FF-SRD5985 Series
ISSUE 1
PK 107013-01
2
PK 107013-01-EN FR26 GLO 398 Printed in Germany
SPECIFICATIONS
Input
Nominal voltage
120 VAC (-15%, +10%), 230 VAC (-20%, +10%), 24 VDC (-10%, +20%)
Nominal consumption
120 VAC, 230 VAC: 4 VA; 24 VDC: 2.5 W
Nominal frequency
50 to 60 Hz
Control contacts
Two NO contacts
Nominal voltage at S13/S23
24 VDC / 0VDC (provided by control module)
Nominal input current between S13/S14 and S23/S24
35 mA (ensure 10 mA switching capability with sensors connected to two inputs)
Time required for simultaneous contact closure
of S13/S14 and S23/S24
3 sec (max.)
Output
Contact complement
2 NO contacts
Contact type
Safety relay, positive-guided
Response time
Activation/deactivation by inputs S13/S14 and S23/S24 : 30 ms
Switching Capability
Power factor = 1 with resistive load
Current Range (min. to max.)
1 mA to 10A (see caution)
Voltage Range (min. to max.)
0.1 to 250 VAC/DC
Typical Electrical Life Expectancy
3A
5A
10A
Power factor = 1 at 230 VAC/DC (note 1)
1,000,000 operations
500,000 operations
220,000 operations
Typical Power Factor (cos
ϕϕ
)
0.3
0.5
0.7
1.0
Limitation Factor (note 2)
0.45
0.70
0.85
1.00
Fuse rating
6 A gL (max.)
Mechanical life
Ten million switching operations
General
Temperature range
-15
°
C to + 55
°
C (5
°
F to 131
°
F) at 90% humidity (max.)
Sealing
Housing IP 40 Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm; Frequency 10 to 55 Hz
Conductor connection
1 x 4 mm
2
solid (max.) [12 AWG] or 2 x 1.5 mm
2
(max.) [16 AWG] stranded wire with sleeve DIN
46288
Conductor attachment
M 3,5 screws terminals; wire contacts are enclosed to prevent electrical shock
Mounting
Quick install rail mounting EN 50022-35
Weight
450 g (0.99 lb.)
NOTE 1: Install arc suppression
device across load to avoid
module contact arcing and
ensure specified relay life
expectancy.
NOTE 2:
Total operations =
operations at power factor 1
multiplied by the limitation
factor. If the power factor is 0.5
at 230 vac, 3A (1,000,000
operations), the limitation factor
is 0.70. 1,000,000 x 0.70 =
700,000 total operations.
FIG 1. CONTACT LIFE FOR 100%
RESISTIVE LOAD (typical) (note 1)
power factor = 1 (cos
ϕ
)
FIG 2. LIMITATION FACTOR FOR INDUCTIVE
LOADS (note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability during the lifetime of the contact, NEVER exceed 300 mA and 60 V.
Failure to comply with these instructions will result in product damage.
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...