E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-104
Application example for Alarms:
X0=forward
switch
X1=backward
switch
X2=front location switch
X3=back location switch
X4=alarm device reset button
Y0=forward Y1=forward
Y2=alarm indicator
S910=forward alarm device
S920=backward alarm
Y0
ANS
T0
K100
S910
X2
X4
ANRP
M1000
M1049
Y1
ANS
T1
K200
S920
X3
X0
Y0
X2
M1048
Y2
Y0
X1
Y1
X3
Y1
1.
When M1049=ON, Alarms are enabled. If M1048=ON, an alarm has occurred,
D1049=lowest alarm number.
2.
If Y0=ON > 10 seconds and has not reached the front location X2, S910=ON.
3.
If Y1=ON > 20 seconds and not reached the back location X3, S920=ON.
4.
When X1=ON, and Y1=ON, and X3=ON, Y1 = OFF.
5.
If an alarm occurs, alarm indicator Y2=ON.
6.
Each alarm that is activated will be reset one by one, each time the reset button X4 = ON
during the execution of this instruction. The lowest numbered alarm is reset every execution
of this instruction.