10.4 Accuracy
258
Operating temperature and humidity for guaranteed accuracy : 23
5°C (73
41°F), 80% RH or
lower (no dew condensation allowed)
Temperature coefficient: 0.1 x basic accuracy x (T-23) weighted --- operating temperature T [°C]
Warm-up time : 20 min.
• Input crest value is allowed up to 1.5 times the range
• When networks D and F are used, the guaranteed accuracy ranges (full-scale value of each range) are
0.67 and 0.5 times, respectively
• Value calculated based on voltage detected at terminals of a network having a non-inductive resistance
of 1 k
.
• Measurements in voltage measurement mode conform to the accuracy listed below. (1 mA=1 V)
Measurement of DC
Measurement of AC/AC + DC
(During AC measurements, the frequency characteristics of the high-pass filter (fc=4 Hz) is added)
Measurement of ACPeak
(Disabled in network A and B and when the filter is set to Off in network C)
Voltage monitor accuracy(Less than 80 V is indicated as "Less than 80 V")
Current monitor accuracy(Less than 0.5 A is indicated as "Less than 0.5 A")
Measurement method: average value response, effective value conversion
10.4 Accuracy
Current Measurement Section
Range
Guaranteed accuracy range
Measurement resolution
Accuracy
50.00 mA
4.000 mA to 50.00 mA
10
A
± 2.0%rdg.±6dgt.
5.000 mA
0.400 mA to 5.000 mA
1
A
± 2.0%rdg.±6dgt.
500.0
A
40.0
A to 500.0
A
0.1
A
± 2.0%rdg.±6dgt.
50.00
A
4.00
A to 50.00
A
0.01
A
± 2.0%f.s.
Range
Guaranteed
accuracy range
Measurement
resolution
Accuracy
0.1 Hz
f < 15 Hz
15 Hz
f
100 kHz
100 kHz < f
1 MHz
50.00 mA
4.000 mA to
50.00 mA
10
A
± 4.0%rdg.±10dgt.
± 2.0%rdg.±6dgt.
± 2.0%rdg.±10dgt.
5.000 mA
0.400 mA to
5.000 mA
1
A
± 4.0%rdg.±10dgt.
± 2.0%rdg.±6dgt.
± 2.0%rdg.±10dgt.
500.0
A
40.0
A to
500.0
A
0.1
A
± 4.0%rdg.±10dgt.
± 2.0%rdg.±6dgt.
± 2.0%rdg.±10dgt.
50.00
A
4.00
A to
50.00
A
0.01
A
± 4.0%f.s.
± 2.0%f.s.
± 2.0%f.s.
Range
Guaranteed
accuracy range
Measurement resolution Accuracy
15Hz
f 10 kHz
10 kHz <
f
100 kHz
100 kHz < f
1MHz
75.0 mA
8.0 mA to 75.0 mA 100
A
± (2%rdg.±6dgt.)
± 5.0%f.s.
± 15.0%f.s.
10.00 mA
0.80 mA to
10.00 mA
10
A
± (2%rdg.±6dgt.)
± 5.0%f.s.
± 15.0%f.s.
1.000 mA
0.100 mA to
1.000 mA
1
A
± 2.5%f.s.
± 5.0%f.s.
± 15.0%f.s.
500.0
A
40.0
A to
500.0
A
0.1
A
± 4.0%f.s.
± 5.0%f.s.
± 20.0%f.s.
Range
Guaranteed accuracy range
Measurement resolution
Accuracy
300 V
85 V to 275 V
0.1 V
± 5%rdg.±10dgt.
Range
Guaranteed accuracy range
Measurement resolution
Accuracy
20 A
0.5 A to 20 A
0.1 A
± 2%rdg.±5dgt.
Summary of Contents for ST5540
Page 2: ......
Page 6: ...Contents iv Index i ...
Page 29: ...23 2 Chapter 2 Instrument Labels and Screens Instrument Labels and Screens Chapter 2 ...
Page 80: ...4 8 Changing the Measurement Method Auto Manual 74 ...
Page 121: ...115 8 9 7 Chapter 7 Instrument System Settings Instrument System Settings Chapter 7 ...
Page 144: ...7 14 Setting the Backlight 138 ...
Page 284: ...10 14 Measurement Networks 278 ...
Page 290: ...11 4 Instrument Disposal 284 ...
Page 320: ...Appendix4 External Dimensions A30 ...
Page 323: ......
Page 324: ......
Page 325: ......
Page 326: ......