APPLICATION EXAMPLES
FIG 9. ONE-CHANNEL EMERGENCY STOP CONNECTION
L1 (+)
N (-)
A1(+)
S33
S34
Y2
13
23
14
24
Y1
A2(-)
SRS 5934
F349.eps
(A) This may be an emergency stop push button with a single output safety device in series such as
- safety limit or interlock switches (for example: CLS, GK and GSS).
(B) Manual start mode: Insert start push-button; the jumper between Y1/Y2 is omitted;
Automatic start mode: Insert shunt between Y1/Y2
FUNCTIONAL DESCRIPTION
After activation of the Emergency-stop push button, the K1/K2 will turn OFF, indicating that the two internal safety
relays K1 and K2 are de-energized. The normally open safety outputs 13/14 and 23/24 will open. There exist two
different start modes:
Manual start mode:
The jumper between S33/S4 is omitted (see
(B)).
1. After removing the stop condition, press the START push button to start the safety control module.
2.
The K1/K2 LED will turn ON indicating that the safety relays K1 and K2 are energized. The two normally open
safety contacts will close allowing the machine to operate.
Automatic start mode:
Set the connection between S33/S34 (see
(B)).
1. After removing the stop condition, the safety control module will immediately reset.
2.
The K1/K2 LED will turn ON indicating that the safety relays K1 and K2 are energized. The two normally open
safety contacts will close allowing the machine to operate.
FIG 10. ONE-CHANNEL EMERGENCY STOP CONNECTION (WITH EXTERNAL CONTACTORS
L1 (+)
N (-)
A1(+)
S33
S34
Y2
13
23
14
K3
K4
K3
K4
24
Y1
A2(-)
SRS 5934
F3410.eps
Contact reinforcement through external relays:
For currents higher than 5A, the output contacts can be reinforced by external safety relays. The proper operation of
the external contactors is monitored by looping the NC contacts into the Final Switching Device (FSD) loop between
terminals Y1/Y2.
After activation of the Emergency-stop push button, the K1/K2 LED will turn OFF, indicating that the two internal
safety relays K1 and K2 are de-energized. The normally open safety outputs 13/14 and 23/24 will open and de-
energize the external contactors K3 and K4.
After removing the stop condition, press and release the START push button to start the safety control module. If the
two contactors K3 and K4 are working properly, the K1/K2 LED will turn ON indicating that the safety relays K1 and
K2 are energized. The two normally open safety contacts will close and energize the external contactors K3 and K4.
Fuse
Start push-button
Emergency Stop
Machine Control
Fuse
Emergency Stop
Start
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...