3 . I n s t r u c t i o n S e t
M N 0 5 0 0 3 0 0 3 E F o r m o r e
i n f o r m a t i o n
v i s i t :
w w w. e a t o n . c o m
3 - 3 5 3
z
RTU mode (COM3: M1320 = ON COM1: M1139 = ON):
When X0 = ON, MODRW instruction executes the function specified by Function Code 03
ELC
Ö
the drive, ELC sends: ” 01 03 0708 0006 45 7E”
The drive
Ö
ELC, ELC receives: “01 03 0C 0000 0503 0BB8 0BB8 0000 012D 8E C5”
Registers for received data
Register
Data
Descriptions
D0 0000
H
ELC converts data in 0708 H and stores the converted data
automatically.
D1 0503
H
ELC converts data in 0709 H and stores the converted data
automatically.
D2 0BB8
H
ELC converts data in 070A H and stores the converted data
automatically.
D3 0BB8
H
ELC converts data in 070B H and stores the converted data
automatically.
D4 0136
H
ELC converts data in 070C H and stores the converted data
automatically.
D5 012D
H
ELC converts data in 070D H and stores the converted data
automatically.
Program example 5: COM2(RS-485), Function Code H05
1.
Function code K5(H05): Force ON/OFF
bit device
2.
ELC1 connects to ELC2: (M1143 = OFF, ASCII mode), (M1143 = ON, RTU Mode)
3.
n
= 1 indicates Force ON (set FF00H) and
n
= 0 indicates Force OFF (set 0000H)
4.
For ASCII or RTU mode, ELC COM2 stores the data to be sent in D1256~D1295 and stores
the received data in D1070~D1085
5.
Take the connection between ELC1 (ELC COM2) and ELC2 (ELC COM1) for example, the
tables below explain the status when ELC1 Force ON ELC2 Y0.
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...