107011-10 EN FR26 GLO 0499 Printed in Germany
3
FIG 3. CURRENT VS. TEMPERATURE LIMIT
F
S
R2501
-22 32 50 68 86 104 122 140 T(°F)
Ambient Temperature
Figure 3. displays the maximal recommended
external temperature versus the total load of all the
safety module contacts. To use this curve, do the
following:
(1) Follow the horizontal line from the value (vertical
axis) equal to the current inside the safety
module contacts and note intersection of the
appropriate curve.
(2) Follow the intersection point down to determine
the maximal recommended ambient
temperature.
(Ex: 4 A current inside each two safety contacts,
then T = 43
°
C (109
°
F).
If the module is located in a higher temperature
environment, the lifetime of the electronic
components may be reduced. Ventilation of the
cabinet may be required.
MECHANICAL INSTALLATION
The FF-SR25980 must be installed inside a NEMA 3
(IEC IP54) rating enclosure or better. The module
can be mounted easily onto a 45mm width DIN rail
(see figures 4 and 5 below for installation and
removal).
FIG 4. MOUNTING DIMENSIONS (
for reference only)
FIG 5. INSTALLATION DIAGRAM
CONTROL RELIABILITY
“Control Reliability” means that “the device, system or
interface shall be designed, constructed and installed
such that a single component failure within the device,
interface or system shall not prevent normal stopping
action from taking place but shall prevent a successive
machine cycle.” (ANSI B11.19-1990, 5.5)
OSHA 29 CFR 1910.217 states that “the control system
shall be constructed so that a failure within the system
does not prevent the normal stopping action from being
applied to the press when required, but does prevent
initiation of a successive stroke until the failure is
corrected. The failure shall be detectable by a simple test,
or indicated by the control system.”
Honeywell uses self-checking techniques that combine
reliability with safety. This means that a faulty component
in our system will make the safety control modules fail in a
safe mode.
The FF-SR25980 safety control module functions with
dual internal channel redundancy and positive self-check
monitoring.
a Width: 45 mm 1.77 in.
b Height: 74 mm 2.91 in.
c Depth: 121 mm 4.76 in.
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...