the front of the unit.
The LNK indicator will be lit at all nodes participating in the data links as long
as operation is normal. The mode (manual/automatic) of any node active in
the network can be checked using the M/A indicator, regardless of whether
that node is participating in the data links. Using the RING indicator, it is also
possible to check the transmission path format set for an active network, as
well as the status of cables when in token-ring mode. See 10-1 Troubleshoot-
ing Using Indicators for details.
5-4-2
Data Link Status Area
The data link status area can be used to check for errors when data link does
not operate normally even though no abnormality has been detected by the
PLC’s CPU Unit or the Controller Link Unit. The data link status area contains
the data link status information shown below. This status information is stored
in the same words for CS-series, CVM1, and CV-series.
The number of words used for data link status, and the information that is
reflected, depends on the setting (8-bit or 4-bit format) for the data link status
storage format specification in the DM parameters area, as shown in the fol-
lowing diagram.
See 10-2 Status Area and Troubleshooting for troubleshooting procedures
and see 5-4-5 Data Link Status Storage Format for details on storage format.
Name
Color
Status
Contents
LNK
(data link)
Yellow
ON
Participating in data links.
Flashing
Data link table setting error
OFF
Not in data links or data links are inactive.
M/A
(data link
mode)
Yellow
Data links active in
network.
Data links not active in
network.
ON
Manual
Note: This indicator
will always be OFF
when the data links are
not active.
OFF
Automatic
RING
(transmission
path format)
Yellow
ON
Token-ring mode setting (cable normal)
Flashing
Token-ring mode setting (cable discon-
nected)
OFF
Token-bus mode setting
CVM1 and CV-series PLCs
CS-series PLCs
Optical Ring Controller Link Unit
(CLK12 for H-PCF cable, CLK52 for GI cable)
Optical Ring Controller Link Unit
(CLK12 for H-PCF cable, CLK52 for GI cable)
RUN
PS
ERC
ERH
RING MA
INS
LNK
SD
RD
RUN PS
ERC ERH
RING MA
INS
LNK
SD
RD
CLK12-V1
CLK52-V1
Make sure that the LNK
indicator is ON at nodes
participating in the active data
links.
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...