FF-SPS4 Series Installation Manual
Installation
For application help: call 1-800-537-6945
Honeywell
•
MICRO SWITCH Sensing and Control 23
Test input option
This fail-safe equipment is based upon a permanent self-checking principle which means that
its integrity does not rely upon the use of the test option. However, the test input may be used
to interface the equipment with the machine circuitry to check the correct operation of the Final
Switching Devices K1 and K2 when the equipment is not often triggered by frequent beam
occultations :
A test cycle can be triggered when closing an external NO test contact or when opening an
external NC test contact. The configuration of the type of external test contact (NO or NC
contact) is be done by setting a jumper located behind the emitter side cover. In order to
change the jumper setting, open the emitter by unscrewing the side covers and follow the
following indications :
EMITTER
Jumper position
Test NO test contact (Factory setting)
Jumper position
Test NC test contact
Wiring diagram
Receiver
R1
R2
Neutral
Additional Output
A1
A2
B1
B2
C1
C2
C3
C5
Arc suppressor
(see relay supplier for best value)
100 ms < t < 3,4 s
Hot
Hot
R1
R2
Emitter
FF-SPE
X
q
Emitter
50 mA / 20 Vdc
C4
(+)
C5
(-)
Jumper position (see NOTICE)
Test input :
R1
R2
Machine control
Power
Contacts status
TEST-CONTACT
NO contacts X1 and X2
NC contacts X1 and X2
NO contacts K1 and K2
De-activated
Closed
Open
Closed
Activated
Open *
Closed *
Open *
*Press the restart push-button if necessary.
After activation of the test contact, the NO contacts of the equipment (X1 and X2) are open,
the NC contact of the equipment is closed and the NO contacts of the FSD (K1 and K2) are
open.
NOTICE
1) On delivery, the equipment is configured for the use of a NO test contact.
2) The cyclic use of the test input is easier in the Automatic restart mode or in the start
interlock mode.
3) In the Automatic restart mode, it takes 140 ms for the system to restart after the test
contact is released.
Jumper
location
C4
C5
C4
C5
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...