3 . I n s t r u c t i o n S e t
M N050 03003E F or mo re infor ma tio n vi sit:
w w w. e a t o n . c o m
3-161
D1371: Time unit of CH0 output pulses when M1070 = On.
D1372: Time unit of CH1 output pulses when M1071 = On.
D1373: Time unit of CH2 output pulses when M1530 = On.
D1374: Time unit of CH3 output pulses when M1531 = On.
D1375: Low word of the current number of output pulses from CH2.
D1376: High word of the current number of output pulses from CH2.
D1377: Low word of the current number of output pulses from CH3.
D1378: High word of the current number of output pulses from CH3.
3. Flags and special registers for ELCM-PH/PA series ELC:
M1070: Switching clock pulse of Y1 for PWM instruction (ON:100 us, OFF: 1ms)
M1071: Switching clock pulse of Y3 for PWM instruction (ON:100 us, OFF: 1ms)
D1032: Low word of the present value of Y1 pulse output
D1033
High word of the present value of Y1 pulse output
D1338: Low word of the present value of Y3 pulse output.
D1339: High word of the present value of Y3 pulse output.
4. Time unit settings for ELC-PV series:
You cannot modify M1070 in the program.
D1371, D1372, D1373 and D1374 determine the time units of the output pulses for CH0, CH1,
CH2 and CH3. The default setting is K1. If the value is not within range, the default value will be
used.
D1371, D1372, D1373, D1374
K0
K1
K2
K3
Time unit
10us
100us
1ms
10ms
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...