background image

Cat. No. W457-E1-07

CompoNet Slave Units
and Repeater Unit

CRT1 Series

OPERATION MANUAL

Summary of Contents for CRT1 - 10-2009

Page 1: ...Cat No W457 E1 07 CompoNet Slave Units and Repeater Unit CRT1 Series OPERATION MANUAL...

Page 2: ......

Page 3: ...CRT1 Series CompoNet Slave Units and Repeater Unit Operation Manual Revised October 2009...

Page 4: ...iv...

Page 5: ...n some OMRON products often means word and is abbreviated Wd in documentation in this sense The abbreviation PLC means Programmable Controller PC is used however in some Program ming Device displays t...

Page 6: ...vi...

Page 7: ...3 Communications Cable 37 2 4 Communications Cable Wiring Examples 42 SECTION 3 Installation and Wiring 47 3 1 Installing Slave Units 48 3 2 Connecting Cables 57 3 3 Preparing Flat Connectors 58 3 4 C...

Page 8: ...s 363 7 1 Temperature Input Units 364 7 2 Overview of Temperature Input Units 367 7 3 Status Areas 376 7 4 Monitoring Temperature Data 378 7 5 Temperature Input Units 382 SECTION 8 Expansion Units 391...

Page 9: ...perature Input Unit Functions 540 SECTION 12 Troubleshooting and Maintenance 579 12 1 Indicator Meanings and Troubleshooting 580 12 2 Troubleshooting 581 12 3 Device Maintenance 588 Appendices A Compo...

Page 10: ...x...

Page 11: ...ave Units Section 7 describes the Temperature Input Units Section 8 describes the Expansion Units Section 9 describes the Bit Slave Units Section 10 describes the Repeater Unit Section 11 individually...

Page 12: ...mpoNet Master Unit functions W342 CS1G H CPU H CS1G H CPU EV1 CS1D CPU H CS1D CPU S CS1W SCB V1 CS1W SCU V1 CJ1G H CPU H CJ1G CPU P CJ1G CPU CJ1M CPU CJ1W SCU V1 CP1H X CP1H XA CP1H Y NSJ B G5D NSJ B...

Page 13: ...AS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBL...

Page 14: ...that the uses listed may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this manual Nuclear...

Page 15: ...nfirm actual specifications of purchased products DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are shown PERFORMANCE...

Page 16: ...xvi...

Page 17: ...Unit You must read this section and understand the information contained before attempting to set up or operate a CompoNet Network using CompoNet Slave Units or Repeater Units 1 Intended Audience xvi...

Page 18: ...cient for the systems machines and equipment and be sure to provide the systems machines and equipment with double safety mechanisms This manual provides information for programming and operating the...

Page 19: ...for such problems external safety measures must be provided to ensure safety in the system WARNING The CPU Unit refreshes I O even when the program is stopped i e even in PROGRAM mode Confirm safety...

Page 20: ...in malfunction When installing the Units ground to 100 min Wire all connections correctly according to instructions in the manual Always separate Special Flat Cables Standard and Sheathed for differ...

Page 21: ...ution before actually running it on the Unit Not checking the program may result in unexpected operation Check all wiring and switch settings to be sure they are correct Always turn OFF the power supp...

Page 22: ...g and other conditions of the equipment or control panel on which the OMRON devices are installed The customer must therefore perform the final check to confirm that devices and the overall machine co...

Page 23: ...onfiguration of the control panel used other devices connected to the control panel wiring and other conditions You must therefore confirm that the overall machine or equip ment complies with EC Direc...

Page 24: ...xxiv Conformance to EC Directives 6...

Page 25: ...els that are available 1 1 Features of CompoNet Slave Units 2 1 1 1 Overview 2 1 1 2 Features of CompoNet Slave Units 2 1 1 3 CompoNet Slave Unit Functions 7 1 2 Slave Unit Models 19 1 2 1 Word Slave...

Page 26: ...Unit can quickly measure the ON OFF timing of input and output contacts without relying on the ladder program Contact types IN OUT OUT IN IN IN OUT OUT and trigger patterns ON OFF OFF ON ON ON OFF OFF...

Page 27: ...c tion time for the most recent 4 communication failures within the slave unit This data can be read by using the CX Integrator Input Filters The Slave Units read input values multiple times during th...

Page 28: ...ting the Number of AD Conversion Points The conversion cycle is 4 ms max when using all 4 analog inputs The AD conversion cycle can be made faster if fewer AD conversion points are used Rate of Change...

Page 29: ...mperature range can be measured in seconds Explicit messages can be used to see if the measured time has exceeded a monitoring set value The temperature range total time count settings are made by usi...

Page 30: ...1 V D08S 1 CRT1 D S 1 CRT1 D16SH 1 CRT1B D02S 1 CRT1B D0 SP 1 CRT1 VAD04S CRT1 VDA02S No special tools are required for connections because industry standard e CON connectors are used Electrical cable...

Page 31: ...evices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfuncti...

Page 32: ...es Yes Network Power Voltage Monitor Yes Yes I O Power Status Monitor Communications Error History Monitor Yes Yes Input Filter Communications Error Output Yes Yes Preventing Malfunctions Caused by In...

Page 33: ...ing Units Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Communications Error Output Yes...

Page 34: ...Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Output Yes Ye...

Page 35: ...ower Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Communications Error Output Yes Preventing Malfunctions Caused by Inrush Current at I O...

Page 36: ...s Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Yes Yes Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Out...

Page 37: ...s Naming Connected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Yes Yes Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Yes Communications Error Out...

Page 38: ...es Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfunctions Caus...

Page 39: ...Yes Network Power Voltage Monitor Yes I O Power Status Monitor Yes Communications Error History Monitor Yes Input Filter Yes Yes Yes Communications Error Output Yes Yes Yes Preventing Malfunctions Ca...

Page 40: ...nnected Devices Yes Network Power Voltage Monitor Yes I O Power Status Monitor Communications Error History Monitor Yes Input Filter Communications Error Output Yes Yes Yes Preventing Malfunctions Cau...

Page 41: ...onitor Communications Error History Monitor Yes Input Filter Communications Error Output Preventing Malfunctions Caused by Inrush Current at I O Startup Power Short circuit Detection Unconnected Line...

Page 42: ...Naming Units Yes Yes Naming Connected Devices Yes Network Power Voltage Monitor Yes Yes I O Power Status Monitor Communications Error History Monitor Yes Yes Input Filter Yes Yes Yes Yes Yes Yes Yes C...

Page 43: ...ave Units with 2 tier termi nal blocks and 16 points Bit Slave Units Bit Slave Units are Slave Units that are allocated units of 2 bits in I O memory of the CPU Unit Bit Slave Units Bit Slave Units ar...

Page 44: ...nal blocks can be attached removed from the Unit Expansion Units can be added 16 inputs PNP CRT1 ID16 1 16 outputs NPN CRT1 OD16 16 outputs PNP CRT1 OD16 1 8 inputs 8 outputs NPN CRT1 MD16 Terminal bl...

Page 45: ...cted Line Detection 8 inputs NPN CRT1 ID08TAH 8 inputs PNP CRT1 ID08TAH 1 8 outputs NPN CRT1 OD08TAH 8 outputs PNP CRT1 OD08TAH 1 Without Short cir cuit and Discon nected Line Detection 16 inputs NPN...

Page 46: ...1 MD16S 1 With Short circuit and Dis con nected Line Detec tion 16 inputs NPN CRT1 ID16SH 16 inputs PNP CRT1 ID16SH 1 16 outputs NPN CRT1 OD16SH 16 outputs PNP CRT1 OD16SH 1 8 inputs and 8 outputs NPN...

Page 47: ...s NPN CRT1 VOD32ML 32 outputs PNP CRT1 VOD32ML 1 16 inputs 16 outputs NPN CRT1 VMD32ML 16 inputs 16 outputs PNP CRT1 VMD32ML 1 Type Appearance I O capacity Model Features Digital I O Slave Units with...

Page 48: ...4 to 20 mA 2 outputs CRT1 DA02 MS OM RO N AN ALO G TER MIN AL CR T1 AD 04 NS WO RD NO DE AD R X1 X10 0 63 1 2 3 4 5 6 7 8 A D SW ON INPU T RAN GE CH 0 1 INPU T RAN GE CH 2 3 1 2 3 4 5 6 Type Appearan...

Page 49: ...AD 04 NS WO RD NO DE AD R X1 X10 0 63 1 2 3 4 5 6 7 8 A D SW ON INPU T RAN GE CH 0 1 INPU T RAN GE CH 2 3 1 2 3 4 5 6 Type Appearance I O capacity Model Features Expansion Units with 2 tier Terminal B...

Page 50: ...4 inputs NPN CRT1B ID04SP 4 inputs PNP CRT1B ID04SP 1 Bit Slave Units with Compact Connec tors 2 inputs NPN CRT1B ID02JS Compact space saving design Internal hook communications con nectors Network p...

Page 51: ...trunk line adding more nodes increasing the connection distance and changing the type of cable upstream and downstream of the Repeater Unit PO RT2 PO RT2 PORT1 PORT1 PR T PR T NO DE AD R NO DE AD R N...

Page 52: ...T1 ID16SH 1 Shared with com munications power supply See note CRT1 OD16SH 1 I O power must be supplied externally for connected devices CRT1 MD16SH 1 Shared with com munications power supply only for...

Page 53: ...e CON Connectors CRT1 VAD04S DIN Track or Mounting Bracket e CON connectors CRT1 VDA02S With MIL Connectors CRT1 VAD04ML MIL connectors CRT1 VDA02ML Temperature Input Units CRT1 TS04T DIN Track Termi...

Page 54: ...ply to Expansion Slave Unit Digital Input Slave Unit with Expansion Input Unit Example CRT1 ID16 XWT ID16 or XWT ID08 Not required The Expansion Unit uses the same I O power supply as the Digital I O...

Page 55: ...Elements 32 2 1 2 Segments 34 2 2 Wiring Formations 35 2 3 Communications Cable 37 2 3 1 Cables That Can Be Used 37 2 3 2 Criteria for Selecting Cables 38 2 3 3 Maximum Distance and Number of Connecte...

Page 56: ...transfers I O data between the PLC and the Slave Units There is only one Master Unit per network The Master Unit must be con nected to the trunk line Multidrop connection on branch line CompoNet Maste...

Page 57: ...e same physical layer Terminating Resistors With a CompoNet Network the Master Unit is located at one end of the trunk line and a Terminating Resistor is connected to the other end of the trunk line I...

Page 58: ...k line from the Repeater Unit One power supply cannot be used to supply communications power to more than one line i e to the trunk line and sub trunk line or to two sub trunk lines I O Power Supply A...

Page 59: ...ranch line Trunk line Segment 1 Master Unit Slave Unit Slave Unit Repeater Unit Repeater Unit Terminating Resistor Terminating Resistor Repeater Unit Terminating Resistor Terminating Resistor Repeater...

Page 60: ...table shows the conditions and restrictions for each formation Segment range Segment range Master Unit Slave Unit Terminating Resistor Repeater Unit Slave Unit Slave Unit Slave Unit Slave Unit Termin...

Page 61: ...ly available VCTF cable with four 0 75 mm2 conductors JIS C3306 that meet CompoNet specifications Flat Cable I DCA4 4F10 Standard Flat Cable CompoNet compatible products other than DCA4 4F10 can be us...

Page 62: ...signal low 0 5 mm2 4 Black BS communications power supply negative side 0 75 mm2 5 max Black BS Red BS White BDH Blue BDL Item Cable type Round cable I Round cable II Flat Cable I Flat Cable II Applic...

Page 63: ...und cable II Flat Cable I Standard and Flat Cable II Sheathed are treated as different types of cable Restrictions in Distance between Cables of Multiple CompoNet Systems When using more than one Comp...

Page 64: ...rom the trunk line or sub trunk lines Total branch line length Restrictions on branch line locations Number of Slave Units including Repeater Units 32 32 Master Unit Repeater Unit Trunk line length Br...

Page 65: ...out branch ing With branch ing Length per trunk line or sub trunk line 100 m 300m 30 m 90m 30 m 90 m Branch line length Not sup ported See note 2 2 5 m 2 5 m Total branch line length Not sup ported Se...

Page 66: ...Connectors DCN4 TB4 for connecting Units to connect Communications Cables to Master Units Repeater Units and Slave Units To supply the communications power 24 VDC connect the two commu nications powe...

Page 67: ...nits Connect the communications power supply 24 VDC to the communica tions power supply connector for the Master Unit or Repeater Unit Connect DCN4 TM4 Terminating Resistors and DCN4 TR4 Flat Connec t...

Page 68: ...Two communications power lines Relay terminal block Open Connector Slave Unit Slave Unit Slave Unit Open Connector 24 VDC communications power supply Communications power supply connector Communicati...

Page 69: ...d in parallel by using multidrop connections A DCN4 MD4 Multidrop Connector is required for this Only Flat Cable I can be used Communications connector Flat Cable Communications signal lines BS red an...

Page 70: ...ly Flat Cable I can be used Communications connector Terminating Resistor 121 Master Unit or Repeater Unit Communications power supply 24 VDC Commu nications power Communications power supply connecto...

Page 71: ...2 Branching Communications Cables 77 3 4 3 Extending Communications Cables 80 3 4 4 Connection Locations for Terminating Resistor 82 3 5 Power Supply Wiring 85 3 5 1 Power Supply Specifications 86 3 5...

Page 72: ...TA 1 CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA 1 CRT1 ID16TAH 1 CRT1 OD16TAH 1 CRT1 MD16TAH 1 With e CON Connectors CRT1 VID08S 1 DIN Track or Mounting Bracket CRT1 VOD08S...

Page 73: ...pact Connec tors CRT1B ID02JS 1 M4 screw mounting using CRT1B ATT03 Mounting Bracket CRT1B OD02JS 1 CRT1B ID04JS 1 CRT1B OD04JS 1 CRT1B MD02JS 1 CRT1B MD04JS 1 Repeater Unit CRS1 RPT01 DIN Track or sc...

Page 74: ...secured 3 1 4 Mounting with a Mounting Bracket Slave Units with e CON connectors CRT1 V D08S 1 CRT1 VAD04S CRT1 VDA02S or MIL connectors CRT1 V D ML 1 CRT1 VAD04ML CRT1 VDA02ML can be panel mounted or...

Page 75: ...ocedure 1 Attach the Mounting Bracket to the panel surface or wall with two Phillips screws as shown in the following diagram For mounting hole dimensions refer to Dimensions above 18 7 35 mm 13 Mount...

Page 76: ...ors Mounting Procedure 1 Attach the Mounting Bracket to the panel surface or wall with two Phillips screws as shown in the following diagram For mounting hole dimensions refer to Dimensions above 2 Mo...

Page 77: ...ontal Mounting to a Wall Units with e CON Connectors CRT1 V D08S 1 CRT1 VAD04S CRT1 VDA02S Units with MIL Connectors CRT1 V D ML 1 CRT1 VAD04ML CRT1 VDA02ML 6 0 45 45 Mounting Bracket mm The Unit show...

