107017-11 EN FR26 GLO 0999 Printed in Germany
2
SPECIFICATIONS
Input
Nominal voltage
120 VAC (-15%, +10%), 230 VAC (-15%, +10%), 24 VDC (-10%, +20%)
Nominal power consumption
24 VDC: 2 W; 230 VAC: 4 VA
Nominal frequency
50 to 60 Hz
Start time
Manual START function: 50 ms (-25%, +50%); Automatic START function: 1 s (-25%,
Nominal voltage at S11
24 VDC with 35 mA current ±25% (provided by control module)
Minimum voltage at S11
21 VDC when activated
Cable resistance between S11/S12
and S21/S22
68 • (max.)
Output
Contact complement
3 NO, 1 NC contacts
Response time
After opening of input (S11/12 or S21/22): 25 ms; Opening in supply circuit (L1(+)/A1): 50
Contact type
Safety relay, positive-guided
Switching capability
Power factor = 1 with resistive load
Current range (min. to max.)
1 mA to 10 A (see caution)
Voltage range (min. to max.)
0.1 to 250 VAC/DC
Typical Electrical Life Espectancy
3A
5A
10A
Power factor = 1 at 230 VAC/DC (note 1)
1,000,000 operations
500,000 operations
220,000 opeerations
Typical Electrical Life Expectancy
0.3
0.5
0.7
1.0
Limitation factor (note 2)
0.45
0.70
0.85
1.00
Operating frequency
600 switching cycles/h
Fuse rating
6 A gL (max.)
Mechanical life
Ten million switching operations
General
Temperature range
-15°C to +55°C (5°F to 131°F) at 90% humidity (max.)
Sealing
Housing IP 40; Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm: Frequency 10 to 55 Hz
Conductor connection
1 x 4 mm² solid (max.) [12 AWG] ot 2 x 1.5 mm² (max.) [16 AWG] stranded wire with sleeve
Conductor attachment
Removable block temrinals with M3,5 screws; wire contacts are enclosed to prevent
Mounting
Quick install rail mounting EN 50022-35
Weight
450 g (0.99 lb.)
NOTE 1: Install arc
suppression device across
load to avoid module contact
arcing and ensure specified
relay life expectancy.
NOTE 2: Total operations =
operations at power factor 1
multiplied by the limitation
factor. if the power factor is
0.5 at 230 vac, 3A
(1,000,000 operations), the
limitation factor is 0.70.
1,000,000 x 0.70 = 700,000
total operations.
FIG 1. CONTACT LIFE FOR
100% RESISTIVE LOAD
(typical)
(note 1)
power factor = 1 (cos
ϕ
)
FIG 2. LIMITATION FACTOR
FOR INDUCTIVE LOADS
(note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability during the lifetime of the contact, NEVER exceed 300 mA and 60 V.
Failure to comply with these instructions will result in product damage.
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...