b1
b2
Parity
00:None
01:Odd
11: Even
b3
Stop bits
0: 1 bit, 1: 2 bits
0001 (H1): 110
0010 (H2): 150
0011 (H3): 300
0100 (H4): 600
0101 (H5): 1200
0110 (H6): 2400
0111 (H7): 4800
1000 (H8): 9600
1001 (H9): 19200
1010 (HA): 38400
1011 (HB): 57600
1100 (HC): 115200
b4
b5
b6
b7
Baud rate
1101 (HD): 500000
1110 (HE): 312500
1111 (HF): 921000
(ELCM COM2 /
COM3 support)
b8
Select start bit
0: None
1: D1124
b9
Select the 1
st
end bit
0: None
1: D1125
b10
Select the 2
nd
end bit
0: None
1: D1126
b11~b15
Reserved (leave at 0)
Default data packet format for all ports is: 7 data bits, 1 stop bit, Even parity, 9600 baud. If a