SPECIFICATIONS
Input
Nominal voltage
24 Vac/Vdc (-5%, +10%)
Nominal power consumption
DC: ca. 2 W
Nominal frequency
50 to 60 Hz
Start time
Manual START function: 40 ms
Automatic START function: 500 ms
Nominal voltage at S11
23 Vdc (provided by control module)
Input current between
S11/S12 and S21/S22
40 mAdc
Minimum voltage at S12/A2
21 Vdc when activated
Cable resistance between
S11/S12 and S21/S22
68
Ω
(max.)
Output
Contact complement
2 NO, 1 NC contacts
Response time
Opening of inputs (S11/S12; S21/S22): 15
ms;
Opening in supply circuit (A1(+)/A2(-)): 50 ms
Contact type
Safety relay, positive-guided
Current Range (min. to max.)
Voltage Range (min. to
max.)
Switching Capability per
AC15 (EN 60947-5-1)
1 mA to 7A (see caution)
0.1 to 250 Vac/dc
NO contact: 3 A / 230 V
NC contact: 2A / 230 V
Typical Electrical Life
Expectancy
2A
5A
7A
Power factor = 1 at 230 Vac/dc (see fig. 1,
note 1)
750,000 operations
220,000 operations
110,000 operations
Typical Power Factor (cos
ϕ
)
0.3
0.5
0.7
1.0
Limitation Factor (see fig. 2, note 2)
0.45
0.70
0.85
1.00
Operating frequency
1200 switching cycles/hour (max.)
Output contact fuse rating
Time delay 6 A (max.)
Mechanical life
Ten million switching operations
General
Temperature range
-15
°
C to + 55
°
C (5
°
F to 131
°
F)
at 90% humidity (max.)
Sealing
Housing IP 40; Terminals IP 20
Housing material
Thermoplastic
Vibration resistance
Amplitude 0.35 mm; Frequency 10 to 55 Hz
Wire/conductor connection
1 x 2.5 mm
2
solid (max.) [14 AWG] or 2 x 1.5
mm
2
(max.) [16 AWG] stranded wire with
sleeve DIN 46288
Wire/conductor attachment
Removable terminal strips with M3.5
screws; wire contacts are enclosed to prevent
electrical shock
Mounting
Quick install rail mounting EN 50022-35,
width: 35 mm (1.38 in.)
Weight
220 g (0.49 lb.)
NOTE 1: Install arc suppressors across load to avoid module contact
arcing and ensure specified contact life expectancy.
NOTE 2: Total operations = operations at power factor 1 multiplied by
the limitation factor. If the power factor is 0.5 at 230 Vac, 2A (750,000
operations), the limitation factor is 0.70. 750,000 x 0.70 = 525,000 total
operations.
FIG 1. CONTACT LIFE FOR
100% RESISTIVE LOAD
(typical) (note 1)
power factor = 1 (cos
ϕ
)
ope
ra
tions
switching power [kVA]
]
FIG 2. LIMITATION FACTOR
FOR INDUCTIVE LOADS
(note 2)
power factor < 1 (cos
ϕ
)
CONTACT DAMAGE
To ensure the 1 mA capability
during the lifetime of the
contact, NEVER exceed 300
mA or 60 V.
Failure to comply with these
instructions will result in
loss of low current
switching capability.
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...