Page 78: ...heck to be sure that the Unit is securely mounted Mounting Bit Slave Units Using Screw Brackets The Bit Slave Units CRT1B ID02S 1 and CRT1B OD02S 1 are installed using the enclosed screw bracket along...

Page 79: ...1B D02JS 1 or CRT1B D04JS 1 can be mounted using special Mounting Brackets Required Brackets Dimensions CRT1 ATT03 Guides Screw bracket Screw bracket hook Name Model Applicable Slave Unit Mounting Bra...

Page 80: ...ing holes B Tighten the screws to the following torque Tightening torque 0 9 N m 2 As shown in the following figure press in on the Unit until the internal hooks of the Mounting Bracket make a clickin...

Page 81: ...in the following table 3 2 1 Round Cable I II Slave Unit Repeater Unit connections Cable branches T branch connections Multidrop connections Open Type Connector Note Bits Slave Units with a Flat Cable...

Page 82: ...nits are available with a Flat Cable included as a stan dard feature Flat Connector Socket Flat Connector Plug Multidrop Connector Bit Slaves with Compact Connectors Note If a Sheathed Flat Cable II i...

Page 83: ...ons Cable to a DCN4 MD4 Multidrop Connector when a multidrop con nection is used Flat Connector II Socket DCN5 TR4 Used as a set with the DCN5 BR4 Flat Connector Plug in the following applications Ext...

Page 84: ...the Cable Stopper Set the Cable Stopper Close the cover secure the hooks and then press down on the cable stopper until it clicks into place Name Appearance Model Application Pliers DWT A01 Crimping...

Page 85: ...y been set Attaching the Housing Confirm that the cable labels match the cable colors and then temporarily secure the housing to the cover Note The housing cannot be removed from the cover once it has...

Page 86: ...2 Do not pressure weld the connector cover at the back of the pressure welding block 3 Set the connector in the correct orientation 3 After attaching the cable confirm that it is properly pressure wel...

Page 87: ...at there are no whiskers on the wires Setting the Cable Stopper when Extending Cable or Connecting a Terminating Resistor A stopper must be set in advance when extending a line or connecting a Ter min...

Page 88: ...ing to the cover Note The housing cannot be removed from the cover once it has been attached The connector may be damaged if the housing is force fully removed Pressure welding the Connector The conne...

Page 89: ...sure welded as shown below Processing and Mounting Procedure for DCN4 BR4 Flat Connector Plug Flat Connector Plug Component Names Cutting the Cable Cut the cable perpendicular to the length To prevent...

Page 90: ...arrows of the con nector cover with the center of the crimping block on the Pliers 2 Squeeze firmly on the Pliers until the lock on the connector clicks into place Note 1 Do not pressure weld the conn...

Page 91: ...2 3 1 Confirm the colors again and temporarily secure the housing to the cover Pressure welding the Connector Use the DWT A01 Pliers to pressure weld Connector 1 2 3 1 As shown in the following figur...

Page 92: ...Cut the cable perpendicular to the length To prevent short circuits cut the cable with a sharp blade such as wire cut ters and be sure that there are no whiskers on the wires Setting the Cable Stoppe...

Page 93: ...te line is in the direction of the side with the open cover with the white line on the cable facing upward T branch Connections Line Extensions and Terminating Resistor Connections 2 Hold the cable so...

Page 94: ...or on the pressure welding block of the crimping tool As shown below align the center see arrows of the connector cover with the center of the pressure welding block on the Pliers 2 Squeeze firmly on...

Page 95: ...that the white line is in the direction of the side with the open cover with the white line on the cable facing upward 2 Hold the cable so that it does not move and close the cover Pressure welding t...

Page 96: ...firmly on the Pliers until the lock on the connector clicks into place 3 After attaching the cable confirm that it is properly pressure welded as shown below Pliers Connector cover Be sure there are...

Page 97: ...DCN4 MD4 Used to connect Slave Units or Repeater Units to trunk lines sub trunk lines or branch lines by using multidrop connec tions Terminating Resistor DCN4 TM4 This is a Connector type Terminating...

Page 98: ...ess in on the latches on both sides and pull out the Open Type Connector 2 Open the terminal cover of the Open Type Connector and connect the ca ble wires to BDH communications data high and BDL commu...

Page 99: ...remove a Connector once it has been attached press in on the latches on both sides of the Connector and pull it out Connecting Flat Cable I for Bit Slave Units with Compact Connectors Connect a DCN4 M...

Page 100: ...it in until it clicks into place Note To remove a Connector once it has been attached press in on the latches on both sides of the Connector and pull it out Flat Cable II Flat Cable II cannot be used...

Page 101: ...k first attach the M3 crimp terminals shown below to the wires Using Flat Cable I Attach a DCN4 BR4 Flat Connector Plug to the DCN4 TR4 Flat Connector Socket connected to Communications Cable Installa...

Page 102: ...cks into place Note To remove a Connector once it has been attached press in firmly on the latches on both sides of the front of the Connector and pull it out Multidrop Connections Using Round Cable I...

Page 103: ...e communications connector of the Slave Unit or Repeater Unit and then attach two DCN4 BR4 Flat Connec tor Plugs that are already connected to Communications Cables Installation Method 1 2 3 1 Place t...

Page 104: ...Cables Flat Cable I Attach a DCN4 BR4 Flat Connector Plug to a DCN4 TR4 Flat Connector Socket connected to Communications Cable Installation Method Be sure the surface of the Flat Connector Plug on wh...

Page 105: ...to Communications Cable Installation Method Orient the Flat Connector Plug so that the white line on the cable is facing downward and press in the Connector until it clicks into place Note To remove a...

Page 106: ...ow connect the Terminating Resistor at the end of the line so that the length of a is greater than b Round Cable I Connect the cable wires to a DRS1 T Terminating Resistor Master Unit Trunk line Conne...

Page 107: ...CN4 TR4 Flat Connector Socket connected to the cable Connection Method Push in the Terminating Resistor until it clicks into place Note To remove a Terminating Resistor once it has been connected pres...

Page 108: ...tor that is connected to the Unit This is only possible when Flat Cable I is used Flat Cable II Attach a DCN5 TM4 Terminating Resistor to the DCN5 TR4 Flat Connector Socket connected to Communications...

Page 109: ...ors on Repeater Units Communications power supply Used for communications with individual Units and for internal circuit operations of Units I O power supply Used for I O operations for Units with ext...

Page 110: ...ter Unit or Repeater Unit Communica tions power supply terminals I O power supply terminals 24 VDC I O power supply Round cable II or Flat Cable I II Communications power supply connector on Master Un...

Page 111: ...urrent number of inputs used sensor current consumption number of sensors used actual load current number of actuators used 2 Use a power supply with sufficient capacity considering the inrush current...

Page 112: ...e communica tions power supply and the communications power supply connector must be no longer than 3 m Connect an Open Type Connector here Note When using the UL standards please install a unit to re...

Page 113: ...24 VDC power supply is provided using the following method Units with e CON Connectors CRT1 OD S 1 MD S 1 OD SH 1 and MD SH 1 Connect the 24 VDC power supply line to the V terminal and G terminal of t...

Page 114: ...nits CRT1 VAD04S are equipped with a sensor power supply connector for supplying of power to the connected sensor Peel back the coating on the included power supply cable and connect the wires to the...

Page 115: ...an external communications power supply for the Master Unit Not Using a Repeater Unit BS BDH BDL BS V G V G BS BDH BDL BS BS BDH BDL BS BDH BDL BS BS BS BS Termi nating Resistor Communications power s...

Page 116: ...2 BDL 2 BS 2 BS 2 PORT1 PORT2 BDH BDL BS BS BS BS Master Unit Termi nating Resistor Power supply Slave Unit I O power supply Communications power supply Multi power supply Slave Unit Round cable I Rep...

Page 117: ...BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 T POR 2 BS 2 BS 2 BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT2 BS 2 BS 2 Termi nating Resis tor Trunk line Slave Units Communications power supply and I O...

Page 118: ...connected at only one location for the trunk line and one location each for the sub trunk lines Communications power to the trunk line can be supplied only through the communications power supply conn...

Page 119: ...ommunications errors may occur if this restriction is not observed Trunk line or sub trunk line Sub trunk line Master Unit Repeater Unit Repeater Unit Trunk line or sub trunk line Communications power...

Page 120: ...G BS BDH BDL BS BS BDH BDL BS BS BDH BDL BS BS BDH BDL BS V G BS BDH BDL BS BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT2 BS 2 BS 2 V G BDH 1 BDL 1 BS 1 BS 1 BDH 2 BDL 2 BS 2 BS 2 PORT1 PORT...

Page 121: ...age drop is expressed by the following formula If the voltage drop is too large and power cannot be supplied to the farthest Slave Unit within the allowable range add a Repeater Unit and supply power...

Page 122: ...ods Supplying I O Power from One Source When supplying I O power to the entire system from one source the power consumed by each device and all the loads must be considered Select the cables so that...

Page 123: ...t the overall system from stopping to ensure system safety consider placing power supplies in more than one location and con sider the way Slave Units should be grouped when supplying power Cost Consi...

Page 124: ...ID16 1 CRT1 OD16 1 CRT1 MD16 1 CRT1 ROS08 CRT1 ROF08 CRT1 ROS16 CRT1 ROF16 With 3 tier Terminal Block CRT1 ID08TA 1 CRT1 OD08TA 1 CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA...

Page 125: ...ng the other screw the terminal block will warp possibly causing it to crack Analog I O Slave Units With 2 tier Terminal Block CRT1 AD04 Screw terminal block M3 CRT1 DA02 With e CON Connectors CRT1 VA...

Page 126: ...ROF16 Models with 3 terminal blocks CRT1 ID08TA 1 CRT1 OD08TA CRT1 ID08TAH 1 CRT1 OD08TAH 1 CRT1 ID16TA 1 CRT1 OD16TA 1 CRT1 MD16TA 1 CRT1 ID16TAH 1 CRT1 OD16TAH 1 CRT1 MD16TAH 1 Analog I O Slave Uni...

Page 127: ...connector cover matches the wire color as shown in the following table For Digital I O Slave Unit 37104 2124 000FL Green AWG22 0 3 mm2 to AWG20 0 5 mm2 sheath outer diameter 1 0 to 1 2 mm 37104 2165...

Page 128: ...in the following diagram 2 Insert the wire all the way to the back of the wire insertion opening Check that the sheath of the line is inserted into the wire insertion opening and that the end of the...

Page 129: ...nnecting to MIL Connector Terminals Use any of the following methods to connect to a MIL connector Use an OMRON MIL Cable Pressure weld a Flat Cable to a MIL Socket Pressure weld a loose wire cable to...

Page 130: ...2ML G79 O50 25 D1 50 cm G79 O75 50 D1 75 cm G7TC OC16 OC08 G7OD SOC16 VSOC16 G7OD FOM16 VFOM16 G7OA ZOC16 3 G7OD SOC08 G7OR SOC08 CRT1 VOD32ML 1 G79 O50 25 D1 50 cm G79 O75 50 D1 75 cm G7OD SOC16 1 G7...

Page 131: ...cut G79 Y100C 1 m G79 Y150C 1 5 m G79 Y200C 2 m G79 Y300C 3 m G79 Y500C 5 m Forked terminals are attached to the loose wires Forked terminal 161071 M2 Nippon Terminal CRT1 V D32ML 40 pins G79 A200C D...

Page 132: ...Red 18 Red 9 White Black 19 White Black 10 Red 20 Red Pin No Wire color Dots Dot color Pin No Wire color Dots Dot color 1 Light brown Black 21 Light brown Black 2 Red 22 Red 3 Yellow Black 23 Yellow B...

Page 133: ...release two latches on one side without releasing the latches on the other side 2 Insert the Flat Cable between the separated Socket sides line it up with the contacts align the contact side with the...

Page 134: ...on individual components refer to the Connectors Group Catalog Cat No G015 Component Wire size AWG24 Wire size AWG28 to AWG26 Socket No polarity guide XG5M 1031 N XG5M 1034 N Uses polarity guide XG5M...

Page 135: ...must be placed on the cable wires The applicable pin terminals are listed in the following table The pin terminal conductor should be about 8 to 10 mm in length Wiring to the Screw less Clamp Termina...

Page 136: ...the sealing The cables are held between the sealing section cover and sealing section housing to ensure resistance to splashing For cables with smaller outer diameters the sealing pieces can be used t...

Page 137: ...the housing as described above Tightening the Cover Finally close the cover and tighten the cover screws The tightening torque is 0 8 to 1 0 N m 3 6 6 Connecting to Compact Connectors The compact conn...

Page 138: ...te 1 Automated Crimp Tools are also available For details contact the manu facturer 2 For information on the processing procedure refer to the instruction man ual included with the tool or contact the...

Page 139: ...f Slave Units This section provides the basic specifications of the Slave Units 4 1 Basic Specifications of Slave Units 116 4 1 1 Communications Specifications 116 4 1 2 Performance Specifications 117...

Page 140: ...Units CompoNet Master Units Connectable Slave Units CompoNet Slave Units Maximum I O capacity Word Slave Units 1 024 inputs and 1 024 outputs 2 048 I O points total Bit Slave Units 256 inputs and 256...

Page 141: ...to 60 Hz with double amplitude of 0 7 mm 60 to 150 Hz and 50 m s2 in X Y and Z directions for 80 min each Shock resistance 150 m s2 3 times each in 6 directions on 3 axes Dielectric strength 500 VAC b...

Page 142: ...icipat ing Normal communications are in progress but the node is not yet participating in the network Lit red Fatal communications error The address is set out of range The same address has been set f...

Page 143: ...ck 177 5 3 13 Sixteen point Output Units 3 tier Terminal Block 183 5 3 14 Eight point Input and Eight point Output Units 3 tier Terminal Block 190 5 4 Units with Connectors 197 5 4 1 Eight point Input...

Page 144: ...ed to Master Unit The Digital I O Slave Unit has two status areas the Warning Status Area and the Alarm Status Area The status bit detection allocated to the master is OR of all slaves Bit Content Des...

Page 145: ...e node address set for the Unit Units with 16 I O points 8 inputs and 8 outputs are allocated two words the node address set for the Unit The data is allocated to the lower bytes of the words and the...

Page 146: ...O Unit Thirty two point Input Unit Thirty two point Output Unit Thirty two point I O Unit Input Area 1 2 3 4 5 6 7 0 Not used Output Area 1 2 3 4 5 6 7 0 Not used Input Area 1 2 3 4 5 6 7 8 9 10 11 12...

Page 147: ...rea Sixteen point Input Unit Eight point Expansion Output Unit Two node address areas are allocated Node address m in the Input Area and node address m in the Output Area Sixteen point Output Unit Six...

Page 148: ...utput Unit Eight point Expansion Input Unit Two node address areas are allocated Node address m in the Output Area and node address m in the Input Area Output Area 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 149: ...each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input curren...

Page 150: ...left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08 NPN Nam...

Page 151: ...O power supply NC 16 NC 17 NC 18 NC 7 NC 8 NC 9 1 2 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red Black White Blue Black Brown White B...

Page 152: ...ors prior to the revisions Dimensions Same for CRT1 ID08 and CRT1 ID08 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN...

Page 153: ...ent 0 5 A output 2 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 m...

