4.7.2 FSDs monitoring loop (terminals 26-27)
The FSDs monitoring loop is provided by the RESTART input. (see chapter 4.8.2).
The Normally Closed contacts of the two FSDs relays K1 and K2 or FF-SRE extension
module must be connected in series between terminals 26-27 to check correct operation of
the FSDs each time the OSDs outputs switch. If a failure of the FSDs relays K1 and K2 or
FF-SRE extension module is detected, the OSDs outputs remain open until the failure is
removed.
IMPROPER EXTERNAL SAFETY RELAYS PERFORMANCE
•
Use two independent stop circuit safety relays K1 and K2 with mechanically linked
contacts (such as GE CR120 BP Machine Tool Relay or Telemecanique CA3-KN31BD3 or
CA3-DN31BD relay) or FF-SRE extension module to reliably detect a welded contact.
•
Always use the FSD monitoring loop to check correct operation of relays K1 and K2.
Failure to comply with these instructions could result in death or serious injury
Figure 4.12 : Connection of the FSDs monitoring loop
Features
RESTART input
Type
voltage presence and without reference potential
Dynamic signal
pic of 50 mA min.
NC contacts
50 Ohms max. resistance
Protections
galvanic insulation : 500 Vdc
+24Vdc
FF-SRM
+24V
OUTPUT
32
OSD1
OSD2
25
FSD
K1 *
FSD
K2 *
2.5A
Machine
control
circuitry
K1
K2
27
26
RESTART
K1
K2
P/B3
8
2
0 V
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...