Inspection and Maintenance
FF-SM Series Installation Manual
52 Honeywell
•
PK 107007-01 EN FR26 GLO 0298 Printed in France
For application help: see Warranty Information
Inspection
Important Information
The important examination criteria listed in the following two warnings must be strictly
followed, especially if any installation modifications have occurred that may affect operator
safety. The condition of the control unit must be examined regularly. A competent person
designated in writing shall perform regular examinations of the protective safety equipment
and document the examination results. After each maintenance intervention, perform an
operational test and examination of the system.
If a system malfunction occurs, refer to the Indicator Status and Corrective Actions (see page
54) table and the Troubleshooting Flow Diagram for guidance (see pages 55 and 56).
IMPROPER MACHINE GUARDING PROTECTION
•
Refer to and comply with prEN 999 and ANSI standards when calculating safety distances.
•
Design a large enough sensing zone of safety mat(s) to ensure an operator cannot reach a
dangerous machine operation before it can be stopped.
•
Ensure operator detection is effective for the entire sensing zone.
•
When using FF-SM Series safety mats for point-of-operation guarding, DO NOT allow an
operator to stand undetected between the safety mat and dangerous machine operation.
•
If safety mat location allows possible access to dangerous machine operation, install
additional protective safety equipment.
•
To prevent safety mat removal and possible operator injury, secure the safety mat to the
ground using edge trim.
•
Clearing the sensing zone must not start dangerous machine operation. When restarting
machine operation, a normal machine control start sequence must be used.
•
Ensure the location of the manual restart function is outside of the danger zone and
provides the operator with a clear view of the zone.
•
Ensure each safety mat activation immediately stops machine operation within the response
time of the components.
•
Ensure FF-SM status indicators operate properly and are visible from the dangerous area.
Failure to comply with these instructions could result in death or serious injury.
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...