52
4 STARTUP
4.5 Test operation mode
■
Test operation mode via Ethernet connection
1.
Turn off the power.
2.
Set SW1-1 to "OFF (down)" and SW1-2 to "ON (up)" to set CC-Link IE Field Network Basic communication.
CC-Link IE Field Network Basic communication is not enabled when switches SW1-1 and SW1-2 are set during power-on.
3.
Turn on the servo amplifier.
4.
Set the IP address.
5.
Cycle the power.
6.
Create a multi-axis project with MR Configurator2. For full information, refer to Help of MR Configurator2.
7.
Start operation with the personal computer.
When operation is done with the personal computer, the decimal point on the first digit blinks as follows.
If an alarm or warning occurs during the test operation, the decimal point on the first digit also blinks as follows.
1
ON
2
1
ON
2
Set SW1-1 to "OFF (down)" and SW1-2 to "ON (up)".
After 1.6 s
Blinking
After 0.2 s
After 0.8 s
After 0.8 s
Blinking
Blinking
After 0.2 s