4 STARTUP
4.2 Startup
39
4
4.2
Startup
Confirm that the servo motor operates properly alone before connecting the servo motor with a machine.
Slide switch setting
To switch to CC-Link IE Field Network Basic communication, turn the slide switch 1 (SW1-1) "OFF (down)" and turn the slide
switch 2 (SW1-2) "ON (up)".
Power on
When the main and control circuit power supplies are turned on, "b01" (when the identification number is "01h") appears on
the servo amplifier display.
When the absolute position detection system is used in a rotary servo motor, [AL. 25 Absolute position erased] occurs with
first power on, and the servo-on status cannot be made. Cycle the power to deactivate the alarm.
If the power is switched on when the servo motor is rotated by an external force at a speed of 3000 r/min or higher, it may
cause a position mismatch. Make sure that the servo motor is not rotated before switching the power on.
IP address setting
• Use a twisted pair cable compliant with Ethernet Category 5e (1000BASE-T) or higher as an Ethernet cable.
The maximum cable length between nodes is 100 m.
• Use a hub with a transmission speed of 100 Mbps or faster when branching the Ethernet communication
using a switching hub.
• For a switching hub without the auto-negotiation function, set it to the transmission speed of 100 Mbps and
half duplex.
• The initial value of the IP address is 192.168.3.0.
• The 4th octet can be set to 1 to 255 by using the rotary switches (SW2/SW3).
• Cycle the power of the servo amplifier after changing the parameter setting of the IP address or using the
rotary switches (SW2/SW3).
• The IP address range of CC-Link IE Field Network Basic is from 0.0.0.0 to 223.255.255.254. Set the IP
address within the range.