Page 154: ...th the 10s digit set on the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communi...

Page 155: ...H BDL BS Internal circuits Physical layer DC DC converter not isolated Voltage drop 0 1 G V 24 VDC BS BDH BDL BS Photocoupler Photocoupler Internal circuits DC DC converter not isolated Physical layer...

Page 156: ...ctive load such as a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an external diode V 10 1 11 3 12 5 13 7 14 NC 15 G 1 0 2 2 3 4 4 6 5 NC 6 24 VDC...

Page 157: ...nications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector...

Page 158: ...age 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min...

Page 159: ...on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID16 NPN CRT1 ID16 1 PNP Name LED status I O status Meaning 0 to 15 Lit yellow Input ON The input is ON Not lit Input OFF...

Page 160: ...0 2 3 4 4 6 5 8 6 24 VDC I O power supply 11 16 13 17 15 18 10 7 12 8 14 9 1 2 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red Black Whi...

Page 161: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connecto...

Page 162: ...and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 16 outputs comm...

Page 163: ...switches is read when power is turned ON Internal Circuits CRT1 OD16 NPN CRT1 OD16 1 PNP Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The output is ON Not lit Output OFF The output...

Page 164: ...for absorbing the counterelectromotive force or install an external diode V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC I O power supply Solenoid valve etc 11 16 13 17 15 18 10 7 12 8...

Page 165: ...unications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connecto...

Page 166: ...rminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF curre...

Page 167: ...1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Power supply type Multi power supply Output handling for commu...

Page 168: ...0 G1 V2 24 VDC G2 DC DC converter not isolated Physical layer Internal circuits Photocoupler Photo coupler Voltage drop Photocoupler Photocoupler 1 DC DC converter not isolated Physical layer Interna...

Page 169: ...andards for photoelectric and proximity sensors The previous colors are shown in parentheses Solenoid valve etc Solenoid valve etc Brown red Brown white Blue black Blue black 3 wire sensor with NPN ou...

Page 170: ...cations Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector I...

Page 171: ...tions on 3 axes Dielectric strength 500 VAC between isolated circuits Insulation resistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to...

Page 172: ...decimal number with the 10s digit set on the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is...

Page 173: ...M BS BDH BDL BS DRTA NY5W K 5 VDC Internal circuits Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2...

Page 174: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Page 175: ...ide will bend out in the direction of the arrow releasing the hook 3 Using a tool such as a screwdriver press down on the relay socket lever and remove the Relay from the socket 0 1 0 3 0 5 1 3 5 2 3...

Page 176: ...esistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage t...

Page 177: ...the left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1...

Page 178: ...C SSR SSR 0 1 COM BS BDH BDL BS Internal circuits Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 CO...

Page 179: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Page 180: ...lated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage temperature 25 to 65 C Storage...

Page 181: ...f the output indicators are given in the following table Setting the Node Address The node address is set as a decimal number with the 10s digit set on the left rotary switch and the 1s digit set on t...

Page 182: ...oto coupler Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 COM0 OUT6 OUT4 OUT1 OUT3 OUT8 OUT7 OUT5...

Page 183: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Page 184: ...ide will bend out in the direction of the arrow releasing the hook 3 Using a tool such as a screwdriver press down on the relay socket lever and remove the Relay from the socket 30 VDC t 40 ms 30 VDC...

Page 185: ...esistance 20 M min between isolated circuits Ambient operating temperature 10 to 55 C Ambient operating humidity 25 to 85 with no condensation Ambient operating atmosphere No corrosive gases Storage t...

Page 186: ...he left rotary switch and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 f...

Page 187: ...coupler Photocoupler Photo coupler Physical layer DC DC converter for internal circuits not isolated DC DC converter for relay drive not isolated OUT0 OUT2 COM0 OUT6 OUT4 OUT1 OUT3 OUT8 OUT7 OUT5 OUT1...

Page 188: ...imensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When...

Page 189: ...input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms m...

Page 190: ...Section 5 3 Component Names and Functions Same for CRT1 ID08TA 1 CRT1 ID08TAH 1 Communications indicators MS and NS Node address switches 10 and 1 from left Communications connector I O terminal bloc...

Page 191: ...aximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08TA NPN Name LED status I O status Meaning 0 to 7 Lit yellow Input ON The input i...

Page 192: ...rter not isolated Input circuits BS BDH BDL BS V G Input 0 to 7 V Photocoupler Internal circuits Physical layer DC DC converter not isolated Input circuits V G0 to G7 G Disconnection or short circuit...

Page 193: ...ensor 2 wire sensor e g limit switch 0 V G V G V G V G 1 7 NC Brown white Black white Brown red Blue black Blue black 3 wire sensor with PNP output photoelectric sensor or proximity sensor 2 wire sens...

Page 194: ...en changed according to the revised JIS standards for photoelectric and proximity sensors The previous colors are shown in parentheses Brown white Black white Brown red Blue black Blue black 3 wire se...

Page 195: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 196: ...l and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disco...

Page 197: ...digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS Node address switches 10 and...

Page 198: ...ge drop Physical layer DC DC converter not isolated Internal circuits BS BDH BDL BS V 24 VDC G V G Output 0 to 7 Photocoupler Voltage drop Physical layer DC DC converter not isolated Internal circuits...

Page 199: ...pt for the I O power supply terminals 3 Do not wire NC terminals V G V V G G Output 0 to 7 Photo coupler Voltage drop BS BDH BDL BS Physical layer DC DC converter not isolated Internal circuits Discon...

Page 200: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 201: ...nput terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max...

Page 202: ...igit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS Node address switches 10 and 1...

Page 203: ...cal layer BS BDH BDL BS V1 24 VDC G1 G1 0 to 7 V1 V2 24 VDC G2 G2 8 to 15 V2 Photo coupler Photo coupler Internal circuits DC DC converter not isolated Input circuits Input circuits Physical layer G V...

Page 204: ...Brown red Blue black Blue black 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 3 wire sensor with NPN output photoelectric sensor or proximity se...

Page 205: ...white Brown red Blue black Blue black Brown white Black white Brown red Blue black Blue black 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 3 wi...

Page 206: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 207: ...etween each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per common 8 outputs common Load short circuit detection Supported...

Page 208: ...Section 5 3 Component Names and Functions Same for CRT1 OD16TA 1 CRT1 OD16TAH 1 Communications indicators MS and NS Node address switches 10 and 1 from left Output indicators 0 to 15 Communications co...

Page 209: ...e setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD16TA NPN Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The output is ON Not lit Output OFF T...

Page 210: ...converter not isolated Internal circuits Photocoupler Photocoupler Voltage drop Voltage drop BS BDH BDL BS G1 V1 G1 G2 V2 V2 Output 0 to 7 Output 8 to 15 Photocoupler Photocoupler Physical layer DC D...

Page 211: ...cuits Voltage drop Voltage drop Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit Solenoid valve etc 3 wire external device with NPN input Through beam...

Page 212: ...tive force or install an external di ode 4 Do not wire NC terminals Dimensions Same for CRT1 OD16TA 1 CRT1 OD16TAH 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Cable Dimensions when...

Page 213: ...Screw Terminal Blocks Section 5 3 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 106 37 mm 48 45 5 10 m...

Page 214: ...8 inputs Internal I O common NPN PNP NPN PNP ON voltage 15 VDC min between each input terminal and the V terminal 15 VDC min between each input terminal and the G terminal 10 5 VDC min between each i...

Page 215: ...ax 0 5 A DC between each output terminal and the G termi nal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load...

Page 216: ...ow Input or output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status Meaning 0 to 7 inputs Lit red Short circuit detection The power supply...

Page 217: ...not isolated Physical layer Internal circuits Photocoupler Photocoupler Voltage drop Input circuits 0 to 7 Internal circuits Photocoupler Voltage drop V G G V G V G BS BDH BDL BS DC DC converter not...

Page 218: ...ensor 3 wire external device with NPN input Through beam emitter of photoelectric sensor 2 wire sensor e g limit switch 0 V1 G1 V1 G1 V1 G1 V1 G1 1 7 0 V2 G2 V2 G2 V2 G2 V2 G2 1 7 NC NC Brown white Bl...

Page 219: ...JIS standards for photoelectric and proximity sensors The previous colors are shown in parentheses Solenoid valve etc 3 wire sensor with NPN output photoelectric sensor or proximity sensor 3 wire ext...

Page 220: ...munications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 221: ...he G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max in...

Page 222: ...he 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and...

Page 223: ...circuits Input circuits Short protection BS BDH BDL BS Internal circuits DC DC converter not isolated Physical layer Photo coupler Photo coupler V0 NC G IN0 V1 NC G IN1 Short protection Input circuits...

Page 224: ...t photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Black White Blue Black Brown Red Blue Black V V V V V V V V NC NC NC NC NC NC NC NC IN0 IN1 IN2 IN3 IN4 IN5 IN6 IN7 G0 G1 G2 G...

Page 225: ...en a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted mm The numbers inside the parenthese...

Page 226: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted mm 136 5 37 mm 48 10 mm 1...

Page 227: ...nal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 8 outputs common Isolation met...

Page 228: ...the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Output indicators 0 to 7 Communications indicato...

Page 229: ...BS BDH BDL BS Photo coupler Photo coupler V NC G OUT0 V NC G OUT1 V G DC DC converter not isolated Physical layer Internal circuits Voltage drop V NC G OUT0 V NC G OUT1 V G BS BDH BDL BS Photo coupler...

Page 230: ...rnal device with NPN input Through beam emitter of photoelectric sensor V V V V V V V V NC NC NC NC NC NC NC NC G G G G G G G G 1 2 3 4 OUT 0 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 G V Blue black B...

Page 231: ...en a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 23 101 7 90 6 4 5 3 60 66 2 102 96 7...

Page 232: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted mm 136 5 37 mm 48 10 mm 1...

Page 233: ...the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 11 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Power supply short circuit detec tion Operates at 50 mA...

Page 234: ...ting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID16S NPN Name LED status I O status Meaning 0 to 15 Lit yellow Input ON The input is ON Not lit Input OFF The input...

Page 235: ...C G1 IN1 BS BDH BDL BS Internal circuits DC DC converter not isolated Physical layer Input circuits Input circuits Photo coupler Photo coupler Disconnection or short circuit detection circuit Disconne...

Page 236: ...NC G11 IN 11 V NC G12 IN 12 V NC G13 IN 13 V NC G14 IN 14 V NC G15 IN 15 3 4 1 2 3 4 G0 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Brown Red...

Page 237: ...ommunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connec...

Page 238: ...tput terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection detec tion Operates at 3 mA point max Does not...

Page 239: ...rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and 1 from left Output indicators 0 to...

Page 240: ...otocoupler Photocoupler V NC G OUT1 V NC G OUT0 V G G V Internal circuits DC DC converter not isolated Physical layer Voltage drop Voltage drop Internal circuits Voltage drop Photocoupler Photocoupler...

Page 241: ...isolated Physical layer BS BDH BDL BS Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit V NC G OUT1 V V G G NC V G OUT0 Internal circuits Voltage drop P...

Page 242: ...ither V terminal Connection can be made to either G terminal V NC G OUT 8 NC G OUT 9 NC G OUT 10 NC G OUT 11 NC G OUT 12 NC G OUT 13 NC G OUT 14 NC G OUT 15 1 2 3 4 V V V V V V V V G V NC G OUT 0 NC G...

Page 243: ...Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Conn...

Page 244: ...ecification Model CRT1 MD16S CRT1 MD16S 1 CRT1 MD16SH CRT1 MD16SH 1 I O capacity 8 inputs Internal I O common NPN PNP NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10...

Page 245: ...ter minal and the G terminal 1 2 V max 0 5 A DC between each output ter minal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Suppor...

Page 246: ...ame LED status I O status Meaning 0 to 7 inputs 0 to 7 outputs Lit yellow Input or output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status...

Page 247: ...ernal circuits Photo coupler Photocoupler V1 NC G0 IN0 V NC G OUT0 V G G V Physical layer Input circuits Short protection Voltage drop Internal circuits V0 NC G1 IN0 V V G G NC V G OUT0 BS BDH BDL BS...

Page 248: ...rcuits Voltage drop Internal circuits Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit BS BDH BDL BS DC DC converter not isolated Photo coupler Photoco...

Page 249: ...proximity sensor 3 wire external device with NPN input Through beam emitter of photoelectric sensor 2 wire sensor e g limit switch Brown Red Black White Blue Black Brown White Blue Black Solenoid valv...

Page 250: ...the JIS stan dards for photoelectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions Solenoid valve etc 3 wire sensor with PNP output photoelectric sensor o...

Page 251: ...mmunications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connec...

Page 252: ...FF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 11 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Power supply short circuit detec tion Operates at 50 mA point min Dis...

Page 253: ...ry switches is read when power is turned ON Internal Circuits CRT1 ID32S NPN Name LED status I O status Meaning 0 to 15 IN1 0 to 15 IN2 Lit yellow Input ON The input is ON Not lit Input OFF The input...

Page 254: ...C G1 IN1 BS BDH BDL BS Photo coupler Photo coupler Input circuits Input circuits Internal circuits DC DC converter not isolated Physical layer Disconnection or short circuit detection circuit Disconne...

Page 255: ...NC G1 IN 1 V NC G2 IN 2 V NC G3 IN 3 V NC G4 IN 4 V NC G5 IN 5 V NC G6 IN 6 V NC G7 IN 7 V NC G8 IN 8 1 2 V NC G9 IN 9 V NC G10 IN 10 V NC G11 IN 11 V NC G12 IN 12 V NC G13 IN 13 V NC G14 IN 14 V NC...

Page 256: ...mmunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 257: ...5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection detec tion Operates at...

Page 258: ...ss is 63 The setting on the rotary switches is read when power is turned ON Communications connector Node address switches 10 and 1 from left Output indicators 0 to 15 OUT1 Communications indicators M...

Page 259: ...ide Right side V NC G OUT0 V G G V V NC G OUT0 V G G V Internal circuits DC DC converter not isolated Physical layer Voltage drop Voltage drop V V G G NC V G OUT0 V V G G NC V G OUT0 BS BDH BDL BS Pho...

Page 260: ...sical layer Voltage drop Voltage drop Disconnection or short circuit detection circuit Disconnection or short circuit detection circuit V V G G NC V G OUT0 V V G G NC V G OUT0 BS BDH BDL BS Photocoupl...

Page 261: ...white Blue black 3 wire external device with NPN input Through beam emitter of photoelectric sensor Brown red Pink white Blue black 3 wire external device with NPN input Through beam emitter of photo...

Page 262: ...mmunications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connect...

Page 263: ...pecification Model CRT1 MD32S CRT1 MD32S 1 CRT1 MD32SH CRT1 MD32SH 1 I O capacity 16 inputs Internal I O common NPN PNP NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 1...

Page 264: ...G terminal 1 2 V max 0 5 A DC between each output ter minal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Load short circuit detection Supported Disconnection...

Page 265: ...output ON The input or output is ON Not lit Input or output OFF The input or output is OFF Name LED status I O status Meaning 0 to 15 inputs Lit red Short circuit detection The power supply is short c...

