Program Example 2:
1. Timing diagram and program control:
Y0
Y1
D0=k40
D0=k10
4sec
2sec
1
2
3
4
M0
T0
5sec
D0=
k-1
M0
K50
CVM
D0
K50
Y0
D0
T0
TMR
MOV
k-1
T0
2. Control
phases:
1) Phase
1
: When M0 = On, because the valve position is not known, set D0 = K-1 to
deliberately close the valve (Y0 = Off, Y1 = On) for 5 seconds and make sure the valve is
at the position of 0 seconds before moving on to the next step.
2) Phase
2
: When T0 = On, allow D0 = K40 to begin execution. Open the valve (Y0 = On,
Y1 = Off) for 4 seconds, moving the valve to the position of 4 seconds.
3) Phase
3
: Change the position of the valve and make D0 = K10. Because the previous
position was at 4 seconds, the valve shall be closed (Y0 = Off, Y1 = On) for 3 seconds,
moving the valve to the position of 1 second.
4) Phase
4
: Switch off M0 and the valve will no longer move (Y0 = Off, Y1 = Off).