3 . I n s t r u c t i o n S e t
M N 0 5 0 0 3 0 0 3 E F o r m o r e
i n f o r m a t i o n
v i s i t :
w w w. e a t o n . c o m
3 - 3 6 3
Register
Data
Descriptions
D1263 Low byte
‘3’
33 H
D1263 High byte ‘4’
46 H
D1264 Low byte
‘1’
33 H
D1264 High byte ‘2’
46 H
Data contents
1234H
Content of register D0
D1265 Low byte
‘9’
39 H
LRC CHK 1
D1265 High byte ‘3’
33 H
LRC CHK 0
Checksum: LRC CHK (0,1)
Received data
Register
Data
Descriptions
D1070 Low byte
‘0’
30 H
ADR 1
D1070 High byte
‘1’
31 H
ADR 0
D1071 Low byte
‘0’
31 H
CMD 1
D1071 High byte
‘F’
46 H
CMD 0
D1072 Low byte
‘0’
30 H
D1072 High byte
‘5’
35 H
D1073 Low byte
‘0’
30 H
D1073 High byte
‘0’
30 H
Data Address
D1074 Low byte
‘0’
30 H
D1074 High byte
‘0’
30 H
D1075 Low byte
‘1’
31 H
D1075 High byte
‘0’
30 H
Number of Data(count by bit)
D1076 Low byte
‘D’
44 H
LRC CHK 1
D1076 High byte
‘B’
42 H
LRC CHK 0
z
RTU mode (M1143 = ON)
When X0 = ON, MODRW instruction executes the function specified by Function Code H0F
ELC1
Ö
ELC2
,
ELC1 sends: “01 0F 0500 0010 02 34 12 21 ED”
ELC2
Ö
ELC1
,
ELC1 receives: “01 0F 0500 0010 54 CB”
Data to be sent
Register
Data
Descriptions
D1256 Low byte
01 H
Address
D1257 Low byte
0F H
Function
D1258 Low byte
05 H
D1259 Low byte
00 H
Data Address
D1260 Low byte
00 H
D1261 Low byte
10 H
Number of Data(count by bit)
D1262 Low byte
02 H
Byte Count
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...