Page 266: ...e Right side DC DC converter not isolated Physical layer Internal circuits Input circuits Voltage drop Short protection BS BDH BDL BS Photo coupler Photocoupler Left side Right side V NC G0 IN0 V NC G...

Page 267: ...limit switch V NC IN 0 V NC G1 IN 1 V NC G2 IN 2 V NC G3 IN 3 V NC G4 IN 4 V NC G5 IN 5 V NC G6 IN 6 V NC G7 IN 7 V NC G8 IN 8 1 2 V NC G9 IN 9 V NC G10 IN 10 V NC G11 IN 11 V NC G12 IN 12 V NC G13 IN...

Page 268: ...N 5 V6 NC G IN 6 V7 NC G IN 7 V8 NC G IN 8 1 2 V9 NC G IN 9 V10 NC G IN 10 V11 NC G IN 11 V12 NC G IN 12 V13 NC G IN 13 V14 NC G IN 14 V15 NC G IN 15 3 4 1 2 3 4 G V NC G OUT 8 NC G OUT 9 NC G OUT 10...

Page 269: ...nications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector...

Page 270: ...l 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 ms max Number of...

Page 271: ...h and the 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 VID16ML NPN Name LED sta...

Page 272: ...rter not isolated Physical layer Photo coupler 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch Blue Black Brown White Blue Black Brown Red Black W...

Page 273: ...ernally connected 3 wire sensor with PNP output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 IN 7 IN 6 IN 5 IN 4 IN 3 IN 2...

Page 274: ...1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 5 3 78 7 60 15 21 5 92 8 85 7 1...

Page 275: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 136 5 mm 48 10 mm 25 4...

Page 276: ...See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5...

Page 277: ...e 1s digit set on the front side rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 from mounted side Output...

Page 278: ...VOD16ML 1 PNP BS BDH BDL BS Internal circuits Photo coupler Photo coupler V OUT0 OUT1 G DC DC converter not isolated Voltage drop Physical layer BS BDH BDL BS Photo coupler Photo coupler V OUT0 OUT1...

Page 279: ...e the output power supply externally rather than from the terminals Solenoid valve etc Solenoid valve etc 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 G V G V OUT 7 OUT 6 OUT 5 OUT 4 OUT 3 OUT 2...

Page 280: ...or install an ex ternal diode Dimensions Same for CRT1 VOD16ML and CRT1 VOD16ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable W...

Page 281: ...ts with Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 136 5 mm 48 10 mm 25 4...

Page 282: ...minal and the V terminal 17 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G...

Page 283: ...set on the front side rotary switch The maximum node address is 62 The setting on the rotary switches is read when power is turned ON Input indicators I 0 to 15 II 0 to 15 Communications indicators M...

Page 284: ...BS BDH BDL BS Photo coupler V IN0 IN1 G Input circuits Input circuits Internal circuits DC DC converter not isolated Physical layer Photo coupler BS BDH BDL BS Photo coupler V IN0 IN1 G Input circuits...

Page 285: ...IN 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G...

Page 286: ...N 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G V V IN 0 IN 2 IN 3 IN 4 IN 5 IN 6 IN 7 IN 8 IN 9 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 IN 1 G G V V 2 wire sensor e g limit switch Brown W...

Page 287: ...ions Same for CRT1 VID32ML and CRT1 VID32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug...

Page 288: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Page 289: ...ON simultaneously at an ambient operating temperature of 55 C When Units Are Mounted Facing Upwards If 32 points may be turned ON simultaneously the distance between the Units must be restricted depe...

Page 290: ...n See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0...

Page 291: ...on the front side rotary switch The maximum node address is 62 The setting on the rotary switches is read when power is turned ON Output indicators I 0 to 15 II 0 to 15 Communications indicators MS a...

Page 292: ...VOD32ML 1 PNP BS BDH BDL BS Photo coupler V OUT0 OUT1 G Internal circuits DC DC converter not isolated Physical layer Photo coupler Voltage drop V OUT0 OUT1 G Voltage drop Internal circuits BS BDH BD...

Page 293: ...0 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 G G V V G G V V OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT 0 2 3 4 5 6 7 8 9 10 11 12 1...

Page 294: ...allocated words and bits when the first word for a Slave Unit allocated in the Master Unit is n 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 3...

Page 295: ...ions Same for CRT1 VOD32ML and CRT1 VOD32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug...

Page 296: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Page 297: ...nsumption 45 mA max for 24 VDC power supply voltage 70 mA max for 14 VDC power supply voltage Weight 110 g max Item Specification Model CRT1 VMD32ML CRT1 VMD32ML 1 I O capacity 16 inputs Internal I O...

Page 298: ...rrent 0 3 A output 2 A common See note Residual voltage 1 2 V max 0 3 A DC between each output terminal and the G terminal 1 2 V max 0 3 A DC between each output terminal and the V terminal Leakage cu...

Page 299: ...on the rotary switches is read when power is turned ON Internal Circuits CRT1 VMD32ML NPN Name LED status I O status Meaning I 0 to I 15 word m Lit yellow Input or output ON The input or output is ON...

Page 300: ...nits with Connectors Section 5 4 CRT1 VMD32ML 1 PNP V1 IN0 G1 V2 OUT0 G2 BS BDH BDL BS Photo coupler Internal circuits DC DC converter not isolated Physical layer Photo coupler Voltage drop Input circ...

Page 301: ...5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 G1 G1 V1 V1 G2 G2 V2 V2 OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT 0 2 3 4 5...

Page 302: ...as a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an ex ternal diode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 2...

Page 303: ...RT1 VMD32ML 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted 0 1 2 3 4 5 6 7 8 9...

Page 304: ...ith Connectors Section 5 4 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 134 6 mm 41 9 48 10 mm 25...

Page 305: ...ON simultaneously at an ambient operating temperature of 55 C When Units Are Mounted Facing Upwards If 16 points may be turned ON simultaneously the distance between the Units must be restricted depe...

Page 306: ...and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 mA max Input current At 24 VDC 6 0 mA max input At 17 VDC 3 0 mA min input ON delay 1 5 ms max OFF delay 1 5 m...

Page 307: ...and the 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 ID08SL NPN Name LED status I O...

Page 308: ...r to the revisions G V V G G V BS BDH BDL BS 0 to 7 Photocoupler Internal circuits DC DC converter not isolated Physical layer 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2...

Page 309: ...ed Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Page 310: ...e V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 8 outputs common Isolation method Photocoupler Output indicators LED yellow Installation...

Page 311: ...1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD08SL NPN Name LED status I O status M...

Page 312: ...al diode V G V V G G BS BDH BDL BS 0 to 7 Photo coupler Voltage drop Internal circuits Physical layer DC DC converter not isolated Solenoid valve etc 3 wire external device with NPN input Through beam...

Page 313: ...hen a DCN4 TB4 Open Type Connector Is Mounted Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II...

Page 314: ...ach input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal OFF current 1 0 mA max Input current...

Page 315: ...he 1s digit set on the right rotary switch The maximum node address is 63 The setting on the rotary switches is read when power is turned ON Node address switches 10 and 1 from left Input indicators 0...

Page 316: ...rter not isolated G V 0 to 15 Phy sical layer Photocoupler G V G V BS BDH BDL BS Internal circuits DC DC converter not isolated V G 0 to 15 Phy sical layer Photocoupler V G V G 3 wire sensor with NPN...

Page 317: ...r to the revisions Dimensions Same for CRT1 ID16SL and CRT1 ID16SL 1 When a DCN4 TB4 Open Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR...

Page 318: ...Clamp Terminal Blocks Section 5 5 When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 106 37 mm 45 5 48 10 m...

Page 319: ...5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per com mon 16 outputs common Isolation method Photocoupl...

Page 320: ...maximum node address is 63 The setting on the rotary switches is read when power is turned ON Internal Circuits CRT1 OD16SL NPN Name LED status I O status Meaning 0 to 15 Lit yellow Output ON The out...

Page 321: ...not wire NC terminals BS BDH BDL BS Internal circuits V G 0 to 15 Physical layer Photocoupler V V G G Voltage drop DC DC converter not isolated Solenoid valve etc 3 wire external device with NPN input...

Page 322: ...d Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Page 323: ...em Specification Model CRT1 MD16SL CRT1 MD16SL 1 I O capacity 8 inputs Internal I O common NPN PNP ON voltage 15 VDC min between each input terminal and the V terminal 15 VDC min between each input te...

Page 324: ...d the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of circuits per common 8 outputs common I...

Page 325: ...n power is turned ON Internal Circuits CRT1 MD16SL NPN Name LED status I O status Meaning 0 to 7 inputs 0 to 7 outputs Lit yellow Input or output ON The input or output is ON Not lit Input or output O...

Page 326: ...onverter non isolated Physical layer 0 to 7 Solenoid valve etc 3 wire external device with NPN input Through beam emitter of photoelectric sensor Brown white Black white Brown red Blue black Blue blac...

Page 327: ...e force or install an ex ternal diode 3 Do not wire NC terminals 4 Wire colors have been changed according to revisions in the JIS stan dards for photoelectric and proximity sensors The colors in pare...

Page 328: ...d Communications Cable Dimensions when Connector and Cable Are Connected When a DCN4 BR4 Flat Connector I Plug Is Mounted When a DCN5 BR4 Flat Connector II Plug Is Mounted When a DCN4 TB4 Open Type Co...

Page 329: ...Data 319 6 3 2 I O Data Type and Allocation 322 6 4 Status Areas 322 6 4 1 Analog Input Slave Unit Status Area 323 6 4 2 Analog Output Slave Unit Status Area 324 6 5 Analog Data Monitor 325 6 6 Units...

Page 330: ...he speed of the conversion cycle 4 Moving average function Averages the most recent 8 values of the analog input value This provides a smooth input value for an input that oscillates Disabled Scaling...

Page 331: ...n be utilized by the user reducing the calculation load on the ladder pro gram in the Master Unit Disabled 0 to 6 000 User adjustment Shift generated from measurement error due to hardware can be adju...

Page 332: ...onverted to data from 0000 to 1770 Hex 0 to 6000 The input data range for which conversion is possible is 0 25 to 5 25 V and here the output data is FED4 to 189C Hex 300 to 6300 When input data is a n...

Page 333: ...rom F448 to 0BB8 Hex 3000 to 3000 The input data range for which conversion is possible is 11 to 11 V and here the output data is F31C to 0CE4 Hex 3300 to 3300 When input data is a negative voltage it...

Page 334: ...nected line input current is less than 3 04 mA a disconnected line detection function activates and data is set to 7FFF Hex Input Range Settings Setting of input range is performed using Analog Input...

Page 335: ...conversion can be used to obtain the absolute value of the two s complement 6 2 2 Calculation and Selection Processing of Input Data Input Data Calculation The following types of calculations can be...

Page 336: ...ing Trip Point High H Warning Trip Point Low L Alarm Trip Point Low LL can be performed Comparator function Input Moving average Scaling A A Analog input value Peak Bottom Top Valley Rate of change Cu...

Page 337: ...top value valley value and rate of change is selected and allocated The default is allocation of the ana log value Note The comparator function can be used with regards to the value allocated to anal...

Page 338: ...d select Parameters Edit from the pop up menu 3 Select the tab of the channel to select the analog data you want and select the type of allocation data from the Analog Data 1 Allocation pull down list...

Page 339: ...Unit 2 Double click the icon of the Analog Input Unit to set in the Network Config uration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from t...

Page 340: ...e one shot time can be changed For details refer to the one shot time set tings for the top valley hold function Analog Status Flags The Analog Status Flags include allocations for the Comparator Resu...

Page 341: ...set ting 1 Lx Low Limit Alarm Flag Turns ON when the value of data allocated in Analog Data 1 drops below the Low Limit alarm setting 2 PSx Normal Flag pass signal Turns ON when none of the alarms Hi...

Page 342: ...0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 Lower byte 9 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0 Upper byte 15 8 7 0 1 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 0 0 0 0 HD3 HD2 HD1 HD0 Lower byte 1 0 0 0 0 0 0...

Page 343: ...low limit Output Range and Conversion Data Output Range 0 to 5 V Data of 0000 to 1770 Hex 0 to 6000 is converted to voltage from 0 to 5 V and output The output data range for which conversion is poss...

Page 344: ...this case the output data becomes from 11 to 11 V Negative voltages are specified as two s comple ments 16 bits Output Range 4 to 20 mA Data of 0000 to 1770 Hex 0 to 6000 is converted to current from...

Page 345: ...Integrator on page 481 regarding details for CX Inte grator 1 2 3 1 Turn ON the power to the CompoNet Slave Unit 2 Double click the icon of the Analog Output Unit to set in the Network Con figuration...

Page 346: ...two s complements 6 4 Status Areas An Analog I O Slave Unit has two status areas the Warning Status Area and the Alarm Status Area The status flags in these areas are turned ON and OFF based on the th...

Page 347: ...supply voltage is reduced below the set monitor value 3 Unit Maintenance Flag OFF Normal ON Error Higher than the monitor value Turns ON when the cumulative total unit conduction time exceeds the set...

Page 348: ...g Hardware Error Flag OFF Normal ON Error Turns ON when there is an error in the analog circuits in the Unit 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Bit Content Descrip...

Page 349: ...Integrator Monitor screen 10 Reserved 11 Reserved 12 Reserved 13 Reserved 14 Reserved 15 Reserved Bit Content Description Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Erro...

Page 350: ...nit Con duction Time Displays the total time that the Unit has been ON cumulative power ON time Present Network Power Voltage Displays the present network power supply voltage Network Power Voltage Pe...

Page 351: ...tab Buttons Clear Button Click this button to clear the displayed values Update Button Click this button to update the Maintenance informa tion Save Mainte nance Counter Button Click this button to sa...

Page 352: ...eing held in the unit Min Value Status check boxes Over Range Turns ON if the analog data exceeds the upper limit of the displayable range High Alarm Over Turns ON if the analog data exceeds the set m...

Page 353: ...d Cumu lated Counter Over Turns ON when the time integrated values increases above the monitor value set by the cumulated count function Cumulated Counter Overflow Selected when there is an overflow i...

Page 354: ...ata 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 0000 to 1770 hex full scale 0 to 6 000 AD conversion range 5 FS of the above data ranges Isolation method Photocoupler isol...

Page 355: ...ot be enabled 3 The DIP switch settings are read when the power is turned ON Input CH0 CH1 range common 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 1s digit of node address 10s digit of node address Pin N...

Page 356: ...Circuits Terminal Arrangements Communications Connector Analog I O Terminal Block Input range Pin 4 Pin 5 Pin 6 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to...

Page 357: ...ance 1 k min 600 max Resolution 1 6 000 full scale Overall accuracy 25 C 0 4 FS 0 4 FS See note 10 to 55 C 0 8 FS 0 8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F44...

Page 358: ...DE ADR X10 0 63 X1 ON SW A D 1 2 3 4 5 6 7 8 INPUT RANGE CH0 1 INPUT RANGE CH2 3 RSV LSET 1 2 3 4 5 6 7 8 0 1 2 3 456 7 8 9 0 1 2 3 456 7 8 9 ANALOG TERMINAL CRT1 CRT1 DA02 DA02 DIP switch for setting...

