E L C P r o g r a m m i n g M a n u a l
F o r
m o r e
i n f o r m a t i o n v i s i t :
w w w. e a t o n . c o m
M N 0 5 0 0 3 0 0 3 E
3 - 3 8 6
Description: (ELCM-PH/PA)
1.
S
is the designated pulse output frequency. Available range: -100,000Hz ~ +100,000 Hz. “+/-”
signs indicate forward/reverse output direction. The frequency can be changed during pulse
output execution. However, if the specified output direction is diferent from the current output
direction, the instruction will stop for 1 scan cycle then restart with the changed frequency.
2.
D
1
is the pulse output address. It can use CH0(Y0) and CH1(Y2).
3.
D
2
is the direction signal output device. It can use CH0(Y1) and CH1(Y3).
4.
The operation of
D
2
corresponds to the “+” or “-“ of
S
. When
S
is “+”,
D
2
will be OFF; when
S
is “-“,
D
2
will be ON.
5.
M1305 and M1306 can change the output direction of CH0
/
CH1 set in
D
2
. When
S
is “-“,
D
2
will be ON, however, if M1305/M1306 is set ON before instruction executes,
D
2
will be OFF
during execution of instruction.
6.
PLSV instruction does not support the settings for ramp up or ramp down. If ramp up/down is
needed, use API 67 the RAMP instruction.
7.
If the drive contact turns off during the pulse output process, the pulse output will stop
immediately.
Program Example:
When M10 = ON, Y0 will send pulses at 20kHz. Y1 = OFF indicates forward direction.
M10
DPLSV K20000
Y0
Y1
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...