5 CiA 402 DRIVE PROFILE
5.1 State machine control of the servo amplifier
57
5
• State transitions
*1 This is not available with MR-J4-_GF_(-RJ) servo amplifier.
Transition
No.
Event
Remark
(0)
The control circuit power supply is turned on.
Initialization
(1)
The state automatically transitions when the control circuit power
supply is turned on.
Communication setting
(2)
The state transitions with the Shutdown command from the master.
(3)
The state transitions with the Switch on command from the master.
RA turns on.
(4)
The state transitions with the Enable operation command from the
master.
The operation becomes ready after servo-on.
(5)
The state transitions with the Disable operation command from the
master.
The operation is disabled after servo-off.
(6)
The state transitions with the Shutdown command from the master.
RA turns off.
(7)
The state transitions with the Disable Voltage command or Quick
Stop command from the master.
(8)
• The state transitions with the Shutdown command from the
master.
• The state transitions when the main circuit power supply is turned
off.
The operation is disabled after servo-off or RA-off.
(9)
The state transitions with the Disable Voltage command from the
master.
The operation is disabled after servo-off or RA-off.
(10)
The state transitions with the Disable Voltage command or Quick
Stop command from the master.
RA turns off.
(11)
The state transitions with the Quick Stop command from the master.
Quick Stop starts.
(12)
• The state transitions automatically after the completion of Quick
Stop (If the Quick Stop option code is 1, 2, 3, or 4).
• The state transitions with the Disable Voltage command from the
master.
The operation is disabled after servo-off or RA-off.
(13)
Alarm occurrence
Processing against the alarm is executed.
(14)
Automatic transition
After processing against the alarm has been completed, servo-off or
RA-off is performed and the operation is disabled.
(15)
The state transitions with the Fault Reset command from the master.
Alarms are reset.
Resettable alarms can be reset.
(16) (Not
supported)
The state transitions with the Enable Operation command from the
master.
(If the Quick Stop option code is 5, 6, 7, or 8)
The operation becomes ready.