E L C P r o g r a m m i n g M a n u a l
F o r m o r e i nf o r m a t i o n v i sit :
w w w. e a t o n . c o m
MN05003003E
3-6
Mnemonic Operands
Function
Program steps
MPS
X, Y, M, S, T, C
Store the current result of the internal ELC
operations
1
ELC ELCB
ELCM
PB
PC/PA/PH
PV
PB
PH/PA
Description:
MPS stores the connection point of the ladder circuit so that further coil branches can recall the
value later.
Mnemonic Operands
Function
Program steps
MRD
X, Y, M, S, T, C
Reads the current result of the internal ELC
operations
1
ELC ELCB
ELCM
PB
PC/PA/PH
PV
PB
PH/PA
Description:
MRD recalls or reads the previously stored connection point data and forces the next contact to
connect to it.
Mnemonic Operands
Function
Program steps
MPP
X, Y, M, S, T, C
Pops (recalls and removes) the currently
stored result
1
ELC ELCB
ELCM
PB
PC/PA/PH
PV
PB
PH/PA
Description:
MPP pops (recalls and removes) the stored connection point. First, it connects the next contact,
then it removes the point from the temporary storage area.
Basic points to remember:
1.
Use these instructions to connect output coils to the left hand side of a contact. Without these
instructions connections can only be made to the right hand side of the last contact.
2.
For every MPS instruction there MUST be a corresponding MPP instruction.
3.
The last contact or coil circuit must connect to an MPP instruction.
4.
At any programming step, the number of active MPS-MPP pairs must be no greater than 8.
Summary of Contents for ELC-PB
Page 1: ......
Page 5: ...For more information visit www eaton com MN05003003E iv...
Page 29: ...ELC Programming Manual For more information visit www eaton com MN05003003E 1 24 MEMO...
Page 502: ...3 Instruction Set MN05003003E For more information visit www eaton com 3 333...
Page 601: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 432...
Page 625: ...ELC Programming Manual For more information visit www eaton com MN05003003E 3 456...