Page 359: ...ernal Circuits Wiring Communications Connector Output range Pin 1 Pin 2 Pin 3 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to 20 mA OFF OFF ON 0 to 20 mA ON OFF...

Page 360: ...k Dimensions External device Output 1 Current output NC I0 V1 I1 1 NC V0 0 NC NC NC NC NC NC NC NC NC NC V0 V1 Voltage output terminal I0 I1 Current output terminal 0 1 Voltage current output terminal...

Page 361: ...prox 250 Resolution 1 6 000 full scale Overall accuracy 25 C 0 3 FS 0 4 FS 10 to 55 C 0 6 FS 0 8 FS Conversion cycle 1 ms 1 point AD conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000...

Page 362: ...is turned ON Input range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators MS and NS I O connector e CON connector Sensor power supply con...

Page 363: ...se the CX Integrator rather than the DIP switch to make the settings 2 Do not set the DIP switches or pins other than as specified in the table above Sensor Power Supply Mode Settings Switch 4 Input C...

Page 364: ...4 Input CH3 sensor power supply mode toggle Pin No Setting Specification 1 Input CH0 voltage current input mode toggle OFF Voltage input ON Current input Default setting is OFF 2 Input CH1 voltage cur...

Page 365: ...sor power supply mode settings switch Analog GND 24 VDC Sensor power supply Sensor power supply connector Input type Sensor power supply mode settings switch Voltage Current input mode settings switch...

Page 366: ...ON Power supply for 3 wire sensor ON Current input 24 VDC Sensor power supply n Voltage current input 0V Sensor power supply 4 3 2 1 n Voltage current input I O connector 24 VDC Sensor power supply 4...

Page 367: ...Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted 92 8 85 7 102 96 7 90 90 101 7 5 3 6 4 23 60 66 2 mm The...

Page 368: ...its with Connectors Section 6 7 When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 mm 136 5 mm 48 10 25 4 m...

Page 369: ...8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 0000 to 1770 hex full scale 0 to 6 000 DA conversion range 5 FS...

Page 370: ...t pin 8 to ON if the DIP switch is used to set the ranges If this pin is OFF the DIP switch settings will not be enabled 3 The DIP switch settings are read when power is turned ON 0 1 2 3 4 5 6 7 8 9...

Page 371: ...to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10 to 10 V ON ON OFF 4 to 20 mA OFF OFF ON 0 to 20 mA ON OFF ON Output range Pin 4 Pin 5 Pin 6 0 to 5 V OFF OFF OFF 1 to 5 V ON OFF OFF 0 to 10 V OFF ON OFF 10...

Page 372: ...ng for Current Output Dimensions When a DCN4 TB4 Open Type Connector Is Mounted Analog GND In Vn n 3 4 2 4 3 2 1 External device I O connector 4 3 2 1 External device I O connector 92 8 85 7 102 96 7...

Page 373: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is...

Page 374: ...000 full scale Overall accuracy 25 C 0 3 FS 0 4 FS 10 to 55 C 0 6 FS 0 8 FS Conversion cycle 1 ms 1 point AD conversion data 10 to 10 V range F448 to 0BB8 hex full scale 3 000 to 3 000 Other ranges 00...

Page 375: ...switch settings are read when power is turned ON Input range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators MS and NS Input range swit...

Page 376: ...e the CX Integrator rather than the DIP switch to make the settings 2 Do not set the DIP switches or pins other than as specified in the table above Voltage Current Input Mode Settings Switch 4 Input...

Page 377: ...t mode toggle 4 Input CH3 voltage current input mode toggle BS BDH BDL BS Communications power supply Communications data high Communications data low Communications power supply Pin No Signal name Pi...

Page 378: ...250 n n Analog GND Voltage Current input mode settings switch Input type Voltage Current input mode settings switch Voltage input OFF Voltage input Current input ON Current input n RSV n AG n Voltage...

Page 379: ...munications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is...

Page 380: ...k min 600 max Resolution 1 6 000 full scale Overall accuracy 25 C 0 4 FS 0 4 FS See note 10 to 55 C 0 8 FS 0 8 FS See note Conversion cycle 2 ms 2 points DA conversion data 10 to 10 V range F448 to 0...

Page 381: ...ode address is 63 Rotary switch settings are read when power is turned ON Output range switch Top Front Bottom Mounted side Node address switches 10 and 1 from mounted side Communications indicators M...

Page 382: ...or output CH1 See the next table Default setting All pins OFF 5 6 7 Always OFF Always set this pin to OFF Malfunctions may occur if it is set to ON 8 Range setting method OFF Use CX Integrator ON Use...

Page 383: ...urrent Output Pin No Signal name Pin No Signal name 1 V0 Voltage output 2 V1 Voltage output 3 I0 Current output 4 I1 Current output 5 0 Voltage current output 6 1 Voltage current output 7 N C 8 N C 9...

Page 384: ...Type Connector Is Mounted Communications Connector Dimensions Including the Connector and Cable When a DCN4 BR4 Flat Connector Plug Is Mounted 92 8 85 7 102 96 7 90 90 101 7 5 3 6 4 15 60 78 73 mm The...

Page 385: ...its with Connectors Section 6 7 When a DCN5 BR4 Flat Connector Plug Is Mounted When a DCN4 TB4 Open Type Connector Is Mounted When a DCN4 MD4 Multidrop Connector Is Mounted 37 mm 136 5 mm 48 10 25 4 m...

Page 386: ...362 Units with Connectors Section 6 7...

Page 387: ...64 7 1 2 List of Data Processing Functions 364 7 1 3 Temperature Input Unit Display Modes 365 7 2 Overview of Temperature Input Units 367 7 2 1 Math Operations and Processing Input Data 367 7 2 2 I O...

Page 388: ...aximum and minimum temperature input val ues Disabled Top valley hold Holds the top and valley temperature input values Disabled Rate of change Calculates the rate of change for temperature input val...

Page 389: ...c imal place the value sent to the master will be 10 times the actual value The decimal point is omitted Example 1 R type thermocouple at 1 000 C 1 000 converted to hexadecimal 03E8 hex Example 2 U ty...

Page 390: ...in the Network Configuration Window or right click the icon and select Parameter Edit to open the Configuration Window 3 Click the General Tab and select Temperature Data1 1 100 in the Default Connect...

Page 391: ...h between values Treat any values displayed in Normal Display Mode beyond the specified input resolution as reference data 7 2 Overview of Temperature Input Units 7 2 1 Math Operations and Processing...

Page 392: ...L and LL can be performed for Temperature Data 1 This is called the comparator function Flow of Data in Temperature Input Units In a Temperature Input Unit it is possible to switch the display mode of...

Page 393: ...Display mode Set from CX Integrator 1 100 Display Mode 2 words input Temperature Data 1 allocated I O data Normal Display Mode 1 word input Data can be allocated for I O as Temperature Data 1 in eithe...

Page 394: ...rate of change The temperature input value is allocated by default Note The comparator function can be used with the value allocated as Temperature Data 1 Top Valley Detection Timing Flags 1 input wor...

Page 395: ...own in the following dia gram If the 1 100 Display Mode is set for the temperature input value with the CX Integrator eight words sixteen bytes will be allocated in the Master s Input Area as shown in...

Page 396: ...he Default Con nection Path In Field The following example shows selecting the temper ature data and status flags 4 Click the Transfer PC to Unit Button to download the data and then click the Reset B...

Page 397: ...ted in the Master Unit is shown below 2 words 4 bytes 15 0 First word 0CH Temperature Data 1 for Input CH0 First word 1CH Temperature Data 1 for Input CH1 First word 2CH Temperature Data 1 for Input C...

Page 398: ...Low Limit alarm setting 1 Lx Low Limit Alarm Flag Turns ON when the value of data allocated in Temperature Data 1 drops below the Low Limit alarm setting 2 PSx Normal Flag pass signal Turns ON when n...

Page 399: ...4 7 6 9 8 11 10 13 12 15 14 17 16 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0 Temperature Data 1 for Input CH0 Lower Word Lower byte 1 Upper byte 2 Temperature Data 1 for Input CH0 Upper Word L...

Page 400: ...notices of the status flag in the Master Unit turns ON The Temperature Input Unit s status area information can be read by using the CX Integrator or explicit messages 15 8 7 0 1 0 Bit 7 Bit 6 Bit 5...

Page 401: ...itoring 4 Reserved Cannot be used 5 Reserved Cannot be used 6 Reserved Cannot be used 7 Reserved Cannot be used 8 Temperature Input Warning Flag OFF Within range below set moni tor value ON Out of ran...

Page 402: ...et monitor value Turns ON when the number of tops or valleys exceeds the set monitor value 13 Reserved Cannot be used 14 Reserved Cannot be used 15 Reserved Cannot be used Bit Content Description Bit...

Page 403: ...has exceed the monitor value set by the Unit Conduction Time Monitor Function Network Power Voltage Drop Selected if the network power supply voltage has fallen below the monitor value set by the Net...

Page 404: ...lue Displays the present temperature input value Peak Value Display the peak value bottom value top value and valley value of the temperature data retained by the Unit Bottom Value Top Value Valley Va...

Page 405: ...er Selected when the cumulated time exceeds the monitor value set for the Cumulative Temperature Function Cumulative Counter Overflow Selected when there is an overflow in the cumu lative counter valu...

Page 406: ...on Time Displays the total time that the network power supply had been ON when the error occurred Clear Button Clears the error history Item Specifications Model CRT1 TS04T CRT1 TS04P Input type Switc...

Page 407: ...signals Photocoupler isolation Mounting method 35 mm DIN track mounting See note Communications power supply current 75 mA max at 24 VDC 110 mA max at 14 VDC 75 mA max at 24 VDC 110 mA max at 14 VDC W...

Page 408: ...3 nodes can be set Note The rotary switch settings are read when the power is turned ON 0 1 2 3 4 567 8 9 0 1 2 3 4 567 8 9 T S S Communications connector Communications indicators MS and NS Node addr...

Page 409: ...C or F display OFF C conversion ON F conversion Default setting OFF SW7 Always OFF Always set this pin to OFF Malfunctions may occur if it is set to ON SW8 Selects the input type set ting method OFF...

Page 410: ...wer supply to the Temperature Input Unit 2 Double click the icon of the Temperature Input Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Confi...

Page 411: ...ture range C Temperature range F Input type Temperature range C Temperature range F PT100 200 to 850 C 200 0 to 850 0 300 0 to 1 500 0 PT100 200 to 200 C 200 0 to 200 0 300 0 to 380 0 Input type C Dis...

Page 412: ...on broken or disconnected input wire will be detected and the temperature data will be set to 7FFF Hex If the input temperature returns to the convertible range the off wire detection function will be...

Page 413: ...detection wire the unused input terminals as shown in the following diagram Alternatively set the Input Error Detection Disable Function from the CX Integrator Dimensions Same for CRT1 TS04T and CRT1...

Page 414: ...390 Temperature Input Units Section 7 5...

Page 415: ...tion describes the Expansion Units 8 1 Expansion Units 392 8 2 Expansion Unit Specifications 394 8 2 1 Eight point Input Units 394 8 2 2 Eight point Output Units 397 8 2 3 Sixteen point Input Units 40...

Page 416: ...properly mated I O Power Supply If an Expansion Input Unit is connected to a Digital Input Slave Unit then I O power must be supplied only to the Digital I O Slave Unit If any other combi nation of U...

Page 417: ...le CRT1 ID16 XWT ID16 Not required The Expansion Unit uses the same I O power supply as the Digital I O Slave Unit Digital Input Slave Unit with Expan sion Output Unit Example CRT1 ID16 XWT OD16 Requi...

Page 418: ...en each input terminal and the V terminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input te...

Page 419: ...24 VDC 0 1 G Photocoupler Internal circuits Photocoupler V 24 VDC 0 1 G Photocoupler Internal circuits V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Brown White Blue Black 3 wire s...

Page 420: ...ensors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for XWT ID08 and XWT ID08 1 V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Blue Black Brow...

Page 421: ...outputs Rated output current 0 5 A output 2 0 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V te...

Page 422: ...Specifications Section 8 2 Internal Circuits XWT OD08 NPN XWT OD08 1 PNP 0 1 G V 24 VDC Internal circuits Photocoupler Photocoupler Voltage drop 0 1 G V 24 VDC Internal circuits Photocoupler Photocou...

Page 423: ...diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for XWT OD08 and XWT OD08 1 V 6 1 7 3 8 5 9 7 10 G 1 0 2 2 3 4 4 6 5 24 VDC I O power supply Solenoid v...

Page 424: ...the V terminal 15 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max between each input terminal and the V terminal 5 VDC max between each input terminal and the G terminal O...

Page 425: ...circuits Photocoupler V 24 VDC 0 1 G Photocoupler Internal circuits Photocoupler V 10 1 11 3 12 5 13 7 14 9 15 G 0 2 3 4 4 6 5 8 6 24 VDC I O power supply 11 16 13 17 15 18 10 7 12 8 14 9 1 2 Brown Wh...

Page 426: ...rentheses are the wire colors prior to the revisions Dimensions Same for XWT ID16 and XWT ID16 1 V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC 11 16 13 17 15 18 10 7 12 8 14 9 I O power...

Page 427: ...ted output current 0 5 A output 4 0 A common Residual voltage 1 2 V max 0 5 A DC between each output terminal and the G terminal 1 2 V max 0 5 A DC between each output terminal and the V terminal Leak...

Page 428: ...Specifications Section 8 2 Internal Circuits XWT OD16 NPN XWT OD16 1 PNP 0 1 G V 24 VDC Internal Circuits Photocoupler Photocoupler Voltage drop 0 1 G V 24 VDC Internal Circuits Photocoupler Photocou...

Page 429: ...force or install an external diode Dimensions Same for XWT OD16 and XWT OD16 1 V 10 1 11 3 12 5 13 7 14 9 15 G 1 0 2 2 3 4 4 6 5 8 6 24 VDC 11 16 13 17 15 18 10 7 12 8 14 9 I O power supply Solenoid v...

Page 430: ...406 Expansion Unit Specifications Section 8 2...

Page 431: ...4 Two point Output Units IP54 423 9 3 5 Four point Input Units IP54 427 9 4 Clamp Terminal Blocks 432 9 4 1 Two point Input Two point Output Units IP54 432 9 5 Bit Slave Units with Compact Connectors...

Page 432: ...Transmitted to Master Unit The Bit Slave Unit has two status areas the Warning Status Area and Alarm Status Area The status bit detection allocated to the master is OR of all slaves Bit Content Descri...

Page 433: ...ocated four bits the input and output node address areas Two point Input Units Four point Input Units Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Error occurred Turns ON...

Page 434: ...bit input area 0 is input Four point I O Units Bit Slave Units are allocated node address areas in order without leaving any bits unused in the middle For example eight two point Slave Units are allo...

Page 435: ...apacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G terminal OFF voltage 5 VDC max be...

Page 436: ...n the middle rotary switch and the 1s digit set on the right rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators 0 and 1...

Page 437: ...l circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protection circuit DC DC converter not isolated Internal circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protectio...

