M1130
0
1
0
D1124: user defined
D1125: user defined
D1126: user defined
D1124: H 0002
D1125: H 0003
D1126: H 0000 (no setting)
M1
12
6
1
D1124: user defined
D1125: user defined
D1126: user defined
D1124: H 003ª (’:’)
D1125: H 000D (CR)
D1126: H 000A (LF)
7.
Example of setting communication format in D1120:
Communication format:
Baud rate: 9600, 7, N, 2
STX: “: “
ETX1: “CR”
ETX2: “LF”
Check to the table in point 4 and the set value H788 can be referenced corresponding to the
baud rate. Set the value into D1120.
b15
b0
0 0 0 0 0 1 1 1 1 0 0 0 1 0 0 0
7
8
8
D1120
0
N/A
MOV
H788
D1120
M1002
When STX, ETX1 and ETX2 are applied, care should be taken on setting the ON/OFF status
of M1126 and M1130.
8. D1250(COM1)
、
D1253(COM3) communication error code:
Value
Error Description
H0001 Communication
time-out
H0002 Checksum
error
H0003
Exception Code exists
H0004
Command code error / data error
H0005
Communication data length error
9.
Corresponding table between D1167~D1169 and the associated interrupt pointers. (Only
lower 8 bits are valid)
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...