EL C Pro g rammi ng Manu al
F O R MORE INFORM AT ION VISIT: WWW.E ATON.COM MN05003003E
2-98
Function
D1116
Analog output channel 0 (DA 0).
D1117
Analog output channel 1 (DA 1).
D1118
Analog input filter setting (ms).
For ELC-PA controllers, sampling time of analog/digital conversion Sampling time
will be regarded as 5ms If D1118
≦
5.
For ELCM-PA controllers, sampling time of analog/digital conversion Sampling
time will be regarded as 2ms If D1118
≦
2.
Function Group
Algorithm Error Flag
Number
M1067~M1068, D1067~D1068
Contents:
Algorithm error flag:
Component
Explanation
Latched
STOP
→
RUN
RUN
→
STOP
M1067
Algorithm error flag
None
Clear
Latched
M1068
Algorithm error lock flag
None
Unchanged
Latched
D1067
Algorithm error code
None
Clear
Latched
D1068
STEP value of algorithm error
None
Unchanged
Latched
Error code explanation:
D1067
error code
Function
0E18
BCD conversion error
0E19
Divisor is 0
0E1A
Usage exceeds limit (include E and F)
0E1B
It is negative number after doing radical
0E1C
FROM/TO communication error
Function Group
Low Voltage
Number
M1087, D1100
Contents:
1.
When the ELC detects LV (Low Voltage) signal, it will check if M1087 is “ON” or not. If M1087
is “ON”, the content in D1100 will be stored in Y0 ~ Y17.
2.
Bit0 (LSB) of D1100 corresponds to Y0, bit1 corresponds to Y1, bit8 corresponds to Y10 and
so on.
Function Group
File Register
Number
M1101, D1101~D1103
Contents:
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...