Page 438: ...nsors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02S and CRT1B ID02S 1 Brown Red Black White Blue Black 2 wire sensor e g limit switch 3 wire sens...

Page 439: ...em Specification Model CRT1B OD02S CRT1B OD02S 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 2 A output Load power supply voltage Communications power supply voltage 0 V...

Page 440: ...rotary switch and the 1s digit set on the right rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators 0 and 1 Power short...

Page 441: ...D02S NPN Internal Circuits V NC BS BS BD H BD L NC OUT0 V NC NC OUT1 Load short circuit protection circuit Load short circuit protection circuit DC DC converter not isolated Internal Circuits NC NC BS...

Page 442: ...a solenoid valve either use a built in diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for CRT1B OD02S and CRT1B OD02S 1 Solenoid valve etc Solenoid va...

Page 443: ...B ID02SP CRT1B ID02SP 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G term...

Page 444: ...it set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicator...

Page 445: ...nal Circuits BS BS BD H BD L V NC G IN0 V NC G IN1 Load short circuit protection circuit DC DC converter not isolated Internal Circuits BS BS BD H BD L V NC G IN0 V NC G IN1 DC DC converter not isolat...

Page 446: ...colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02SP and CRT1B ID02SP 1 V NC G IN 0 V NC G IN 1 1 2 3 4 Brown Red Black White Blue Black 3 wire sensor wit...

Page 447: ...l load current number of actuators used Item Specification Model CRT1B OD02SP CRT1B OD02SP 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 2 A output Load power supply volt...

Page 448: ...set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Power short circuit indicator SHT0 Communications in...

Page 449: ...OD02SP NPN Internal Circuits V NC BS BS BD H BD L NC OUT0 V NC NC OUT1 Load short circuit protection circuit DC DC converter not isolated Load short circuit protection circuit Internal Circuits G NC B...

Page 450: ...id valve either use a built in diode for absorbing the counterelectromotive force or install an external diode Dimensions Same for CRT1B OD02SP and CRT1B OD02SP 1 Solenoid valve etc Solenoid valve etc...

Page 451: ...T1B ID04SP CRT1B ID04SP 1 I O capacity 4 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input terminal and the G te...

Page 452: ...set on the middle rotary switch and the 1s digit set on the bottom rotary switch The setting on the rotary switches is read when power is turned ON Communications indicators MS and NS I O indicators...

Page 453: ...Section 9 3 Internal Circuits CRT1B ID04SP NPN BS BS BD H BD L V0 NC G0 IN0 V0 NC G0 IN1 V1 NC G1 IN2 V1 NC G1 IN3 Load short circuit protec tion circuit Internal Circuits DC DC converter not isolate...

Page 454: ...D L V0 NC G0 IN0 V0 NC G0 IN1 V1 NC G1 IN2 V1 NC G1 IN3 Internal Circuits DC DC converter not isolated Load short circuit pro tection circuit Load short circuit pro tection circuit V0 NC IN 0 V0 NC G0...

Page 455: ...theses are the wire colors prior to the revisions Dimensions Same for CRT1B ID04SP and CRT1B ID04SP 1 V0 NC G0 IN 0 V0 NC G0 IN 1 V1 NC G1 IN 2 V1 NC G1 IN 3 1 2 3 4 Brown Red Black White Blue Black 3...

Page 456: ...n Model CRT1B MD04SLP CRT1B MD04SLP 1 I O capacity 2 inputs Internal I O common line NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input term...

Page 457: ...ly voltage 0 V max Communications power supply voltage 1 2 V min Residual voltage 1 2 V max 0 2 A DC between each output terminal and BS 1 2 V max 0 2 A DC between each output terminal and BS Leakage...

Page 458: ...NPN Name LED status I O status Meaning 0 to 3 Lit yellow Input output ON The input output is ON Not lit Input output OFF The input output is OFF SHT0 Lit red Power short circuit detected The power sup...

Page 459: ...G IN0 V NC G IN1 NC NC G OUT0 NC NC G OUT1 DC DC converter not isolated Load short circuit protection circuit Load short circuit protection circuit Load short circuit protection circuit V NC IN 0 V NC...

Page 460: ...toelectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B MD04SLP and CRT1B MD04SLP 1 V NC G IN 0 V NC G IN 1 1 2 3 4 NC NC OUT 0...

Page 461: ...ble I Multidrop Connector Plug at the location where a Bit Slave Unit with Compact Connectors is to be connected secure the extended cable with the terminal block so as not to cause a short circuit an...

Page 462: ...ecification Model CRT1B ID02JS CRT1B ID02JS 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input t...

Page 463: ...ll not be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation betwee...

Page 464: ...ID02JS NPN CRT1B ID02JS 1 PNP BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 DC DC Conve...

Page 465: ...lors in parentheses are the wire colors prior to the revisions Dimensions Same for CRT1B ID02JS and CRT1B ID02JS 1 G S V G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown w...

Page 466: ...el CRT1B OD02JS CRT1B OD02JS 1 I O capacity 2 outputs Internal I O common NPN PNP Rated output current 0 1 A output Load power supply voltage Communications power supply voltage 0 V max Communications...

Page 467: ...t be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between dec...

Page 468: ...02JS NPN CRT1B OD02JS 1 PNP BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 DC DC Con...

Page 469: ...nals are shown below CRT1B OD02JS NPN CRT1B OD02JS 1 PNP Dimensions Same for CRT1B OD02JS and CRT1B OD02JS 1 G S V Solenoid valve etc G S V Signal Signal Emitter OFF input Photoelectric sensor emitter...

Page 470: ...pecification Model CRT1B ID04JS CRT1B ID04JS 1 I O capacity 4 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between each input...

Page 471: ...e performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decima...

Page 472: ...ors Section 9 5 Internal circuits CRT1B ID04JS NPN BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 V2 IN2 G2 V3 IN3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Cont...

Page 473: ...Connectors Section 9 5 CRT1B ID04JS 1 PNP BS BDH BDL BS V0 IN0 G0 V1 IN1 G1 V2 IN2 G2 V3 IN3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continuous s...

Page 474: ...lectric and proximity sensors The colors in parentheses are the wire colors prior to the revisions G S V G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sens...

Page 475: ...451 Bit Slave Units with Compact Connectors Section 9 5 Dimensions Same for CRT1B ID04JS and CRT1B ID04JS 1 20 6 65 24 62 9 mm...

Page 476: ...del CRT1B OD04JS CRT1B OD04JS 1 I O capacity 4 outputs Internal I O common NPN PNP Rated output current 0 1 A output Load power supply voltage Communications power supply voltage 0 V max Communication...

Page 477: ...formed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decimal nod...

Page 478: ...with Compact Connectors Section 9 5 Internal circuits CRT1B OD04JS NPN BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 V2 OUT2 G2 V3 OUT3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit...

Page 479: ...nnectors Pin arrangements and signals are shown below CRT1B OD04JS NPN BS BDH BDL BS V0 OUT0 G0 V1 OUT1 G1 V2 OUT2 G2 V3 OUT3 G3 DC DC Converter not isolated Internal circuits Continuous short circuit...

Page 480: ...Compact Connectors Section 9 5 CRT1B OD04JS 1 PNP Dimensions Same for CRT1B OD04JS and CRT1B OD04JS 1 G S V G S V V G V G Solenoid valve etc Signal Signal Emitter OFF input Photoelectric sensor emitte...

Page 481: ...ed Item Specification Model CRT1B MD02JS CRT1B MD02JS 1 I O capacity 1 input Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between eac...

Page 482: ...V max DC 0 1 A between each output terminal and G terminal 1 2 V max DC 0 1 A between each output terminal and V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of...

Page 483: ...ions will not be performed if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation...

Page 484: ...1B MD02JS NPN CRT1B MD02JS 1 PNP BS BDH BDL BS V IN0 G V OUT0 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit BS BDH BDL BS V IN0 G V OUT0 G DC DC Converte...

Page 485: ...G S V V G V G Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch G S V G S V V...

Page 486: ...462 Bit Slave Units with Compact Connectors Section 9 5 Dimensions CRT1B MD02JS and CRT1B MD02JS 1 15 21 65 24 48 9 mm...

Page 487: ...d Item Specification Model CRT1B MD04JS CRT1B MD04JS 1 I O capacity 2 inputs Internal I O common NPN PNP ON voltage 10 5 VDC min between each input terminal and the V terminal 10 5 VDC min between eac...

Page 488: ...V max DC 0 1 A between each output terminal and G terminal 1 2 V max DC 0 1 A between each output terminal and V terminal Leakage current 0 1 mA max ON delay 0 5 ms max OFF delay 1 5 ms max Number of...

Page 489: ...if the node address is set out of range The factory setting is 0000000 Refer to Appendix F Node Address Settings for Bit Slave Units with Compact Connectors for the relation between decimal node addre...

Page 490: ...ectors Section 9 5 Internal circuits CRT1B MD04JS NPN BS BDH BDL BS V IN0 G V IN1 G V OUT0 G V OUT1 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continu...

Page 491: ...act Connectors Section 9 5 CRT1B MD04JS 1 PNP BS BDH BDL BS V IN0 G V IN1 G V OUT0 G V OUT1 G DC DC Converter not isolated Internal circuits Continuous short circuit protection circuit Continuous shor...

Page 492: ...G S V Signal Signal Blue black Black white Brown red Blue black Brown white 3 wire sensor with NPN output photoelectric sensor or proximity sensor 2 wire sensor e g limit switch V G V G G S V G S V S...

Page 493: ...469 Bit Slave Units with Compact Connectors Section 9 5 Dimensions Same for CRT1B MD04JS and CRT1B MD04JS 1 20 6 65 24 62 9 mm...

Page 494: ...470 Bit Slave Units with Compact Connectors Section 9 5...

Page 495: ...471 SECTION 10 Repeater Units This section describes the Repeater Unit 10 1 Status Areas 472 10 2 Repeater Unit 474 10 2 1 Repeater Unit 474...

Page 496: ...These bits indicate minor errors in the Unit Master Unit The Repeater Unit has two status areas the Warning Status Area and the Alarm Status Area Transmitted to Master Unit Repeater Unit The status b...

Page 497: ...indicate serious errors in the Unit Bit Content Description 0 Reserved 1 EEPROM Data Error Flag OFF Normal ON Error Turns ON when there is an error in the EEPROM data 2 Reserved 3 Reserved 4 Reserved...

Page 498: ...r supply connector Note Communications power for the Repeater Unit is supplied from the BS and BS terminals on the upstream port communica tions connector PORT1 Communications power supply connector a...

Page 499: ...cator status Status Meaning MS Lit green Normal status The Unit is operating normally Flashing green Lit red Fatal error A hardware error has occurred in the Unit The watchdog timer has timed out Flas...

Page 500: ...mmunications Power Supply Connector This connector supplies communications power to Slave Units and Repeater Units connected to the downstream communications connector port 2 Note Communications power...

Page 501: ...477 Repeater Unit Section 10 2 Dimensions 42 3 50 3 1 27 5 95 mm...

Page 502: ...478 Repeater Unit Section 10 2...

Page 503: ...Monitor Digital I O Slave Units Only 495 11 3 2 Input Filter Input Units Only 496 11 3 3 Error Prevention for Surge Current at Startup Input Units Only 497 11 3 4 Contact Operation Monitor 498 11 3 5...

Page 504: ...ld 546 11 6 5 Top Valley Counter 549 11 6 6 Rate of Change Calculation 550 11 6 7 Comparator 552 11 6 8 Temperature Range Count 556 11 6 9 Data Comparison between Channels 558 11 6 10 Input Error Dete...

Page 505: ...it can be set or edited sim ply by double clicking on the Slave Unit in the Offline Window Refer to 11 2 Functions Common to All Slave Units for details on how to set and edit func tions for each Slav...

Page 506: ...ay 2 Right click the network name in the Workspace Window and select Con nect from the pop up menu Toggles to on line status While connected online information on the CompoNet Slave Units is dis playe...

Page 507: ...Operation Time Tab Pages More detailed maintenance information can be found on the OUT IN and Operation Time Tab Pages Online Connection Information Window Save Maintenance Counter Button The maintena...

Page 508: ...484 CX Integrator Section 11 1...

Page 509: ...485 CX Integrator Section 11 1...

Page 510: ...h the Master Unit after the power is turned ON The baud rate setting is stored in memory until the power is turned ON again or until the Master Unit baud rate setting is changed 11 2 2 Hold Clear Outp...

Page 511: ...n a status area in the Slave Unit will turn ON to notify the Master Unit The notification details can be read using the CX Integrator or using explicit messages Note 1 The minimum communications power...

Page 512: ...time that power is ON i e the Total ON Time to the Slave Unit s internal circuits can be stored in the Slave Unit memory This data can be read using the CX Integrator or using explicit messages The mo...

Page 513: ...e Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Click the General Tab Ente...

Page 514: ...ower supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and sele...

Page 515: ...h errors need to be identified The CX Integrator or explicit messages can be used to read write the name i e comment Settings Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet S...

Page 516: ...ick the Reset Button to reset the Unit 6 Click the OK Button and exit the window 11 2 7 Communications Error History Monitor Description Enables storing the error communication failure details the com...

Page 517: ...right click the icon for the desired CompoNet Slave Unit in the Network Configuration Window and select Monitor from the pop up menu 3 Click the Error History Tab in the Monitor Window The communicati...

Page 518: ...ator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively rig...

Page 519: ...fication details can be read using the CX Integrator or using explicit messages Note A detection voltage cannot be set for the I O power supply Checking Using the CX Integrator 1 2 3 1 Turn ON the pow...

Page 520: ...ding pulses shorter than the communications cycle time set the OFF response time to a value longer than the communications cycle time The input may remain ON if the input pulse interval is too short S...

Page 521: ...he I O power is turned ON i e until the Slave Unit stabilizes It helps avoid input errors caused by inrush current from con nected devices when the I O power supply is turned ON This function is enabl...

Page 522: ...mory so once the number of contact operations reaches the monitor value a flag in a status area in the Slave Unit turns ON to notify the Master Unit The notification details can be read using the CX I...

Page 523: ...value and then click the OK Button 5 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 6 Click the OK Button a...

Page 524: ...for inputs of less than 1 s Measuring an ON Time of 0 5 s As shown in Figure A the actual ON time is 1 5 s 3 0 5 s but the total ON time is measured only as 1 s because the input is ON only once when...

Page 525: ...lect Parameters Edit from the pop up menu 3 Click the IN Tab 4 Double click the I O Comment column for the terminal to be set The Edit Terminal Window will be displayed Select Time for the Detection M...

Page 526: ...ication details can be read using the CX Integrator or using explicit mes sages The operation time is stored after the time lag from when the output turns ON until when the input turns ON is measured...

Page 527: ...uble click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 C...

Page 528: ...recover automati cally and power will be output to the connector where the short circuit was detected Note Use a power supply device with a rating of 100 W or higher as the communi cations power supp...

Page 529: ...mation on load short circuit detection refer to the rated output current and internal circuits in the specifications for the applicable Unit An indicator on the Slave Unit can be used to see if a loa...

Page 530: ...in Monitoring Status with the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Go online right click the icon of the applicable CompoNet Slave Unit in the Network Configurat...

