5-94
SELF DIAGNOSIS FUNCTION
Diagnostic methods : Diagnostic information window, select
Diagnostic indication (Displays fault)
8)
(1)
(2)
Fault code
Description
Fail safe function
F01
Ambient temperature sensor open
20˚C
#
alternate value control
F02
Ambient temperature sensor short
F03
Cab inside temperature sensor open
25˚C alternate value control
F04
Cab inside temperature sensor short
F05
Evaporate temperature sensor open
0˚C
#
alternate value control
F06
Evaporate temperature sensor short
F07
Null
-
F08
Null
-
F09
Mode 1 actuator open/short
The alternate value is face
F10
Mode 1 actuator drive circuit malfunction
If not, the alternate value is Def/Foot
F11
Intake actuator open/short
The alternate value is air recirculation
F12
Intake actuator drive circuit malfunction
The alternate fresh air
F13
Temperature actuator open/short
If opening amount is 0 %, the alternate value is 0 %
F14
Temperature actuator drive circuit malfunction If not, the alternate value is 100 %
F15
Null
-
F16
Null
-