Page 531: ...is increased Setting Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open th...

Page 532: ...inputs and uses the resulting value as conversion data When the input value fluctuates frequently as shown in the following diagram averaging can be used to produce a stable input value Setting Using...

Page 533: ...user industry unit values Scaling also eliminates the need for ladder programming in the Master Unit to perform math operations The following two methods of input scaling can be used Default Scaling...

Page 534: ...put between 28 000 to 28 000 but make sure that underflow or overflow does not occur The High Limit is 7FFE hex and the Low Limit is 8000 hex Note The offset value can be set even when using default s...

Page 535: ...ration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the input where scaling is to be performed a...

Page 536: ...e Scaling Point 100 Field 6 For offset compensation set the offset value in the Scaling Offset Field Either Default Scaling or User Scaling can be set in the Scaling Type Field 7 Return to the General...

Page 537: ...erefore even when the Hold Flag is ON the first analog data transmitted to the Master Unit after the CPU Unit power is turned ON may be the data from when the Hold Flag was OFF To collect peak bottom...

Page 538: ...the default connection path click the General Tab and select Holding Value from the pull down menu in the De fault Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the dat...

Page 539: ...he Hold Flag is ON the first analog data transmitted to the Master Unit after the CPU Unit power is turned ON may be the data from when the Hold Flag was OFF To collect top valley hold data using the...

Page 540: ...the default connection path click the General Tab and select Holding Value from the pull down menu in the Default Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the data...

Page 541: ...ing for Setting Data Setting Hysteresis Using the CX Integrator 1 2 3 1 Input the value for hysteresis in the Hysteresis Field in the Top Valley Tab under the Function Choice heading 2 Return to the G...

Page 542: ...ation Description The rate of change can be obtained for each sampling cycle set for the analog input data This function calculates the difference between each set sampling cycle and value obtained in...

Page 543: ...et Slave Unit 2 Double click the icon of the Slave Unit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from t...

Page 544: ...oint High H the Warning Trip Point Low L and the Alarm Trip Point Low LL When the analog data value exceeds the set value the Comparator Result Flag in the area for Analog Status Flags turns ON If an...

Page 545: ...OFF delay can be set so that the Master Unit can receive notification of the Flag s status Setting Using the CX Integrator 1 2 3 1 Turn ON the power supply to the CompoNet Slave Unit 2 Double click t...

Page 546: ...input Functions Section 11 4 4 Click the Comparator Tab and set the four trip points The example here shows the setting for Alarm Trip Point High HH 5 To set the hysteresis value input the desired val...

Page 547: ...ction is also used as the hys teresis value for the top valley hold function 6 To set the OFF delay function input the desired value in the Comparator Off Delay Field 7 Return to the General Tab Page...

Page 548: ...4 to 20 mA input range a disconnected line is detected when the input current is below 3 04 mA 11 4 9 User Adjustment Description Depending on factors such as the characteristics and connection method...

Page 549: ...nsmitted from the connected device to the Unit s input terminal that is equivalent to the 100 value 5 Click the Fix Upper Adjusting Value Button in the Adjustment Window and input the adjusted value 6...

Page 550: ...minutes The count value is the analog input value in the industry unit obtained after scal ing For example 100 0 count hours indicates a value equivalent to an analog input value of 100 counts contin...

Page 551: ...Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the input where the cumulated counte...

Page 552: ...click the Cumulated Count Tab and input the de sired value in the Threshold Cumulated Counter Field 6 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then...

Page 553: ...te from the Last Maintenance Date Field To enter the current date select Today from the bottom of the pull down menu 4 Click the Transfer PC to Unit Button to download the data and then click the Rese...

Page 554: ...pecified scaling or industry specific units for output signal ranges The function eliminates the need for ladder programming in the Mas ter Unit to perform math operations The following two methods of...

Page 555: ...and 28 000 but if underflow or overflow occurs in the scaled line the 100 or 0 output will not be possible The High Limit is 7FFE hex and the Low Limit is 8000 hex Note The offset value can be set ev...

Page 556: ...nit to set in the Network Configuration Window to open the Configuration Window Alternatively right click the icon and select Parameters Edit from the pop up menu 3 Select the Tab Page for the output...

Page 557: ...caling is selected set the 0 value in the Scaling Point 0 Field and set the 100 value in the Scaling Point 100 Field 6 For offset compensation set the offset value in the Scaling Offset Field Also sel...

Page 558: ...be adjusted to compensate for error in the final output The following diagram shows when compensation is applied to the conversion line at the two points for 0 and 100 The ranges supported for adjust...

Page 559: ...Adjust ment Button At this time set the output range Adjusting the Low Limit 4 Output the value from the Master Unit that is equivalent to 0 Always per form adjustment with the 0 value 5 Adjust the an...

Page 560: ...peat adjustments until the correct 100 value is output from the output device After com pensation is completed click the Fix Upper Adjusting Value Button To return to the default settings click the De...

Page 561: ...of 0 1 hours or minutes Monitor values can be set in the Slave Unit When the cumulated count value exceeds the set monitor value the Cumulated Counter Flag in the area for Generic Status Flags turns O...

Page 562: ...To set the counter unit click the Cumulated Count Tab and select Hour or Minute from the pull down menu in the Cumulated Time Field 5 To set the monitor value click the Cumulated Count Tab and input t...

Page 563: ...r a Unit error has occurred the current output will be 0 mA and the voltage output will be 0 V regardless of the setting Low limit Outputs the values in the following table according to the output ran...

Page 564: ...sired item from the pull down menu in the Fault State Field 4 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit...

Page 565: ...moving average processing is to be per formed and select the Moving Average Check Box in the Function Choice Area 4 Return to the General Tab Page click the Transfer PC to Unit Button to download the...

Page 566: ...t occur The High Limit is 7FFE hex and the Low Limit is 8000 hex The High Limit is 7FFFFFFE Hex and the Low Limit is 80000000 Hex for 1 100 Display Mode Note The offset value can be set even when usin...

Page 567: ...ure Input Unit Functions Section 11 6 4 Set 0 value in the Scaling Point 0 Field and set the 100 value in the Scaling Point 100 Field 5 To offset the scaled values set the offset value in the Scaling...

Page 568: ...OFF The comparator function can be used to com pare the peak or bottom values allocated as temperature data 1 Refer to details on the comparator function Example of Bottom Hold Note A delay in network...

Page 569: ...nput Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Configuration Window will be displayed 3 Click the tab for the input where peak bottom hol...

Page 570: ...ram until notification of the flag s status is actually sent to the Slave Therefore even when the Hold Flag is ON the first temperature data transmitted to the Master Unit when the CPU Unit power is t...

Page 571: ...fault Connection Path Out Field 5 Click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 6 Click the OK Button and exit the window Hysteresis Setti...

Page 572: ...C to Unit Button to download the data and then click the Reset Button to reset the Unit 3 Click the OK Button and exit the window Note The hysteresis set for the top valley hold function is also used...

Page 573: ...en mainte nance is required for the Unit or sensor The status can be read in the Monitor Window or via an explicit message to know when the monitor value has been exceeded Valley Counter Operation Set...

Page 574: ...tor value for the top valley counter 6 Return to the General Tab Page click the Transfer PC to Unit Button to download the data and then click the Reset Button to reset the Unit 7 Click the OK Button...

Page 575: ...ving average processing which will set a longer sampling cycle Setting Using CX Integrator 1 2 3 1 Turn ON the power supply to the Temperature Input Unit 2 Double click the icon of the Temperature Inp...

Page 576: ...h Limit High Limit Low Low Limit and Low Limit are set in the Unit a status flag will be turned ON when a value exceeds the set range The four set values are High High Limit HH High Limit H Low Low Li...

Page 577: ...is to stabilize the flag operation The setting range is 0 to 16 383 Note When setting the hysteresis value allow for the decimal point position or the 1 100 Display Mode for each input Always correct...

Page 578: ...o the Temperature Input Unit 2 Double click the icon of the Temperature Input Unit to be set in the Network Configuration Window or right click the icon and select Parameter Edit The Configuration Win...

Page 579: ...al point position Example Alarm value setting for 250 R thermocouple normal display setting 00250 decimal T thermocouple normal display setting 02500 decimal Setting for any input with 1 100 display 2...

Page 580: ...Tab Page The temperature range boundaries are defined by the High High Limit HH High Limit H Low Low Limit LL or Low Limit L If the time within the set tem perature range exceeds the monitor value it...

Page 581: ...guration Window will be displayed 3 Click the tab for the input where time is to be measured and select the Comparator Check Box in the Function Choice Area 4 Click the Comparator Tab and select the d...

Page 582: ...t to detect an excessive temperature difference for preven tative maintenance in devices in which the temperature difference may cause or indicate a problem The comparison result can be checked in the...

Page 583: ...arison Between Channels Tab 4 Double click the Calculation Data1 or Calculation Data2 cell to open the Edit Calculation Data Window 5 Select the two temperature inputs to be compared in the Calculatio...

Page 584: ...led the temperature data is set to 7FFF hex 7FFF FFFFF when 1 100 Display Mode is being used 1 2 3 1 Turn ON the power supply to the Temperature Input Unit 2 Double click the icon of the Temperature I...

Page 585: ...for each of the connected devices This enables the user to easily determine the next maintenance date The date can be set using the CX Integrator Setting Using CX Integrator Setting the last maintenan...

Page 586: ...e the amount of heat endured by a sensor or device The cumulated value can be calculated in hours C hours or F hours or minutes C minutes or F minutes For example when the units are set to hours a cum...

Page 587: ...w or right click the icon and select Parameter Edit The Configuration Window will be displayed 3 Click the tab for the input where the cumulated counter is to be set and select the Cumulated Count Che...

Page 588: ...d value in the Threshold Cumulated Counter Field Note When the Threshold Cumulated Counter is set to 0 the cumulated value will not be monitored 6 Return to the General Tab Page click the Transfer PC...

Page 589: ...hen absolutely necessary OMRON is not re sponsible for the results of user adjustments If a mistake is made in the adjustments the adjustment data can be cleared to return to the factory default setti...

Page 590: ...junction compensator to disable it First adjustment Turn ON the power to the associated system devices Wait at least 30 minutes for the CRT1 TS04T s internal temperature to stabilize This stabilizatio...

Page 591: ...ensors Use a cold junction compensator compatible with the sensor being adjusted Note When using an R S E B or W type thermocouple a K type can be substi tuted Set the ZERO CON to 0 C 32 F CX Integrat...

Page 592: ...type to K 200 to 1 300 C 3 Connect the CX Integrator to the CompoNet network and go online 4 Upload settings to the CX Integrator 5 Turn ON the power supplies of all Units including the Temperature I...

Page 593: ...alue 10 Adjust the upper limit value Input the upper limit voltage from the reference voltage current generator to the input terminals of the input to be adjusted Refer to the following table for the...

Page 594: ...e Data 2 If the correct reference voltage was not input the adjustment values may not be accepted Adjusting the Bias Compensation Value 1 2 3 1 Disconnect the wiring for adjusting the upper and lower...

Page 595: ...verify that the adjustments are correct Test the indication accuracy at three points the lower limit value an intermediate value and the upper limit val ue Connect the external devices as shown in th...

Page 596: ...bilization time Input Unit s power supply ON Wiring for input 0 adjustment Input 0 upper lower limit adjustment Input 0 bias compensation Change wiring for input 1 adjustment Input 1 upper lower limit...

Page 597: ...hen making adjustments Six dial Resistance Box and Precision Digital Multimeter These devices are used to make adjustments at the upper limit and lower limit Prepare devices that can provide accurate...

Page 598: ...re Input Unit that is being adjusted 2 If the correct resistance cannot be obtained properly wire the digital mul timeter to the six dial resistance box and measure the resistance 3 Connect the CX Int...

Page 599: ...ing Value Button in the Adjustment Window to write the adjustment value 10 Adjust the upper limit value Input the resistance from the six dial resis tance box Refer to the following table for the appr...

Page 600: ...etails on the Monitor Win dow refer to 7 4 Monitoring Temperature Data Resetting Adjustments If it is necessary to reset the upper limit adjustment value and lower limit adjustment value to the factor...

Page 601: ...Unit Functions Section 11 6 Note If the power supply is not turned OFF after making an adjustment it is not necessary to wait 30 minutes before continuing testing CRT2 TS04P Six dial resistance box In...

Page 602: ...578 Temperature Input Unit Functions Section 11 6...

Page 603: ...formation on maintenance that should be performed to ensure optimum application of the CompoNet Slave Units 12 1 Indicator Meanings and Troubleshooting 580 12 2 Troubleshooting 581 12 2 1 Troubleshoot...

Page 604: ...Integrator to restore the default data Lit green Configuration error The same node address has been used more than once Repeater Unit configu ration error Check that the node address is set within th...

Page 605: ...g used by more than one Slave Unit change the node address Refer to the next item The NS indicator lights green momentarily and then changes to red Replace the Slave Unit if its NS indicator is always...

Page 606: ...he Network Power Voltage Drop Flag does not turn ON even if the network power sup ply voltage drops The monitor value for the net work power supply voltage is set too low Note The default setting is 1...

Page 607: ...input filter is set there is a delay with the ON or OFF time The operation time ON or OFF edge selection may not be on the intended setting The selected operation time combination is not supported If...

Page 608: ...even though the error has been fixed The status will not turn OFF until the power for the node where the error was detected is reset Cycle the communications power after fixing the error Slaves with...

Page 609: ...then set the monitor value again The input s decimal point position for a Temperature Input Unit was in the wrong place when the monitor value was set Check the decimal point posi tion and enter the...

Page 610: ...e sensor s decimal point position was read incorrectly The following conditions apply to the CRT1 TS04T only In 1 100 Display Mode the display value is multiplied by x100 regardless of the input type...

Page 611: ...is the one word in the normal display area Either change the default con nection path to the 1 100 dis play area or select a connection path in the Master Unit for the 1 100 display area The temperatu...

Page 612: ...ections should occur every 6 months to a year Periodic inspec tions should occur more frequently however for Units that are used in envi ronments subject to high temperatures high humidity or a lot of...

Page 613: ...unctioning devices for repair attach a detailed description of the malfunction to the device and send the device to the OMRON representa tive listed at the end of this manual or to your OMRON represen...

Page 614: ...590 Device Maintenance Section 12 3...

Page 615: ...xplicit message and sends it to a CompoNet Slave Unit The response from the Slave Unit is then converted by the Master Unit from a CompoNet explicit message to a FINS response and sent back to the CPU...

Page 616: ...cified for this parameter In a response the recep tion data defined for the service code is returned Number of Bytes Received Response The number of bytes received in the data from the destination nod...

Page 617: ...ata is smaller than the specified size 0CFF Object state conflict The specified command cannot be executed due to an internal error 20FF Invalid parameter The specified operation command data is not s...

Page 618: ...s 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for Unit Conduction Time unit 0 1 hr 10 hex 95 hex 01 hex 73 hex 4 bytes 0000000 0 to FFFFFFF F hex 0 to 4294967 295 Unit Main ten...

Page 619: ...e ID 0E hex 08 hex 01 to 20 hex 68 hex 4 bytes 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for the total ON time unit s or number of contact operations unit opera tions of the...

Page 620: ...0 hex 68 hex 4 bytes 00000000 to FFFFFFFF hex 0 to 4294967295 Write Writes the set value for the total ON time unit s or number of contact operations unit opera tion for the output No 1 to 32 specifie...

Page 621: ...e Instance ID No 1 to 8 10 hex 97 hex 01 to 08 hex 67 hex 2 bytes See note Operation Time Moni tor Peak Value Read Read Reads the peak value for the time unit ms from the start point trigger until the...

Page 622: ...01 hex Hold Setting for Output Sta tus Hold or Clear after Communi cations Error Write Sets whether hold or clear is set as the output status after a communi cations error for an out put No 1 to 32 s...

Page 623: ...ex 1 byte 00 hex Dis abled Not used 01 hex Enabled Used Write Writes the unconnected line detection setting for the input No 1 to 32 specified by the Instance ID 10 hex 08 hex 01 to 20 hex 6B hex 1 by...

Page 624: ...Command data Service data Attribute ID Data Load Short circuit Detection Status Read Reads the load short cir cuit status for the output No 1 to 32 specified by the Instance ID 0E hex 09 hex 01 to 20...

Page 625: ...the output No 1 to 32 specified by the Instance ID 10 hex 09 hex 01 to 20 hex 6B hex 1 byte 00 hex Disabled Not used 01 hex Enabled Used Load Uncon nected Line Detection Status Read Reads the load un...

Page 626: ...hex fixed 02 Response area 1 03 Response area 2 See note 1 Monitor Status for Total ON Time or Contact Operation Counter for All Slave Units Read at Once Read Reads the monitor sta tus for total ON ti...

Page 627: ...the number of AD conversion points Write 10 hex Read 0E hex 0A hex 00 hex 64 hex 2 bytes 1 byte Input Range Set ting Write Read Sets the input range 10 to 10 V 0 0 to 5 V 1 0 to 10 V 2 4 to 20 mA 3 1...

Page 628: ...hex 2 bytes 28000 to 28000 2 bytes 28000 to 28000 Maximum Value Read Read Reset Reads the maximum value after power is turned ON Read 0E hex Reset 35 hex 0A hex 01 to 04 hex 73 hex 2 bytes Minimum Val...

Page 629: ...hex 0A hex 01 to 04 hex 8E hex 2 bytes Sampling Cycle Set ting Write Read Sets the sampling cycle for obtaining the rate of change based on the previous value Write 10 hex Read 0E hex 0A hex 01 to 04...

Page 630: ...Write Read Default scaling 0 User scaling 1 Write 10 hex Read 0E hex 0B hex 01 to 02 hex 6F hex 1 byte Scaling Point 1 Set ting Write Read Sets a conversion value as the 0 value for user scaling Write...

Page 631: ...1 hex 00 hex 64 hex 1 byte Tempera ture 1 Read for Normal Display Read Reads the value of tem perature data 1 0E hex 31 hex 01 to 04 hex A5 hex 2 bytes Tempera ture 1 Read for 1 100 Display Read Reads...

Page 632: ...le 7 Write 10 hex Read 0E hex 31 hex 01 to 04 hex 6E hex 2 bytes 2 bytes Scaling Point 1 Set ting Write Read Sets an temperature value as the 0 value for user scaling Write 10 hex Read 0E hex 31 hex 0...

Page 633: ...000 4 bytes 415000 to 415000 LL Value Setting Write Read Sets the LL value Write 10 hex Read 0E hex 31 hex 01 to 04 hex 12 hex 4 bytes 415000 to 415000 4 bytes 415000 to 415000 H Value Setting Write R...

Page 634: ...0000 0 0000 0 1 0000 00 2 0E hex 31 hex 01 to 04 hex A3 hex 1 byte Top Valley Count Read Read Reset Reads the number of tops or valleys that have been counted Read 0E hex Reset 35 hex 31 hex 01 to 04...

Page 635: ...ser set tempera ture range Write 10 hex Read 0E hex 31 hex 01 to 04 hex B0 hex 4 bytes 4 bytes Input Tem perature Variation Detection Read Read Reads the result of input temperature varia tion detecti...

Page 636: ...mand data is read by using the EXPLICIT MESSAGE SEND command 28 02 The command data is written in words starting from D01000 in the CPU Unit and the response data is stored in words starting from D020...

Page 637: ...0E Service code 0E hex D01003 00 95 Class ID 0095 hex D01004 00 01 Instance ID 0001 hex D01005 71 00 Attribute ID 71 hex The rightmost 00 hex is not read because the number of bytes of command data i...

Page 638: ...a is received the lower byte is stored first S n 34 12 15 08 07 00 S n 12 34 15 08 07 00 S n 56 12 78 34 15 08 07 00 S n 78 34 56 12 15 08 07 00 Example for 1234 Hex Starting from the Upper Byte of I...

Page 639: ...l Device type Product code Product name Basic Unit Expansion Unit CRT1 ID08 07 hex 1557 CRT1 ID08 CRT1 ID08 1 07 hex 1558 CRT1 ID08 1 CRT1 OD08 07 hex 1559 CRT1 OD08 CRT1 OD08 1 07 hex 1560 CRT1 OD08...

Page 640: ...CRT1 MD16 1 CRT1 ROS08 07 hex 1593 CRT1 ROS08 CRT1 ROF08 07 hex 1594 CRT1 ROF08 CRT1 ROS16 None 07 hex 1511 CRT1 ROS16 XWT ID08 07 hex 1512 XWT ID16 07 hex 1513 XWT OD08 07 hex 1514 XWT OD16 07 hex 1...

Page 641: ...16S 1 CRT1 ID16SH 07 hex 1599 CRT1 ID16SH CRT1 ID16SH 1 07 hex 1600 CRT1 ID16SH 1 CRT1 OD16SH 07 hex 1601 CRT1 OD16SH CRT1 OD16SH 1 07 hex 1602 CRT1 OD16SH 1 CRT1 MD16SH 07 hex 1579 CRT1 MD16SH CRT1 M...

Page 642: ...SP 07 hex 1372 CRT1B ID04SP CRT1B ID04SP 1 07 hex 1373 CRT1B ID04SP 1 CRT1B MD04SLP 07 hex 1374 CRT1B MD04SLP CRT1B MD04SLP 1 07 hex 1375 CRT1B MD04SLP 1 CRT1B ID02JS 07 hex 1727 CRT1B ID02JS CRT1B ID...

Page 643: ...ported Service Not supported Object instance Attribute Not supported Service Not supported Vendor specifica tion addition None Object class Attribute Not supported Service Not supported Object instanc...

Page 644: ...H 1 CRT1 VID08S 1 CRT1 MD16S 1 CRT1 MD16SH 1 CRT1 ID08SL 1 CRT1 MD16SL 1 Assembly instance 5 16 inputs Input 7 6 5 4 3 2 1 0 CRT1 ID16 1 CRT1 ID16 1 XWT OD08 1 CRT1 ID16 1 XWT OD16 1 CRT1 OD16 1 XWT I...

Page 645: ...VOD08S 1 CRT1 MD16S 1 CRT1 MD16SH 1 CRT1 OD08SL 1 CRT1 MD16SL 1 Assembly instance 35 16 outputs Output 7 6 5 4 3 2 1 0 CRT1 ID16 1 XWT OD16 1 CRT1 OD16 1 CRT1 OD16 1 XWT ID08 1 CRT1 OD16 1 XWT ID16 1...

Page 646: ..._ST3 T_ST2 T_ST1 T_ST0 Instance 134 Analog Status Flags 0 BW0 T_ST0 V_ST0 HH0 H0 PS0 L0 LL0 CRT1 AD04 CRT1 VAD04S CRT1 VAD04ML 1 BW1 T_ST1 V_ST1 HH1 H1 PS1 L1 LL1 2 BW2 T_ST2 V_ST2 HH2 H2 PS2 L2 LL2 3...

Page 647: ...12 Ch3 Temperature Data 1 13 14 15 Instance 122 Top Valley Detec tion Timing Flags 0 0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 CRT1 TS04T CRT1 TS04P 1 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0 Instance 134 Temperature D...

Page 648: ...a 1 CRT1 TS04T CRT1 TS04P 1 2 3 4 Ch1 Temperature Data 1 5 6 7 8 Ch2 Temperature Data 1 9 10 11 12 Ch3 Temperature Data 1 13 14 15 16 0 0 0 0 V_ST3 V_ST2 V_ST1 V_ST0 17 0 0 0 0 T_ST3 T_ST2 T_ST1 T_ST0...

Page 649: ...es No 82H Input and Mixed I O Slave Units 80H Output Slave Units and Repeater Units 4 Produced con nection ID Yes No 5 Consumed con nection ID Yes No 6 Initial comm characteristics Yes No 01 hexadecim...

Page 650: ...3 0000 CRT1B ID04JS 1 Input Data 0001 0006 20_04_24_ 03_30_03 0000 CRT1B OD02JS 1 Output Data 0000 0001 0006 20_04_24_ 20_30_03 CRT1B OD04JS 1 Output Data 0000 0001 0006 20_04_24_ 21_30_03 CRT1B MD02J...

Page 651: ...Data 0001 0006 20_04_24_ 04_30_03 0000 XWT ID16 1 Output Data 0000 0002 0006 20_04_24_ 23_30_03 Input Data 0002 0006 20_04_24_ 05_30_03 0000 XWT OD08 1 Output Data 0000 0003 0006 20_04_24_ 25_30_03 X...

Page 652: ...20_04_24_ 05_30_03 0000 CRT1 OD16S 1 Output Data 0000 0002 0006 20_04_24_ 23_30_03 CRT1 MD16S 1 Input Data 0001 0006 20_04_24_ 04_30_03 0000 Output Data 0000 0001 0006 20_04_24_ 22_30_03 CRT1 ID16SH 1...

Page 653: ...30_03 CRT1 MD16SL 1 Input Data 0001 0006 20_04_24_ 04_30_03 0000 Output Data 0000 0001 0006 20_04_24_ 22_30_03 CRT1 AD04 CRT1 VAD04S CRT1 VAD04ML Analog Data 1 0008 0006 20_04_24_ 68_30_03 0000 0000 G...

Page 654: ...0002 0006 20_04_24_ 7A_30_03 0000 0000 Tempera ture Status 0004 0006 20_04_24_ 86_30_03 0000 0000 Tempera ture data 1 Normal Top and val ley shot 000A 0006 20_04_24_ AE_30_03 0000 0000 Tempera ture d...

Page 655: ...V 85 mA max for 14 V CRT1 MD16 35 mA max for 24 V 60 mA max for 14 V CRT1 MD16 1 35 mA max for 24 V 60 mA max for 14 V CRT1 ROS08 95 mA max for 24 V 150 mA max for 14 V CRT1 ROF08 60 mA max for 24 V...

Page 656: ...V CRT1 OD16TAH 1 40 mA max for 24 V 70 mA max for 14 V CRT1 MD16TAH 40 mA max for 24 V 70 mA max for 14 V CRT1 MD16TAH 1 40 mA max for 24 V 70 mA max for 14 V CRT1 VID08S 35 mA max for 24 V 50 mA max...

Page 657: ...D32S 1 45 mA max for 24 V 70 mA max for 14 V CRT1 ID32SH 210 mA max for 24 V 235 mA max for 14 V CRT1 ID32SH 1 210 mA max for 24 V 235 mA max for 14 V CRT1 OD32SH 50 mA max for 24 V 90 mA max for 14 V...

Page 658: ...50 mA max for 14 V CRT1 OD08SL 35 mA max for 24 V 55 mA max for 14 V CRT1 OD08SL 1 35 mA max for 24 V 55 mA max for 14 V CRT1 ID16SL 34 mA max for 24 V 55 mA max for 14 V CRT1 ID16SL 1 34 mA max for...

Page 659: ...x for 24 V 80 mA max for 14 V CRT1B ID02S 1 45 mA max for 24 V 65 mA max for 14 V CRT1B OD02S 55 mA max for 24 V 75 mA max for 14 V CRT1B OD02S 1 55 mA max for 24 V 70 mA max for 14 V CRT1B ID02SP 65...

Page 660: ...A max for 24 V 30 mA max for 14 V CRT1B ID04JS 35 mA max for 24 V 40 mA max for 14 V CRT1B ID04JS 1 35 mA max for 24 V 40 mA max for 14 V CRT1B OD04JS 30 mA max for 24 V 35 mA max for 14 V CRT1B OD04J...

Page 661: ...sor s output residual voltage It is sometimes possible to satisfy the above equation by adjusting the I O power supply voltage VCC to 26 4 V Relation between ON Current of Slave Unit with DC Inputs an...

Page 662: ...FF Ileak IOUT OFF current of a Slave Unit with DC Inputs Ileak Sensor s leakage current Connect a bleeder resistor if the Sensor s leakage current is greater than the OFF current of a Slave Unit with...

Page 663: ...nals input current for number of points used cur rent supplied to input devices for number of points used I O power supply current consumption This value does not apply to 2 tier terminal block type s...

Page 664: ...640 I O Power Supply Current Appendix E...

Page 665: ...SV ON BIT NODE ADR 1 2 4 8 16 32 64 014 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 015 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 016 RSV ON BIT NODEADR 1 2 4 8 16 32 64 017 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 0...

Page 666: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 049 RSV ON BIT NODEADR 1 2 4 8 16 32 64 050 RSV ON BIT NODEADR 1 2 4 8 16 32 64 051 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 052 RSV ON BIT NODEADR 1 2 4 8 16 32 64 053...

Page 667: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 084 RSV ON BIT NODEADR 1 2 4 8 16 32 64 085 RSV ON BIT NODEADR 1 2 4 8 16 32 64 086 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 087 RSV ON BIT NODEADR 1 2 4 8 16 32 64 088...

Page 668: ...RSV ON BIT NODEADR 1 2 4 8 16 32 64 113 RSV ON BIT NODEADR 1 2 4 8 16 32 64 114 RSV ON BIT NODEADR 1 2 4 8 16 32 64 115 RSV ON BIT NODEADR 1 2 4 8 16 32 64 116 RSV ON BIT NODE ADR 1 2 4 8 16 32 64 117...

Page 669: ...g 3 communications power supply 85 comparator 4 520 Comparator Result Flag 552 553 CompoNet networks 32 Configurator writing maintenance dates 561 connection object 625 contact operation monitor 2 498...

Page 670: ...moving average processing 508 MS indicators 580 Multi power Supply Slave Units 85 N naming connected devices 3 491 naming Units 3 490 Network Power Supply Slave Units 86 network power voltage monitor...

Page 671: ...ard Window 481 static electricity xxii status areas 120 322 392 408 472 Alarm Status Area 121 324 325 409 473 Warning Status Area 120 323 324 408 472 T Temperature Data Status Flag 370 373 Terminating...

Page 672: ...648 Index...

Page 673: ...outputs with 2 tier terminal block and SSR outputs with 3 tier termi nal block with e CON connector or with screwless clamp terminals 8 point Input 8 point Output Units with 2 tier terminal block wit...

Page 674: ...650 Revision History...

Page 675: ...rg IL 60173 5302 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711...

Reviews: